2

3

--- That there is continuity of earth bonding.

--- That capacitors are discharged: this shall be do-

ne in a safe manner to avoid possibility of sparking;
--- That no live electrical components and wiring are

exposed while charging, recovering or purging the 

system;

 

an adequate temporary solution shall be used. This 

shall be reported to the owner of the equipment so

 

all parties are advised.

Initial safety checks shall include:

Repairs to sealed components

During repairs to sealed components, all electrical 

supplies shall be disconnected from the equipment 

potentially hazardous situation.

being worked upon prior to any removal of sealed 

covers, etc. If it is absolutely necessary to have an

electrical supply to equipment during servicing, then 

a permanently operating form of leak detection shall 

be located at the most critical point to warn of a 

Particular attention shall be paid to the following to  

ensure that by working on electrical components, 

the casing is not altered in such a way that the le-

vel of protection is affected. This shall include 

     damage to cables, excessive number of connections,

 

terminals not made to original specification, damage 

     to seals, incorrect fitting of glands, etc.

Ensure that the apparatus is mounted securely.

Ensure that seals or sealing materials have not 

degraded to the point that they no longer serve the 

purpose of preventing the ingress of flammable at-

mospheres. Replacement parts shall be in accord-

ance with the manufacturer’s specifications.

The use of silicon sealant can inhibit the effecti-

veness of some types of leak detection equipm-

ent. Intrinsically safe components do not have to

be isolated prior to working on them.

Note

Removal and evacuation

    When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 

procedures shall be used. However, for flammable

refrigerants it is important that best practice is follo-

detector is not a potential source of ignition and is 

suitable for the refrigerant used. Leak detection eq-

uipment shall be set at a percentage of the LFL of the

refrigerant and shall be calibrated to the refrigerant 

employed, and the appropriate percentage of gas 

(25 % maximum) is confirmed.

     Leak detection fluids are suitable for use with most

 

refrigerants but the use of detergents containing ch-

lorine shall be avoided as the chlorine may react with

 

the refrigerant and corrode the copper pipe-work.
    If a leak is suspected, all naked flames shall be rem-

oved/extinguished.

    If a leakage of refrigerant is found which requires br-

azing, all of the refrigerant shall be recovered from

the system, or isolated (by means of shut off valves) 

in a part of the system remote from the leak. For ap-

pliances containing flammable refrigerants, oxygen 

free nitrogen (OFN) shall then be purged through the 

system both before and during the brazing process

.

Cabling

Check that cabling will not be subject to wear, corr-

osion, excessive pressure, vibration, sharp edges or 

any other adverse environmental effects. The check 

shall also take into account the effects of aging or

 

continual vibration from sources such as compressors

or fans.

Leak detection methods

    The following leak detection methods are deemed 

acceptable for all refrigerant systems.

     Electronic leak detectors may be used to detect re-

frigerant leaks but, in the case of flammable refrige-

rants, the sensitivity may not be adequate, or may 

need re-calibration. (Detection equipment shall be

 

calibrated in a refrigerant-free area.) Ensure that the

Repair to intrinsically safe components

   Do not apply any permanent inductive or capacita-

nce loads to the circuit without ensuring that this will 

not exceed the permissible voltage and current per-

Repair and maintenance to electrical components

shall include initial safety checks and component 

inspection procedures. If a fault exists that could

compromise safety, then no electrical supply shall 

be connected to the circuit until it is satisfactorily 

dealt with. If the fault cannot be corrected imme-

diately but it is necessary to continue operation,

are constructed of materials which are inherently

resistant to being corroded or are suitably protec-

ted against being so corroded.

Checks to electrical devices

Specialist’s Manual

mitted  for the equipment in use.

    Intrinsically safe components are the only types 

that  can be worked on while live in the presence of 

a flammable atmosphere. The test apparatus shall 

be at the correct rating.

    Replace components only with parts specified by 

the manufacturer. Other parts may result in the ign-

ition of  refrigerant in the atmosphere from a leak.

Detection of flammable refrigerants

    Under no circumstances shall potential sources of 

ignition be used in the searching for or detection of 

refrigerant leaks. A halide torch (or any other detector 

using a naked flame) shall not be used. 

Содержание ML-PC10AO-K5NNA1A

Страница 1: ...nstructions Portable air conditioner Model ML PC10AO K5NNA1A ML PH12AO K5NNA1A ML PC12AO K5NNA1A Thank you for choosing our product Please read this Owner s Manual carefully before operation and retai...

Страница 2: ...ction for Icons on Display Screen 1 Installation in sash window Optional 1 2 6 8 10 11 12 Function Introduction for Combination Buttons Replacement of Batteries in Remote Controller Maintenance 7 7 12...

Страница 3: ...bol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to property Indicates important but not hazard related information used to indicate r...

Страница 4: ...example open flames an operating gas app liance or an operating electric heater The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified f...

Страница 5: ...hen contact local dealer When nobody is taking care of the unit please turn it off and remove the power plug or disconnect power Prohibit operating the unit in the bathroom or laundry room Far away fr...

