EXTERIOR VENT LOCATIONS AND RESTRICTIONS
FIGURE 3: Exterior Vent Locations
∨
-
Vent Terminal
∧
-
Air Supply Inlet
≡
-
Area where terminal is
not permitted
A =
Clearance above grade, veranda, porch, deck, or bal-
cony (*12 inches (30 cm) minimum)
H =
*Not to be installed above a meter/regulator assembly
within three feet (90 cm) horizontally from the center-line
of the regulator
B =
Clearance to window or door that may be opened
(*12 inches (30 cm) minimum.
I =
Clearance to service regulator vent outlet (*6 feet (1.8m)
minimum)
C =
Clearance to permanently closed window (minimum 12
inches (30 cm) recommended to prevent condensation
on window)
J =
Clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance.
(*12 inches (30 cm) minimum.
D =
Vertical clearance to ventilated soffits located above the
terminal within a horizontal distance of two feet (60
cm) from the center-line of the terminal (18 inches (46
cm) minimum). Vinyl surfaces require 24 inches (60
cm).
K =
Clearance to a mechanical air supply inlet (*6 feet (1.8 m)
minimum)
E =
Clearance to unventilated soffits (12 inches (30 cm)
minimum). Vinyl surfaces require 24 inches (60 cm).
L =
† Clearance above paved side-walk or a paved driveway
located on public property (*7 feet (2.1 m) minimum)
F =
Clearance to outside corner - six inches (15 cm)
M =
Clearance under veranda, porch, deck, or balcony (24
inches (61 cm) minimum ‡)
G =
Clearance to inside corner - 12 inches (30 cm). Vinyl
surfaces require 24 inches (60 cm).
† A vent shall not terminate directly above a sidewalk or paved driveway, which is located between two single-family
dwellings and serves both dwellings.
‡ Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.
* As specified in
CGA B1: 19 Installation Codes (1991).
Note
: Local codes or regulations may require different clear-
ances.
8
Содержание DXV42 TIMBERFIRE
Страница 21: ...2 0...
Страница 22: ...2 1...
Страница 23: ...2 2...
Страница 24: ...2 3...
Страница 40: ...TAPE SHUT POSTAGE NEEDED JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 3 9...
Страница 41: ...4 0 NOTES...
Страница 42: ...4 1 NOTES MENDOTA EXTENDED LIFETIME PROTECTION AND LIMITED WARRANTY...