background image

 
Technical Guide 
Testing self-powered relays with SVERKER 900 
 

 
 

  Page 7(33)  

 
 

SVERKER 900 with indication “Current generator MkII” is designed to test self-powered relays. 
It is important to be aware that the technology behind self-powered relays is in continuous and fast development 
(see par. 2), so it cannot be promised that all self-powered relays are managed. Please contact Megger if you 
need support. 

4.  General information about overcurrent relays. 

4.1. IEC standard for overcurrent protection: IEC 60255-151:2009 

The IEC standard for overcurrent protection function is IEC 60255-151:2009: Measuring relays and protection 
equipment - Part 151: Functional requirements for over/under current protection [8]. 

The information, definitions and testing methodologies described in the IEC relay protection functional 
standards, IEC 60255-1xx are of interest for [9]: 

protection relay manufacturer, where the standards describe the minimum requirements for type-testing, 

test equipment manufacturer 

–to apply the standardized test methodologies 

end-users, for procurement specification, acceptance tests 

the entire relay protection community in general (as well as for commissioning / testing engineers), for using 
the same terminology and definitions  

If all the parties have a competence of IEC 60255-1xx standards, there will be less misunderstandings during 
the purchase but also at commissioning/maintenance of the protection relays, with less discussions, shorter 
testing times and a more reliable protection system [10],[7]. 

The following paragraphs summarize the most important details available in the standard that are useful for the 
work of a relay testing engineers. 

4.1.1. Standardized IEC inverse time curves 

One of the most important successes of IEC 60255-151:2009 was to reach an international consensus on the 
harmonisation of the so-called 

“IEC and IEEE time curves”. The recent IEEE standard C37.112: 2018 [11] has 

in principle adopted the same IEC curves. 

The standardized IEC curves are A, B, C, D, E and F. The common names used for the curves are associated 
to the letters (Figure 4). SVERKER 900 has implemented the standardized curves, as the next paragraphs will 
show. 

Содержание SVERKER 900

Страница 1: ...megger com ZR CR15E Doc CR036201AE V01 Sept 2020 Page 1 33 Testing self powered relays with SVERKER 900 Authors Andrea Bonetti Megger Sweden AB Klaus Spitzenberg Megger GmbH Germany Lennart Schotteniu...

Страница 2: ...Technical Guide Testing self powered relays with SVERKER 900 Page 2 33...

Страница 3: ...PHASE OVERCURRENT RELAY 12 5 2 1 Relay settings 12 5 2 2 Connecting SVERKER 900 to WIC 1 relay 13 5 2 3 SVERKER 900 settings 14 5 2 4 Testing the overcurrent protection function 15 5 2 5 Can we accept...

Страница 4: ...es and hopefully one day will be able to deliver energy to the grid V2G 2 2 More technically smart grids penetrates all the voltage levels One of the important factors that will affect the speed of th...

Страница 5: ...nd it is induced back to the analog inputs of the relay From that current the relay draws the energy to power itself Figure 2 The line feeder must be de energized no primary current shall flow into th...

Страница 6: ...lt current for a certain period before the fault current is really injected In SVERKER 900 this means that the pre fault and fault instrument shall be used where the pre fault currents are set at a ce...

Страница 7: ...er to apply the standardized test methodologies end users for procurement specification acceptance tests the entire relay protection community in general as well as for commissioning testing engineers...

Страница 8: ...st of the border it is intended to verify the accuracy of the border of the relay characteristic For overcurrent relays the characteristic is defined by the start value pick up value5 the current thre...

Страница 9: ...imes at values smaller than 1 3 times the threshold but remember that in case of discussions the IEC 60255 151 requires to test the operate time at least at 1 3 times the start value if no other value...

Страница 10: ...is document is W1C1 W2AS1 Figure 6 and Figure 7 The selected nominal primary current Is will be chosen to be 20 A Figure 6 The multi winding CT of type W1C1 W2AS1 The relay settings are made with dips...

Страница 11: ...user s manual pages 20 21 and 22 5 Copyright SEG GmbH their position in the tested relay and list of different CTs The Normal Inverse characteristic for WIC 1 relay is the standardized curve A Invers...

Страница 12: ...ent to 50 A primary current I _test 30 A x 1 50 0 6 A Characteristic Normal Inverse Time Multiplier a 0 3 I _test 200 A x 1 50 4 0 A Characteristic Definite Time Time Delay t 200 ms The table below re...

