6

CORRECT GAS PRESSURE AND PROPER GAS SUPPLY LINE SIZING ARE IMPERATIVE TO THE SUCCESSFUL PERFORMANCE OF YOUR 
MENDOTA GAS FIREPLACE.  BE SURE THE GAS SUPPLIER OR PLUMBER CAREFULLY CHECKS FOR CORRECT GAS PRESSURE AND GAS 
LINE SIZING WHEN INSTALLING THE FIREPLACE. 

IT IS CRITICAL TO CAREFULLY CHECK FOR GAS LEAKS WHEN HOOKING UP THE FIREPLACE -- CHECK WITH SOAP & WATER SOLUTION. 

BE SURE TO INSTALL "APPROVED" FLEX GAS LINE WITH BRASS-TO-BRASS FITTINGS TO PREVENT GAS LEAKS AT CONNECTIONS. 

GAS SUPPLY PIPING MUST INCLUDE A DRIP LEG TO ELIMINATE THE POSSIBILITY OF CONTAMINANTS ENTERING THE GAS TRAIN.   
ADHERE STRICTLY TO LOCAL AND NATIONAL CODES FOR ENTIRE INSTALLATION. 

 

GAS SUPPLY LINE SIZING

 

The Mendota Gas Fireplace comes equipped with a 3/8" N.P.T. (1.Ocm) inlet on the main gas valve.  This 
may be removed if a ½" flexible connector is used.  Gas supply piping can enter the Fireplace cabinet from 
either the left or right side. 

Install an approved individual shut-off valve in supply line to the fireplace.  The appliance and its individ-
ual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of 
that system at test pressures in excess of 1/2 PSIG (3.5 kPa). 

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off 
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 
PSIG (3.5 kPa). 

The proper gas line diameter must be selected to run from the supply regulator to the Fireplace. Refer to the 
following table for proper gas pipe diameters.  Strictly adhere to the correct pipe sizes. 

 

PIPE LENGTH 

(FEET) 

SCHEDULE 40 PIPE 

INSIDE DIA. 

TUBING, TYPE L 

OUTSIDE DIA. 

 NAT. 

L.P. 

NAT. 

L.P. 

0-10 

1/2"   (1.3 cm) 

3/8"   (1.0 cm) 

1/2"   (1.3 cm) 

3/8"   (1.0 cm) 

10-40 

1/2"   (1.3 cm) 

1/2"   (1.3 cm) 

5/8"   (1.6 cm) 

1/2"   (1.3 cm) 

40-100 

1/2"   (1.3 cm) 

1/2"   (1.3 cm) 

3/4"   (2.0 cm) 

1/2"   (1.3 cm) 

100-150 

3/4"   (2.0 cm) 

1/2"   (1.3 cm) 

7/8"   (2.3 cm) 

5/8"   (1.6 cm) 

150-200 

3/4"   (2.0 cm) 

1/2"   (1.3 cm) 

7/8"   (2.3 cm) 

3/4"   (2.0 cm) 

NOTE:

  

Some areas allow copper tubing or galvanized pipe - check with local approval agencies and codes NEVER use plastic pipe.

 

 
 

GAS PRESSURE CHECKING REQUIREMENTS 

Inlet and manifold gas pressure checking taps are located on gas valve. (See 

FIGURE 2

 pg. 6)  A qualified 

installer should use these fittings for setting the correct gas pressure during initial installation. 
 

NOTE: 

DO NOT DAMAGE OR KINK THE FLEX CONNECTOR.  CHECK FOR GAS LEAKS  

 

WITH SOAP AND WATER SOLUTION. 

NOTE: 

3/8" FLEX OR RIGID PIPING MAY BE USED TO CONNECT GAS SUPPLY TO 
UNIT DEPENDING ON STATE AND LOCAL CODES. 

NOTE:    BE SURE TO INSTALL FLEX GAS HOSE WITH BRASS-TO-BRASS FITTINGS TO  
                PREVENT LEAKS AT CONNECTION. 

NOTE:    THE HARD PLUMBING FITTING IS TO BE USED WITH INSTALLATIONS 

REQUIRING HARD PLUMBING.  IT MAY BE REMOVED IF THE FIREPLACE IS 
BEING INSTALLED WITH A FLEXIBLE CONNECTOR. 

