APPLICATION
The MIT200 series will find applications in electrical contracting,
both on domestic and industrial systems, as well as site
maintenance and service departments.
The MIT200 series of insulation and continuity testers are ideal
for testing transformers, motors, generators, switchgear, panel
building, domestic appliances, power tools etc., as well as fixed
electrical wiring systems.
Their small size and light weight make them ideal for those
engineers that need to carry them for extended periods.
All instruments meet the requirements of most International
Standards including VDE 0413 Part 1 and BS 7671 (the 17th Edition
of the IEE Wiring Regulations).
FEATURES AND BENEFITS
■
■
Meets the international EN 61557 requirements of the rated test
voltage into a 1 mA load.
■
■
Digital display of insulation measurement up to 1000 MΩ on a
linear or logarithmic analogue arc and a digital display.
■
■
Continuity range has 0,01 Ω resolution and a short circuit current
in excess of 200 mA.
■
■
Automatic continuity testing leaves both hands free. No need to
press the test button.
■
■
Automatic power-off if left unattended reduced wasted battery
life.
■
■
Automatic voltage detection avoids accidental contact with
dangerously live circuits.
■
■
Test lead zero allows compensation for test lead resistance.
■
■
Buzzer range operates at <2 Ω.
MIT220 MIT230
Insulation testing
250 V
■
■
500 V
■
■
1000 V
■
1000 MΩ range
■
■
Auto-ranging
■
■
Auto discharge
■
■
Test inhibit
■
■
Live circuit voltage display
■
■
Continuity testing
Continuity at >200 mA
■
■
Continuity to 0.01 Ω
■
■
Test lead null (9.99 Ω)
■
■
Automatic continuity test
■
■
Continuity buzzer with 2 Ω threshold
■
■
Default volts warning
■
■
General
Digital d arc
■
■
Battery condition
■
■
Auto power down
■
■
Tough carry case
■
■
Test leads
■
■
CATIII 600 V
■
■
Environmental
Operation temperature
-10 °C to +55 °C
Storage temperature
-20 °C to +65 °C
IP rating
IP40