9.2.2
Example of a flexible pipe connection on the extract air and/or supply air
side (multi-room version, only when connecting a flexible pipe system)
► Create the channels for the flexible pipe connection according to whether you intend
to connect the flexible pipe system on the extract air side, supply air side or on both
sides.
— Example: Flexible pipe connection
on the extract air side
(item 1 in Fig. 14)
— Example: Flexible pipe connection
on the supply air side
(item 1 in Fig. 15)
► Create one channel for the flexible pipe 170 mm wide and 85 mm deep as far as the
flexible pipe outlet in the ceiling.
► Check that the installation kit fits easily into the wall aperture.
Fig. 14:
Creating channels for flexible pipe
connection on extract air side, dimensions
in millimetres (schematic representation)
218
170
85
218
104
1
Fig. 15:
Creating channels for flexible pipe
connection on supply air side, dimensions
in millimetres (schematic representation)
218
104
218
85
170
1