Содержание DXV42 TIMBERFIRE

Страница 1: ...S 3 DO NOT TRY TO LIGHT ANY APPLIANCE 4 EXTINGUISH ANY OPEN FLAME 5 DO NOT USE THE PHONE IN YOUR BUILDING 6 IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S PHONE 7 FOLLOW THE GAS SUPPLIERS INSTRU...

Страница 2: ...DXV 42 NAT GAS 40 000 27 000 BTUH MODEL DXV 42 L P GAS 38 500 22 000 NOTE AN LP CONVERSION KIT MUST BE PURCHASED SEPARATELY FOR THIS FIREPLACE SEE PG 33 MAIN ORIFICE 30 NAT GAS 49 L P GAS OVERALL EFFI...

Страница 3: ...r and any adjustments to logs or burner must be done by a qualified service person The Fireplace should be inspected before use and at least annually by a professional service person More frequent cle...

Страница 4: ...es 8 17 Observe the restrictions relating to vent position on exterior of home see pg 8 HEATING PERFORMANCE Mendota Gas Built in Fireplaces are true high efficiency gas heaters With its high heat outp...

Страница 5: ...13 This requires 20 minimum to cen ter of opening for the horizontal pipe to exit the wall CAUTION If 90 elbows must be used with LPG a 3 foot vertical starter section must be used directly off the t...

Страница 6: ...erlay nailing flanges and come in contact with the edges of the black front surface but may not overlay the 2 black surface Noncombustible material such as marble or brick can be installed over the 2...

Страница 7: ...alve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG 3 5 kPa The proper gas line diameter must be selected to run from the supply regulator...

Страница 8: ...ace an additional inches to inches regulator must be installed for the Fireplace EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the residence in which case pounds to inches regulators are u...

Страница 9: ...rminal within a horizontal distance of two feet 60 cm from the center line of the terminal 18 inches 46 cm minimum Vinyl surfaces require 24 inches 60 cm K Clearance to a mechanical air supply inlet 6...

Страница 10: ...ts own separate vent system Common vent systems are prohibited To assure proper venting performance of the high performance Mendota Direct Vent Fireplaces and Stoves it is critical that the DuraVent G...

Страница 11: ...FLASHING 0 12 TO 6 12 10 ROOF FLASHING 7 12 TO 12 12 11 STORM COLLAR 12 VERTICAL VENT CAP 13 SUPPORT BAND 14 HORIZONTAL VENT CAP 15 FIRESTOP SPACER 1 0 Figure 5 Flue Venting Components For all DuraVe...

Страница 12: ...OF VERTICAL PIPE AND ONE 90O ELBOW CAN BE USED IF NO HORIZONTAL VENT SECTIONS GREATER THAN 7 ARE USED ALL OTHER INSTALLATIONS MUST FALL WITHIN ABOVE SHADED AREA NOTE THE SHORTEST HORIZONTAL RUN OF 7 6...

Страница 13: ...TION CAN BE USED FOR HORIZONTAL RUNS WARNING For L P gas and high altitude installations above 4 000 ft but below 7 500 ft 45 elbows must be used in place of 90 elbows NOTE This requires 32 minimum he...

Страница 14: ...the way when venting system is attached If this is the case you may want to adjust the fireplace location 2 Measure from the top of the fireplace up minimum 17 to centerline of 90 elbow See FIGURE 1 P...

Страница 15: ...4DF FLASHING 0 12 6 12 PITCH 45 01 00202 4DF12 FLASHING 6 12 12 12 PITCH 45 01 00203 4DSC STORM COLLAR 45 01 00204 4DAIS12 ATTIC INSULATION SHIELD 45 01 00206 4DCACL CO LINEAR APPLIANCE ADAPTOR 45 01...

Страница 16: ...penetrate the outside wall Since vent pipe sections overlap we suggest pre assembling and measuring the total vent pipe run so you can more accurately locate the point where the vent pipe will penetra...

Страница 17: ...f all Duravent pipe sections 5 Cut a 9 x 9 opening in the roof centered in the small drilled hole placed in the roof in No 1 The opening should be a sufficient size to meet all clearance requirements...

Страница 18: ...IMENSION ROOF PITCH FEET METERS FLAT to 6 12 2 6 7 12 to 9 12 2 6 10 12 to 12 12 4 1 2 13 12 to 16 12 6 1 8 17 12 to 21 12 8 2 4 1 7 9 Complete installation with storm collar and vent cap ROOF TERMINA...

Страница 19: ...3 Door Holding Tabs on firebox top 2 Lower door so the 3 Tabs on firebox top fit through the 3 slots on the doorframe i e Hang door on the 3 Tabs 3 Swing in the lower edge of door until it touches low...