Страница 6: ...essionals to deal with it Do not use an extension cord Please put the air conditioner at smooth and flat ground for operation to avoid noise and vibration This air conditioner is equipped with castors...

Страница 7: ...OPER 7 Sleep Timer 8 Health WiFi 10 9 Remote controller Some installation accessories can t be discarded On Off Fan Mode Swing 1 Controller panel Guide louver NOTICE 4 5 6 Filter Air inlet Middle drai...

Страница 8: ...ir conditioner will give out a sound Meanwhile corresponding indicator on control panel will be bright Under OFF status dual 8 nixie tube on control panel won t display Under ON status dual 8 nixie tu...

Страница 9: ...sion of the signal Do not leave the remote control in direct sunlight or ne ar a heater Protect the remote control from moisture and shock Set time TIMER ON TIMER OFF Light Up down swing Child lock Se...

Страница 10: ...imer button Health button This function is not applicable for this model Under ON status press this button to set timer OFF Under OFF status press this button to set timer ON Press this button once an...

Страница 11: ...ons Temperature display switchover function Under OFF status press and Mode buttons simultaneously to switch temperature display betw een C and F using the remote controller Replace new batteries of t...

Страница 12: ...on the air conditioner Eliminate accumulated water in chassis refer to the section of Drainage way for details Check whether window bracket is damaged or not If yes please contact dealer dition Check...

Страница 13: ...he unit again Whether the unit is interfered by thunder radio etc 1 Pour out the water inside chassis 2 If H8 still exits please contact profess ional person to maintain the unit If the malfunction st...

Страница 14: ...c safety regulations when Other places with special circumstances It s not allowed to be installed on the unstable or motive base structure such as truck or in the corrosive environment such as chemic...

Страница 15: ...ews FAN Fan Swing Mode OPER Sleep On Off Timer Health WiFi Optional 1 Mothproof net Bracket Screw Mounting plate Fixed clip Fixed base Sponge B Sponge A Optional 3 Optional 2 Optional 4 Drainage hose...

Страница 16: ...age port to drain water After draining insert the rubber plug Press ON OFF button to restart To reach the maximum performance it is not recommended to drain water during Cool mode It is recommended to...

Страница 17: ...option from the middle hole place portable on a level surface and make sure garden hose is clear of any obstructions and is directed downward Placing portable on an uneven surface or improper hose in...

Страница 18: ...0 465 25 25 25 25 25 25 25 465 127 255 128 128 123 123 Window panel Adjustment panel Extension panel Exhaust cover Fixed base Fixed base Fixed base Fixed base Window panel Adjustment panel Fixed clip...

Страница 19: ...ion of window and screw down by a Mounting plate C 1 2 3 4 5 6 7 Assemble the window kit as below 5 For windows with inner width or height of 770mm push two fixed bases to the end of Window Panel A Fo...

Страница 20: ...Window panel Stuff the Foam seal A between the glass and the window to prevent air and insects from getting into the room 2 Attach the window panel to the window stool Make sure that the exhaust cove...

Страница 21: ...haust cover is attached to the window panel 770mm 1210mm 770mm 1650mm 1210mm 5 Attach the bracket with a screw Recommend ed Bracket Sliding sash window Optional 1 1 Please lay a tabular material under...

Страница 22: ...below figure by the manufacturer Note of Installing heat discharge pipe User can adjust the installation method of the discharge pipe basing on the requirement while the similar installation methods...

Страница 23: ...4 3 Install the other side of heat discharge pipe clock wise into joint D Joint D Insert joint A of heat discharge pipe into the gro ove until you hear a sound Groove joint A Insert joint A of heat di...

Страница 24: ...nd remove the Rear clip by pushing down two PUSH markings slide and close the exhaust cover in the window panel Optional Joint Joint H 1 2 Remove joint F remove joint F from joint H Disassembly for in...

Страница 25: ...RD C1 SA M2 YEGN M1 YEGN PE PE RD CAP CAP BN ROOM TEMP BN RD SENSOR RT1 TUBE TEMP SENSOR OUTTUBE TEMP SENSOR RT3 VALVE 4 WAY 4YV WATER MOTOR YEGN RECEIVER BOARD POWER L N BN BK BU WH YEGN GN N2 WATER...

Страница 26: ...22 b a Specialist s Manual 4 2 Aptitude requirement for maintenance man repairs should be done only be specialists Safety preparation work 2...

Страница 27: ...be avoided as the chlorine may react with the refrigerant and corrode the copper pipe work If a leak is suspected all naked flames shall be rem oved extinguished If a leakage of refrigerant is found w...

Страница 28: ...and that ventilation is available Specialist s Manual Decommissioning a Become familiar with the equipment and its ope ration Isolate system electrically Before attempting the procedure ensure that b...

Страница 29: ...ng the equipment that is at hand and shall be suitable for the recovery of all the relevant waste transfer note arranged Do not mix refrigerants in recovery units and especially not in cylinders If co...

Страница 30: ...66129937317...

Отзывы: