GD-5510-01
Instructions Manual
6.Connection
6-1.Overview of Connection Configuration
● Connect only one motor to one driver.
● Use twisted pair wire for the CW/CCW input signal line.
● Provide shielding for the signal line where considerable noise is generated.
● Use the wire material of the characteristic that is difficult to burn.
● Provide shielding for the motor line if it generates significant noise.
● When relays or electromagnetic switches are used together with the system,
use noise filters to suppress surges generated by them.
〔Example configuration〕
The metallic enclosure and shielded wires work to shield noise.
CWP
J1
CW+
1
R.GND
User
controller
CCWP
+COM
+COM
R.GND
2
3
4
5
6
7
8
9
10
11
12
C.S
O.H.A
P.O
M.F
CCWP
CWP
GD-5510-01
CW-
CCW+
CCW-
M.F+
M.F-
R.GND
R.GND
C.S+
J3
P.O
O.H.A
C.S-
J2
1
2
3
5
3
4
1
2
Protective earth
terminal for the
equipment (PE)
(O.75mm
2
or more)
Motor
Single-phase 100-115V
N
L
Twisted
pair wire
Single-phase 100-115V
-23-
Содержание GD-5510 -01
Страница 13: ...GD 5510 01 Instructions Manual 3 2 AC Input Motor Output Terminal Block J2 J3 13 ...
Страница 34: ...GD 5510 01 Instructions Manual 10 3 I O Signal 1 Example Circuit Connection 34 ...
Страница 40: ...GD 5510 01 Instructions Manual 10 4 Dimensions Unit mm 40 ...
Страница 43: ...GD 5510 01 Instructions Manual 43 ...
Страница 44: ...GD 5510 01 Instructions Manual 44 ...
Страница 45: ...GD 5510 01 Instructions Manual 45 ...
Страница 46: ...GD 5510 01 Instructions Manual 46 ...
Страница 47: ...GD 5510 01 Instructions Manual 47 ...