Страница 20: ...ont surfaces of log for additional glow Add wool to burned out space between front logs Fill area to back burner WARNING Do not block holes with excessive wool Delayed ignition and sooting can occur 4...

Страница 21: ...2 0...

Страница 22: ...2 1...

Страница 23: ...2 2...

Страница 24: ...2 3...

Страница 25: ...and gas supply must be installed in accordance with in structions and local and national codes LIGHTING CHECK OFF LIST All items on Installation Check Off List see above must be completed Connect ther...

Страница 26: ...y hanging slots on upper edge of door over tabs on upper edge of firebox opening Then swing in lower edge of door Carefully pull out the two 2 Spring Loaded Door Holding Bars located under the doorfra...

Страница 27: ...ALWAYS WAIT 60 SECONDS When using remote control be sure to hold in button firmly until unit lights DO NOT push button and release quickly before burner lights Burner should light IMMEDIATELY and the...

Страница 28: ...ervicing BLOWER WIRING DIAGRAM BLOWER OPERATION The Mendota DXV Fireplace is designed so the blower operates at all times the fireplace is operating The blower output can be regulated with the rheosta...

Страница 29: ...ir Shutter MAIN BURNER GAS FLAME ADJUSTMENT During initial installation the burner should be removed by qualified person and the air shutter opening checked to be certain that the shutter is set corre...

Страница 30: ...xterior glass may be cleaned with cleaner as desired Interior glass use soap and water Kel Kem Glass Cleaner or equivalent CAUTION Do Not use oven cleaner to clean glass NOTE Additives that are put in...

Страница 31: ...COMBUSTION SYSTEM MILLIVOLT READING Millivolt readings must be taken by a qualified installer at the time of installation and after any interruption in burner operation These readings will establish...

Страница 32: ...ed with cleaner as desired Interior glass use KEL KEM Polish Plus 65 06 00455 or comparable product Do Not use oven cleaner or abrasive cleaners to clean glass DO NOT CLEAN WHEN GLASS IS HOT 4 PERIODI...

Страница 33: ...1 00416 49 drill see pg 28 for location Orifice is removed and installed with a deep well socket and ratchet 2 Install pilot orifice 05 04 00036 014 see pg 31 for location Remove and install pilot hoo...

Страница 34: ...LOWER WITH MOTOR 15 02 00065 L H BLOWER WITH MOTOR HA 20 00152 VALVE ASSEMBLY WITH LP CONVERSION 05 02 00293 VALVE NAT GAS 15 02 00062 BLOWER ASS Y 05 02 00294 LP PLUG FOR NAT GAS VALVE 05 01 00157 TH...

Страница 35: ...to that shown in the diagram below Any material that protrudes into this area on the sides top or bottom edges can only be flush with the front surface of the fireplace faceplate If planning to instal...

Страница 36: ...imum Required dimensions shown in the diagram be low must be left bare and uncovered Hearth Protection Pad Installation Information when planning to Install the Deerfield Front If planning to install...

Страница 37: ...nner perimeter of the Fireplace s Faceplate The bottom member of this trim however overlaps the bottom 2 black boarder of the fire place front faceplate Therefore DO NOT COVER THE BOTTOM 2 BOARDER OF...

Страница 38: ...in w c 1 7 3 6 Minimum Inlet Pressure in w c 5 0 11 0 _______________________________________________ This appliance is equipped for installation at 0 610 meters This appliance must be installed in a...

Страница 39: ...GAS LEAKS Per Manual CHECK FOR CORRECT GAS PRESSURE AT MANIFOLD Per Manual a 3 5 Inches Water Column Maximum Nat Gas b 10 5 Inches Water Column Maximum L P Gas TAKE COMBUSTION SYSTEM MILLIVOLT READIN...

Страница 40: ...TAPE SHUT POSTAGE NEEDED JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 3 9...

Страница 41: ...4 0 NOTES...

Страница 42: ...4 1 NOTES MENDOTA EXTENDED LIFETIME PROTECTION AND LIMITED WARRANTY...

Страница 43: ...rmine whether the claimed damage or malfunction was caused by abuse improper installation or other cause outside this warranty Mendota is not responsible for any repairs or material purchases that hav...

Страница 44: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBSITE WWW JOHNSONGAS COM or WWW MENDOTAHEARTH COM 0904 Part 65 05 00092...

Отзывы: