Chassis Power Up
88
Mellanox Technologies
4
Chassis Power Up
With N+N PSU redundancy the chassis must be started with a full complement of possible PSUs,
thereafter it can run on half of the total number of PSUs. Connecting the PSUs to different AC
lines provides AC failover protection.
The system should continue to run and allow a hot swap of a defective PSU. Should there not be
enough power to keep all of the leafs running, MLNX-OS® may power down some leafs. If this
happens it will be necessary to reboot the chassis once the defective PSU has been replaced.
1. Check all FRUs for proper insertion and seating before connecting the AC power cords.
• Power supplies
• Leaf fan modules
• Spine modules
• Spine fan modules
2. Insert all leafs that you plan to use in the chassis.
3. Insert thermal blanks in unused leaf and management slots to maintain balanced air flow.
4. Connect the power cords to the PSUs.
5. Connect the power cords to grounded electrical outlets.
4.1
System Status After Power Up
As system boot been completed you should observe the following:
Step 1.
PSU AC OK and DC OK indicators are green.
Step 2.
That the Status LED on each spine, leaf, and management module are
green
which indicates
that the power supplies are good.
Step 3.
Spine module indicators display the status of internal links to the installed leaf modules. All
PHY links to existing leafs should be ON.
Step 4.
Check the spine LEDs and make sure they coincide with
Before starting any procedure on the director switch system put an ESD prevention
wrist strap on your wrist and connect to the chassis.
A fully loaded CS7510 series switch system can draw 7.11kW of power. Make sure
that the outlets and circuits will not be overloaded. Spread out the load over at least
two or three circuits, or a 3 phase supply.
It can take around 5 minutes for the system to boot up. Turn off the system if any LEDs
remain amber for more than 7 minutes.
Содержание Switch-IB
Страница 2: ...Doc MLNX 15 4748 324 2 Mellanox Technologies...
Страница 103: ...104 Mellanox Technologies Figure 77 InfiniBand QSFP Connector Symbol...
Страница 104: ...105 Mellanox Technologies Figure 78 QSFP Connector Male and Female Views...
Страница 111: ...112 Mellanox Technologies 6 7 8 9 10 11...
Страница 112: ...113 Mellanox Technologies 12 13 14 15 16 17...
Страница 113: ...114 Mellanox Technologies 18 19 20 21 WEEE 22 H 4 Chinese 1...
Страница 114: ...115 Mellanox Technologies 2 3 4 5 6 7 8 r r 368...
Страница 115: ...116 Mellanox Technologies 9 10 InfiniBand 11 12 13 14 15 UL CSA 16 QILQL DQG 8 6 9 5 9 39 9...
Страница 116: ...117 Mellanox Technologies 17 18 19 20 WEEE 21 56 8 3 3 36 71 7...
Страница 127: ...128 Mellanox Technologies 3 4 5 6 7 8 9 45 C 113 F 8 3...
Страница 144: ...145 Mellanox Technologies 5 6 7 8 9 10 11 FP 368...
Страница 146: ...147 Mellanox Technologies 19 20 21 2 2 71 7...