4.  DIP Switch Configuration 

 

4.1 The DIP switch is located at the bottom 

right corner of the board as shown in the 

drawing.  (Inside the thermostat) 

 
 

 
 
 

 
 
 
 

 
DIP switch S1 (3 switches) configuration  
 

 DIP 

Switch 

settings 

FUNCTION 

1 2 3 

Internal temp. sensor 
(Default) 

ON OFF

ON 

external temp. sensor 

OFF

ON  OFF 

 
DIP switch S2 (4 switches) is not in use – all switches OFF 
 

 
 

5.  External sensor connection  

 

  The sensor must be MEITAV-TEC type. 

 

N.TC.  Sensor; Temperature ~ Resistance Characteristics 

 

Temp 

°

C

 

7.2  10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2 

Temp 

°

45 50 55 60 65 70 75 80 85 90 

Res. k

 

115.8 

100.9 88.1 77.1 67.7 59.6 52.5 46.4 41.2 36.6 

 

The default from factory is INTERNAL SENSOR. 

 

- Disconnect power to the thermostat 24 Vac. 

- Move DIP switch S1 to external sensor position (1-off, 2-on, 3-off) 

- Connect external sensor to terminals T - To. 

- Reconnect power to the thermostat. 

 

The length of the cable for the external sensor is 100 feet (30 meters) with standard cable. 

If longer distance is needed then the cable MUST be shielded.  

1     2     3

ON

 

* default 

 

DIP switch S1

 