background image

APPLICATION NOTE

 

 

RCD impedance uplift elimination. 

Megger Ltd, Dover, United Kingdom  

www.megger.com 

Sales office: 01304 502 101,  

[email protected]

   

RCD impedance uplift elimination 

Technical support: 01304 502 120,  

[email protected]

  

P1 

The  MFT1845  utilises  a  brand  new  loop  impedance  test  technique  which  provides  immunity  to  the 

increased impedance effects that RCDs and RCBOs can have on the measurement. 

Applications: 

The new MFT 3-wire non-trip loop impedance technique is suitable for use on all low voltage single phase 

circuits, where the earth loop impedance of the circuit is required to be measured through RCD or RCBO 

devices.  

The problem: 

There  is  a  requirement  in  electrical  installations  which  stipulates  that  electricians  must  verify  the  loop 

impedance  of  all  electrical  circuits.    The  loop  impedance  must  be  low  enough  to  ensure  every  circuit 

breaker  protecting  a  circuit  from  over-current,  both  line  to  neutral  and  line  to  protective  earth,  will 

disconnect in the required time.  These requirements are drawn directly from the IEC 60364 regulations 

and from domestic implementation of these regulations.  On a typical 32 A type B circuit breaker this value 

should be less than 1.37 Ω.  This is then multiplied by 0.8 to provide a safe margin for error, giving a loop 

impedance of 1.1 

Ω.  We will come back to this later. 

Many of these circuits are also protected by an RCD or RCBO downstream of the circuit breaker.  The 

most common of these, the 30 mA RCD or RCBO can influence the loop impedance measured by the 

MFT by increasing the measured value by more than 0.5 Ω, the value returned is significantly higher than 

the expected or calculated value.  This can easily push the measured value over the limit, as below: 

Basic circuit resistance (continuity) = 0.7 

Ω 

Measured loop impedance (L-

PE) = 1.2 Ω (remember the limit is 1.1 Ω) 

Uplift created by RCD or RCBO = 1.20 

– 0.7 = 0.5 Ω  

This uplift of the circuit impedance pushes the measured level over the acceptable limit and now presents 

a significant problem for electricians. 

The uplift is not present on all RCDs or RCBOs and can vary greatly on those devices where it does exist. 

 

 

Отзывы: