background image

Bonded Metalwork Testing

Repeat the above test but with the Green lead connected to the exposed

metalwork.

For a Hi Current Phase to Earth loop impedance measurement at a power

socket, repeat the above test using the Mains plug test lead supplied.

Phase-Neutral or Phase-Phase loop impedance

1. Connect the 3-wire test lead to the instrument.

2. Connect the RED [L1] lead to PHASE. Connect the GREEN [L0] lead and

the BLACK lead (Black lead - ensure the black lead is connected to the

green lead) to NEUTRAL (or the 2nd PHASE for Phase to Phase loop

measurement on the LRCD220).

3. The supply voltage is displayed. 

4. Press the [TEST] button to start a loop test.

5. After a short delay the measured loop value is displayed. If desired the

test can be repeated by pressing the [TEST] button again.

N

No

o tt e

e:: Phase – Phase (415 V) loop test is only possible on the LRCD220.

Prospective Fault Current display  [PFC]

1. On completion of a test, press the [PFC] key.

2. The prospective fault current is displayed in Amps or kA.

Notes:

The prospective short circuit current (PSCC) of a circuit is the largest

Prospective Fault Current (PFC). In a single phase system, this would be

the larger of the earth loop PFC and the neutral loop PFC. In a multi-phase

system phase-phase loops also need to be considered and these can be

measured using the (Hi) switch position.

The PFC is calculated by using the sum:- 

Nominal supply voltage   

Loop resistance

The supply voltage used in the calculation depends on the measured

voltage. The instrument uses the following voltage values:-

Actual measured  

Nominal voltage

voltage

>80 V and <150 V

110 V (LRCD220 only)

>150 V and <300 V

230 V

>300 V

400 V (LRCD220 only)

PFC measurement accuracy

An accurate PFC measurement requires an accurate measurement of the

loop resistance. The difference of a few digits in the loop resistance

measured will have a large effect on the PFC displayed.

Warning messages

Noise Indication

The symbol 

is displayed when excessive noise caused by other

equipment exists on the circuit under test. This noise can affect the

accuracy of the loop measurement. 

The operator is advised to repeat the measurement or, if the noise symbol

continually appears, investigate the cause. 

Voltages greater than 280V  [>480V on LRCD220]

LRCD200/210:

If a voltage greater than 280 V is detected, the 

display will show >280 V.

13

PFC=

Содержание LRCD200 series

Страница 1: ...M LRCD200 Series Combined Loop and RCD Tester USER MANUAL...

Страница 2: ...r must be in place whilst conducting tests Voltage indicator LED s cannot reveal a N PE supply reversal National Safety Authorities may recommend the use of fused test leads when measuring voltage on...

Страница 3: ...se contents 5 LCD Display 6 Front panel 6 Connection panel 7 Lid open closure 7 Preparations for use 8 Batteries 8 Preliminary test lead check 8 General operating instructions 8 Display warning symbol...

Страница 4: ...is user manual describes the operation and functions of the following LRCD series of Loop and RCD testers LRCD200 LRCD210 LRCD220 The LRCD200 series test instruments have the following features LRCD20...

Страница 5: ...lead with prods with clips 1 x Plug ended test lead 8 x AA LR6 batteries fitted in instrument 1 x Warranty card 1 x Certificate of test 1 x Calibration certificate 1 x CD containing user manual 1 x Qu...

Страница 6: ...easured results Phase rotation Fuse blown Mains noise Battery status Refer to User Manual Touch voltage bargraph display RCD test type indicator RCD type selector AC AC Selective DC DC Selective PFC 2...

Страница 7: ...b 1 2 Fold away underneath instrument 2 3 and push into retaining slot 4 LRCD 200 210 LRCD220 7 Warning Read user guide Warning Read user guide Earth connection or 2nd Phase connections 220 only Earth...

Страница 8: ...age to operate If the warning V is displayed the supply voltage is below that required to perform an RCD test supply voltage indication Overheating Repetitive loop testing generates heat within the in...

Страница 9: ...se has failed Refer to page 19 280V Displayed on the LRCD200 210 indicates a supply voltage in excess of that allowed is present 480V Displayed on the LRCD220 indicates a supply voltage in excess of t...

Страница 10: ...accurate measurements only use the test leads supplied or by Megger Limited swapped or L N instrument will not perform tests with L N swapped 6 Press the LOCK button or the PFC button to change the s...

Страница 11: ...en L PE greater than 25 V L N Voltage between L N greater than 25 V N PE Voltage between N PE greater than 25 V W Wa ar rn ni in ng g Voltage indicator LED s cannot reveal a N PE supply reversal Polar...

Страница 12: ...If desired the test can be repeated by pressing the TEST button LOOP TESTING 12 Two loop testing options are available No Trip on the LRCD200 210 and Hi test on the LRCD220 Non tripping loop test No...

Страница 13: ...he largest Prospective Fault Current PFC In a single phase system this would be the larger of the earth loop PFC and the neutral loop PFC In a multi phase system phase phase loops also need to be cons...

Страница 14: ...rature hot To protect the instrument from over heating during Loop testing thermal protection is fitted If the message hot appears in the display together with the Gsymbol when loop testing the instru...

Страница 15: ...trip time in milliseconds If the display shows 40 ms the RCD has failed to trip in the appropriate time Check your test lead connections to the RCD and repeat the test If the RCD still fails to trip s...

Страница 16: ...est IIIII 5 I test Example shows 5I on 0 NOTE The current limit for the 5I test is 100 mA as the test current available is limited to 1 Amp 0 or 180 testing Both the 1 x I and 5 x I tests should be pe...

Страница 17: ...lication On the LRCD200 series instruments the touch voltage limit can be switched from 50 V to 25 V as the application demands Should the touch voltage calculation identify a higher touch voltage tha...

Страница 18: ...fficient supply voltage for test Other messages L L Will test with L N swapped L N Will NOT test with L N swapped SEt Setup menu OFF Instrument is about to switch off 18 PHASE SEQUENCE LRCD 220 ONLY A...

Страница 19: ...connected 3 To remove the rear cover release the screw at the bottom of the cover and lift the cover upwards 4 Fit new batteries observing the correct polarity as marked on the battery compartment 5 R...

Страница 20: ...indicator LRCD220 only Three wire identification of phase rotation Loop testing Loop ranges to EN 61557 3 LRCD200 210 220 No Trip Loop test 3 wire Line to Earth Supply LRCD200 210 200 V 280 V 45Hz to...

Страница 21: ...ctive Fault Current PSCC Prospective fault current Nominal supply voltage Loop resistance Accuracy is derived from loop test 1 A 199 A 1 A resolution 0 20 kA 1 99 kA 10 A resolution RCD Testing RCD Te...

Страница 22: ...of EN61557 Electrical safety in low voltage systems up to 1000 V ac and 1500 V dc Equipment for testing measuring or monitoring of protective measures Part1 General requirements Part3 Loop resistance...

Страница 23: ...ing into effect of battery voltage temperature interference and system voltage and frequency where applicable Item Order Code 3 wire test lead set and crocodile clips 6220 782 Mains plug test lead BS...

Страница 24: ...turning and Instrument for Repair If it is necessary to return an instrument for repair a returns authorisation number must first be obtained by contacting one of the addresses shown You will be asked...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...r com Megger Pty Limited Unit 26 9 Hudson Avenue Castle Hill Sydney NSW 2125 Australia T 61 0 2 9659 2005 F 61 0 2 9659 2201 E ausales megger com Megger Limited 110 Milner Avenue Unit 1 Scarborough On...

Отзывы: