4. Technician settings (cont’)
- 30 -
P76 – Fan VFS Low limit in cooling
Range: 0...100%
Default: 0%
P77 – Fan VFS High limit in cooling
Range: 0...100%
Default: 100%
P78 – Fan VFS Low limit in heating
Range: 0...100%
Default: 0%
P79 – Fan VFS High limit in heating
Range: 0...100%
Default: 100%
P83 – View T2 temperature sensor readings
Note:
If T2 is not connected, -9.8°C / -9.8°F
will appear on display
P84 – View T3 temperature sensor readings
Note:
If T3 is not connected, -9.8°C / -9.8°F
will appear on display