background image

Megalarm wireless system 

General points 

The Megalarm wireless fire alarm system is designed for small offices, shops, workshops, site cabins and 
temporary buildings. It can combine up to 10 units consisting of 1 master unit and 9 stave units, either 
manual call points or smoke detectors. The system is powered by batteries and requires no mains voltage 
supply.

The master P300W can be combined with either 9 more P300Ws, C300W radio manual call points 
(MCP), radio smoke heads D300W or a combination of all 3 totalling no more than 9, plus the master. The 
instructions in this manual will enable you to commission all devices together, which when activated will 
register an alarm sound from all P300W units and D300W detectors.

Instructions for decommissioning can be found on the last page should you encounter any difficulties.
This is important should you encounter any set up issue, decommission and start the configuration process 
again.

Technical Data  
P300W master unit 

Power 

Lithium 3V battery capacity: 1300mAh, IEC standard: CR17345 for the radio module & 6LR 61 Alkaline 9 volts battery 

for sounder/beacon operation autonomy: 5 years with at least 5 minutes alarm

Installation Method 

Surface mounted

Sounder 

Integral 90db within 2 meters

Strobe Lights

 Integral high power LEDs

Dimensions 

126(W)x242(H)x75(D)mm

Colour 

White ABS

Manual Call Point

 Integral/wireless complete with 3V lithium battery

Wireless Range

 100m in open area conditions, 30-40m if being used inside a building

C300W manual call point 

Power

 Integral lithium 3V battery, capacity: 1400mAh, IEC standard: CR17345

Range

 Maximum range between manual call point and base = 100m in open area conditions

Installation

 Mounting Surface mounted

Resetting 

Key Included

Wireless Range

 100m in open area conditions, 30-40m if being used inside a building

D300W wireless smoke detector 

Power

 Lithium sealed in battery (non-replaceable)

Sounder

 Integral 85db

Test Button 

Integral

Operating Temperature

 0 ºC - 55 ºC

Radio Linking Frequency 

868 Mhz

Wireless Range

 100m in open area conditions, 30-40m if being used inside a building

Wireless interface 

(optional - not a stock item)

Power

 12V via fire alarm panel

Operating Temperature 

0 ºC - 55 ºC

Dimensions

 83(W)x83(H)x46(D)mm

Interconnection Capacity 

Smoke detectors unlimited

Wireless Range

 100m in open area conditions, 30-40m if being used inside a building

0330 999 2233

www.firedepot.co.uk

[email protected]

1

Содержание P300W

Страница 1: ...setting up your wireless system P300W C300W D300W and wireless interface Standards NFS 61 936 NFS 32001 EN 54 11 0330 999 2233 www firedepot co uk sales firedepot co uk...

Страница 2: ...operation autonomy 5 years with at least 5 minutes alarm Installation Method Surface mounted Sounder Integral 90db within 2 meters Strobe Lights Integral high power LEDs Dimensions 126 W x242 H x75 D...

Страница 3: ...em requires that you make a P300W unit the master and all other components slaves Further P300W units and or both C300W or D300W stage one opening and closing your master P300W unit Open your P300W un...

Страница 4: ...MCP Refer to Step 2 stage one on how to access the MCP step 2 Your C300W unit stage one opening your C300W unit Simply unscrew the holding screw in the front of the box then lift off the front face s...

Страница 5: ...Slave unit is either another P300W C300W or D300W 2 Place the slave next to the master unit 3 Press the CONFIG button in the slave unit for 5 seconds the unit will beep to indicate each second and the...

Страница 6: ...he location space provided see below on the right 3 Within 20 seconds of removing the tag press the clear button on the side of the D300Wsmoke detector and the unit will beep release the button and th...

Страница 7: ...Battery The manual call point battery is faulty 2 MCP Communication No signal has been recieved from the Battery Fault Replace the defective Lithium 3Vcc CR 17 345 for the MCP including the One instal...

Отзывы: