Installation manual
M-WRG-S...
- 22 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
►
Completely fill the cavities between the core drill holes and ventilation pipes with
expanding foam.
►
Wait until the expanding foam has cured.
10.8
Running the connecting cables
DANGER
Potentially fatal voltages.
—
The electrical installation work must only be carried out by a qualified electrician.
—
The VDE regulations or any special safety regulations applicable in your country apply to
the electrical installation work.
►
Disconnect the mains cable for connecting to the ventilation unit on all poles from the
mains supply.
►
Make sure that the mains supply cannot be switched on again.
NOTE
—
Table 4 on page 22 and Table 5 on page 23 contain overviews of the recommended
mains cable and control cable types.
—
A control cable is only needed for certain types of ventilation unit.
—
The ventilation unit (constructed 2018 or later) is equipped with an external control input as
standard. The mains cable
NYM-J 4 x 1.5 mm
2
is needed if this control input is used.
Part no.
Type of ventilation unit Type of mains cable
Type of control cable
5010
M-WRG-S
NYM-J 3 x 1.5 mm
2
or
NYM-J 4 x 1.5 mm
2
(*)
-
5016-1-0
M-WRG-S/Z-S
NYM-J 3 x 1.5 mm
2
or
NYM-J 4 x 1.5 mm
2
(*)
J-Y (St) Y 4 x 2 x 0.6 mm or
J-Y (St) Y 4 x 2 x 0.8 mm
5016-1-1
5016-1-1-1
5016-1-1-2
M-WRG-S/Z-T
M-WRG-S/Z-T-F
M-WRG-S/Z-T-FC
NYM-J 3 x 1.5 mm
2
or
NYM-J 4 x 1.5 mm
2
(*)
J-Y (St) Y 10 x 2 x 0.6 mm or
J-Y (St) Y 10 x 2 x 0.8 mm
5016-1-2
5016-1-2-1
5016-1-2-2
5016-2-2
M-WRG-S/Z-KNX
M-WRG-S/Z-KNX-F
M-WRG-S/Z-KNX-FC
M-WRG-S/Z-EIB
NYM-J 3 x 1.5 mm
2
or
NYM-J 4 x 1.5 mm
2
(*)
J-Y (St) Y 2 x 2 x 0.8 mm or
EIB-Y (St) Y 2 x 2 x 0.8 mm
5016-2-1
M-WRG-S/Z-24
NYM-J 3 x 1.5 mm
2
or
NYM-J 4 x 1.5 mm
2
(*)
J-Y (St) Y 4 x 2 x 0.6 mm or
J-Y (St) Y 4 x 2 x 0.8 mm
5013
5014-1
5014-2
M-WRG-S 485
M-WRG-S 485-TF
M-WRG-S 485-TFC
NYM-J 3 x 1.5 mm
2
or
NYM-J 4 x 1.5 mm
2
(*)
J-Y (St) Y 3 x 2 x 0.6 mm or
J-Y (St) Y 3 x 2 x 0.8 mm
Table 4: Types of mains cable and control cable for each ventilation unit type
(*) If the external control input is used