The terminal definition of MCCD-1212BMD1/2/3/4
Remark
Explanation
24V+,24V-
Power supply DC24V
PE
Ground
A0,B0
RS485 port 0
(
COM0
)
A1,B1
RS485 port 1
(
COM1
)
A2,B2
RS485 port 2
(
COM2
)
CANH
、
CANL
CAN port 0
X00
~
X01
,
S/S
High-speed input port 0
~
1
,
input common
terminal
X02
~
X13
,
S/S
Switch input terminal 02
~
13
,
input common
terminal
Y00
~
Y02
,
COM0
High-speed output port 0
~
2
,
output
common terminal 0
Y03
~
Y07
,
COM1
The channel of switch output3
~
7
,
output
common terminal 1
Y10
~
Y13, COM2
The channel of switch output10
~
13
,
output
common terminal 2
VI1+,VIO1-,IO1+,VI2+,
VIO2-,IO2+
The channel of analog output1
~
2
(
Compatible with voltage and current)
VI1+,VI1-
,
VI2+,VI2-
The channel of analog output 1 and
2(voltage or current)
PT1+,PT1-,PT2+,PT2-
PT100 input channel 1 and channel 2
L1+,L1-,L2+,L2-,L3+,
L3-,L4+,L4-
TC input channel 1,channel 2,channel 3 and
channel 4
ETH
Ethernet
USB1
USB flash drive interface for program
upgrade
USB2
USB interface for program debugging and
downloading
The terminal definition of MCCD-1616BMD1/2/3/4
Remark
Explanation
24V+,24V-
Power supply DC24V
PE
Ground
A0,B0
RS485 port 0
(
COM0
)
A1,B1
RS485 port 1
(
COM1
)
A2,B2
RS485 port 2
(
COM2
)
CANH
、
CANL
CAN terminal 0
X00
~
X01
,
S/S
High-speed input port 0
~
1
,
input
common terminal
X02
~
X17
,
S/S
Switch input terminal 02
~
17
,
input common terminal
Y00
~
Y02
,
COM0
The channel of high-speed
output 0
~
2
,
output common
terminal
Y03
~
Y07
,
COM1
The channel of switch output3
~
7
,
output common terminal 1
Y10
~
Y17, COM2
The channel of switch output10
~
17
,
output common terminal 2
VI1+,VIO1-,IO1+,VI2+,VIO2-,IO2+
The channel of analog output1
~
2
(
Compatible with voltage and
current)
VI1+,VI1-
,
VI2+,VI2-
The channel of analog output 1
and 2(voltage or current)
PT1+,PT1-,PT2+,PT2-
PT100 input channel 1 and
channel 2
L1+,L1-,L2+,L2-,L3+,L3-,L4+,L4-
TC input channel 1,channel
2,channel 3 and channel 4
ETH
Ethernet
USB1
USB flash drive interface for
program upgrade
USB2
USB interface for program
debugging and downloading
5.2 Communication port
Name
Supported
protocols
Position
Physical
layer
Communication port 0
Modbus ( slave
station)
COM0
(
A0 ,B0
)
RS485
Communication port 1
Modbus (master
and slave station)
free port
COM1
(
A1 ,B1
)
RS485
Communication port 2
Modbus (master
and slave station)
COM2
(
A2 ,B2
)
RS485
Communication port 3
CAN free port
CAN0(H,L)
CAN
Communication port 4
Ethernet
ETH
TCP/IP
Communication port 5
USB host
USB1
USB
Communication port 6
USB slave
USB2
USB
Note
: 1. Communication port 2 is HMI resource, which needs to be set
in MEGVIEW2 for use. Modbus slave station is the default.
Communication port 4, 5 and 6 are HMI resources, which need to be
set in MEGVIEW2 for use
6. Switching characteristics of input and output
6.1 Switching input characteristics and signal
specifications
The counter input port has a maximum frequency limit. If the limit is
exceeded, the count may be inaccurate or the system may not function
properly. Please arrange the input port reasonably and select the
appropriate external sensor.
The PLC provides port "S/S" for selecting whether the input signal is
source input or leak input.
6.1.1 Transistor input specifications
Item
High-speed input
Normal input
Input resistance
3.3kΩ
4.3kΩ
Input current
6.5mA (Type value)
5.3mA (Type value)
ON voltage/current
DC18V
/4.5mA DC18V /3mA (Mix.
Содержание MCCD Series