Страница 13: ...rms that no matter which current transformer is used the base value of the secondary test current is 0 4 A Figure 10 Figure 10 No matter which current transformer is used the windings are arranged in...

Страница 14: ...input nr 18 of SVERKER 900 needs to be configured in such a way to be able to manage the voltage trip signal from WIC 1 Voltage sensing trigger on voltage presence from 0 to 1 DC voltage threshold 20...

Страница 15: ...s as shown in Figure 12 5 2 4 Testing the overcurrent protection function Considering the information in par 5 2 3 set up the necessary conditions in SVERKER 900 and run the sequence of tests10 Before...

Страница 16: ...gure 15 Figure 15 First fault of 0 8 A timeout after 10 seconds in MTT pre fault and fault Select MTT by tapping on its button MTT is now armed Figure 16 Figure 16 Activation arming of the MTT mode in...

Страница 17: ...w 4A threshold for I for testing the non trip of the I threshold par 4 1 3 In this case tests slightly above 4A have been done but the test results were well in line with the expected values so there...

Страница 18: ...he test current see par 5 2 1 The procedure is very intuitive Figure 21 Adding the reference curve for I and I Tap on to see the result on a larger graph Figure 22 Figure 22 Viewing the test results g...

Страница 19: ...ings 10 above and 10 below the real settings In this case we obtain two curves that reasonably show the error in the time characteristic When the error for the measured current is below the injected v...

Страница 20: ...ault fault current of 7 A above I threshold of 4 A Remember please that those current values are always referred to the test current It is always good to have in mind the primary values associated to...

Страница 21: ...KER 900 Page 21 33 Figure 25 MTT Pre fault and fault sequence for the presence of load before the fault and test results Figure 26 MTT Pre fault and fault sequence for simulation of no presence of loa...

Страница 22: ...fault Fault 7 A 1 202 ms 216 ms 2 203 ms 215 ms 3 203 ms 216 ms 4 202 ms 215 ms 5 203 ms 215 ms AVERAGE 202 6 ms 215 4 ms We can conclude that the additional time required by WIC 1 to start up some 1...

Страница 23: ...nce conditions this test enables a self testing self supervision through a special procedure that tests the tripping circuit and other signals Figure 27 Figure 27 Procedure for testing the tripping ci...

Страница 24: ...hen press Enter again until selected value comes up When I value is set press again to to set Characteristic repeate above to select If password is still valid only press Enter until selected choise c...

Страница 25: ...user s manual 4 Copyright SEG GmbH 6 2 3 SVERKER 900 settings For testing the phase overcurrent protection function the instrument MTT 12 of pre fault and fault and the possibility to draw graphs of t...

Страница 26: ...ressing the knob Once the operate time is recorded by the SVERKER 900 just rotate the knob to change the fault level and press it again to inject it Until you have finished with the sequence of tests...

Страница 27: ...5 A timeout after 20 seconds in MTT pre fault and fault Figure 32 Activation arming of the MTT mode in pre fault and fault Press the knob to start the injection To stop the sequence of tests tap At th...

Страница 28: ...n phase L1 If this time elapses without that the injection has occurred the procedure must be started again from the relay HMI Before preparing the relay for this test prepare the SVERKER 900 connecti...

Страница 29: ...tton on relay HMI to acknowledge that the test is terminated just follow the instructions that the relay proposes through its screen A simple video clip 14 shows the self testing procedure in WIP 1 re...

Страница 30: ...ure 38 For repeating the tests MTT in pre fault and fault instrument has been used Different approaches are of course possible Figure 37 MTT Pre fault and fault sequence for the presence of load befor...

Страница 31: ...negligible compared to the operate time when the load current is available before the fault Switch onto fault condition or fault in unloaded feeders does not create any noticeable extra time delay in...

Страница 32: ...nput Output IEC TC JWG 17 Documentation of communication in power utility automation https www linkedin com in bonetti andrea 8 2 Klaus Spitzenberg Klaus is training manager and application expert at...

Страница 33: ...luation of distance protection relays in 2016 IEEE PES Transmission and Distribution Conference and Exposition T D May 2016 pp 1 6 doi 10 1109 TDC 2016 7520031 8 IEC 60255 151 2009 IEC Webstore https...

Отзывы: