2

wire cannot form a circuit. As shown in the following figure

Error

Correct

4. Terminal Introduction

4.1 User terminal

MTCW-12-NT terminal silk screen

User terminal definition table

Remark

Description

24V+,24V-

Input power DC 24V
Ground

A0,B0

The first channel of RS485(COM0)

A1,B1

The second channel of RS485(COM1)

GND

The second channel of signal ground

WAN

Ethernet communication port

L1+~L16+

Channels 1 to 16 are positive for thermocouple
(thermal resistance) signal input

L1-~L16-

Channels 1 to 16 are negative for thermocouple
(thermal resistance) signal input

LR1-~LR16-

Channels 1 to 16 are negative for thermal
resistance signal input

Y01~Y04,COM0 Switch output port channel 1~4

Y05~Y08,COM1 Switch output port channel 5~8

Y09~Y12,COM2 Switch output port channel 9~12

Y13~Y16,COM3 Switch output port channel 13~16

VO1+~VO12+

The positive pole of the voltage output channel

1~12

VO1-~VO12-

The negative pole of the voltage output channel

1~12

CT1~CT8

The positive of current input signal channel 1~

8

CT-

The negative of current input signal channel 1~

8

Note

The output only one common terminal COM of MTCW-12-NT

and MTCW-08-TT.

4.2 User connection mode

5 things to pay attention to when wiring:

The thermocouple (thermal resistance) signal is recommended to be

accessed through the shielded cable (connection cable). Cables

should be kept away from power lines or other wires that may cause

electromagnetic interference. Using long cables (connecting cables) is

susceptible to noise interference. It is recommended to use cables less

than 100 meters in length (connecting cables). The cable (connecting

cable) has impedance, which will introduce measurement error. The

characteristic adjustment can solve this problem.

The thermal resistance must be connected by a three-wire system.

It is recommended that the positive and negative terminals of the

channel will not be used L+, L- short connection, in order to prevent the

channel will detect the wrong data.

If there is too much electrical interference, please connect the

shielding line (the compensation cable shielding end of thermocouple,

the cable shielding end of the thermal resistance connection, the

shielding end of the 485 communication line) with the thermostat

grounding end PG.

The thermostat grounding PGND should be good grounding.

5. Electrical indicator

5.1 Power indicator

Item

Unit

Min

value

Typical

value

Max

value

Remark

Input

voltage

range

Vdc

20

24

30

Normal start-up and

working range

Input

current

A

/

0.08

/

Normal temperature

rated full load

5.2 Performance indicators

Item

Indicator

CT input

Number of
input
channels

8

Measuring
current
range

AC0.4~50.0A(rms)(Peak current<71A, number
of turns :800, number of current through :1)

Allowable
max current

AC60A(rms) (Peak current<85A,number of
turns:800, number of current through:1)

Display
precision

Full scale ±5%

Display
resolution

0.1A

Note

The measurable current range is related to the number of turns

of the ct and the number of times the current passes through the CT.

Содержание MTCW Series

Страница 1: ...r cabinet wall above and below shall be no less than 20cm Installation in other directions is not conducive to the product itself heat and the product under the heat must not have equipment Install and fix with DIN slot DIN slot of 35mm width can be used for installation under low vibration environment Open the DIN clasp at the bottom of the module and clip the bottom of the module on the DIN guid...

Страница 2: ...e electromagnetic interference Using long cables connecting cables is susceptible to noise interference It is recommended to use cables less than 100 meters in length connecting cables The cable connecting cable has impedance which will introduce measurement error The characteristic adjustment can solve this problem The thermal resistance must be connected by a three wire system It is recommended ...

Страница 3: ...king status word 1596 1597 1598 1599 1600 1601 1602 1603 1604 1605 1606 1607 1608 1609 1610 1611 Digital filter set of one step 1628 1629 1630 1631 1632 1633 1634 1635 1636 1637 1638 1639 1640 1641 1642 1643 D0 1788 1789 1790 1791 1792 1793 1794 1795 1796 1797 1798 1799 1800 1801 1802 1803 D1 1820 1821 1822 1823 1824 1825 1826 1827 1828 1829 1830 1831 1832 1833 1834 1835 A0 1724 1725 1726 1727 172...

Страница 4: ...25 3526 3527 3528 3529 3530 3531 PID output dead band 3548 3549 3550 3551 3552 3553 3554 3555 3556 3557 3558 3559 3560 3561 3562 3563 Hand automatic smooth transfer 3580 3581 3582 3583 3584 3585 3586 3587 3588 3589 3590 3591 3592 3593 3594 3595 Error status word system error 3612 Error status word broken even error 3613 Set value range error address 3616 3617 Channel characteristics confirmation c...

Страница 5: ...ough cables respectively Communication mode RS485 communication protocol MODBUS 3 Because the default communication parameters are the same so the connection can automatically communicate 4 MTCW 16NN can be controlled by BFM area or temperature control assistant 9 Common problems and solutions When the module does not work properly please check in turn 1 the connection of the power line and the co...

Страница 6: ...perate according to the user s manual 2 Machine damage caused by fire flood abnormal voltage etc 3 Damage caused when a programmable controller is used for unusual functions 4 Self disassembly programmable controller 5 The service fee shall be calculated according to the actual cost If there is another contract the contract shall take precedence 6 If you have any problem you can contact the agent ...

Отзывы: