the telereprogramming of their structure according to user’s requirements and/or
the teleprogramming of newly developed functions.

2. Principle of measurement and of data processing, organization

of the data memory

The measurement of four voltages and of four currents is based on sampling them
with frequency 5120 Hz. The total number of 1024 values with resolution of 14 bits
are always sampled in 200 ms long intervals, following one after another without
timeouts. After transformation into the frequency area, 512 complex harmonic com-
ponents with step 5 Hz (i. e. 51 harmonic components regarding the multiple 50 Hz)
and 461 interharmonic components are then calculated from these values. The mag-
nitudes of voltages U1 to U4, currents I1 to I4 and “control signals” (ripple control)
are calculated from the absolute values of the complete spectrum. Active and reac-
tive power of individual components as well as the unbalance are calculated from
complex components.

The data from channels U1, U2 and U3 for evaluating the events and flicker on

voltages are processed in the time area. The square of the TRMS value for the
elapsed period (20 ms) is calculated after every 10 ms. Frequency is calculated from
the data of channel U1.

Corrections of DC components, corrections of strengthening the current sensors,

of voltage and current measuring channels and frequency characteristics including
corrections of a possible phase shift between individual measuring channels are
made during the calculations. The tables of calibration constants are a part of the
configuration. None up to 100 various tables of calibration constants can be stored in
the memory of the firmware depending on the set of the whole measuring string
(measuring con measuring channels).

The non-destructive data memory, type FLASH with capacity of 2 MB (4 MB as

option) is divided into five circularly organized areas. The first area shall be used for
recording the development in time of RMS values of measured voltages, currents
and power in a complex form. Detailed data on voltage quality in the elapsed week
shall be stored in the second area. The third data area includes unified data with a
list of events according to methodology of ČSN EN 50160 and the fourth data area
includes a detailed record of the development of RMS values of the half-periods of
voltages U1, U2, U3, U4 and currents I1, I2, I3, I4. The fifth data area includes com-
pressed weekly data on quality. The ratios of ranges of individual areas of the data
memories can be mutually changed respecting the user’s requirements.

5

MEgA Měřicí Energetické Aparáty

Содержание MEg 30

Страница 1: ...MEg 30 portable version for LV networks...

Страница 2: ...MEg 31 portable version for MV networks...

Страница 3: ...r is also ready for monitoring the voltages be tween the neutral conductor and ground On its fourth current input the PQ moni tor enables to carry out the measurement and harmonics analysis of the cur...

Страница 4: ...MV networks with heterogeneous instrument voltage transformers Each version of the PQ monitor is provided with an internal back up battery which enables the monitor to be operated during up to 5 minu...

Страница 5: ...from the data of channel U1 Corrections of DC components corrections of strengthening the current sensors of voltage and current measuring channels and frequency characteristics including corrections...

Страница 6: ...ecorded when the monitor operates in this function Average values of up to four voltages four currents and three active and reactive powers U1 I1 U2 I2 U3 I3 are being recorded according to setting Ba...

Страница 7: ...nating and ending of an event with resolution to 10 ms the list of events in cludes the values of maximum deviations of voltages U1 to U3 from the nominal value Adetailed record of events includes the...

Страница 8: ...face USBII is used for displaying the shapes of voltages U1 to U4 and currents I1 to I4 The recording with duration of 2 periods 40 ms can be started case by case or repeatedly 3 6 Communication funct...

Страница 9: ...internal battery The lighting of this diode can be assigned to the indication of state of the relay output by program In a preset tolerance band 90 Unom to 106 Unom the LED diodes U1 U2 and U3 indicat...

Страница 10: ...om to 1 2 Unom 0 2 of the measured value 0 2 Unom outside 0 8 Unom to 1 2 Unom Resolution 0 1 Unom or better Temperature coefficient better than 0 2 Unom 10 C 4 2 Measurement of currents Accuracy of m...

Страница 11: ...er than 10 mHz in range 48 Hz to 52 Hz Resolution 1 mHz 4 4 Measurement of power factor Range of measurement 0 to 1 0 in all four quadrants Accuracy of measurement better than 0 5 at Unom and Inom 4 5...

Страница 12: ...ensured by protective impedance with a combination of component parts 4 12 Supply Supply from any measuring input U1 U2 U3 Range of input power 5 VA Back up supply battery SANYO N 50AAA L 1 5 in aver...

Страница 13: ...nd three LED diodes signalizing the magni tude of connected voltages being measured The case of MEg30 includes a two pole terminal board with a removable plug of the signal SYNC and a three pole termi...

Страница 14: ...supply cables is 150 cm The direction of the current flowing through the current sensors AMOS PQ and MT PQ is indicated by an arrow with an integrated marking of the current being measured I1 I2 I3 an...

Страница 15: ...s the measurement and the LED diode OPERATION PROVOZ will not be lighting any more A switched on notebook with the started program PQ monitor shall be con nected at the place of measurement to the mon...

Страница 16: ...provided by the equipment 7 Demands on maintenance The MEg30 monitor has no requirements on forced ventilation it contains no mov able control elements and beside the usual cleaning of its surface it...

Страница 17: ...ram on CD Optional parts of the set Set of flexible current sensor AMOS PQ 3 or 4 pcs Set of clamp transformers MT PQ 3 or 4 pcs Contact thermometer T PQ Set of safety alligator clips 3 pcs red 1 pc b...

Страница 18: ...correctly or if the monitor or its accessories were operated out of keeping with technical conditions The defects on the monitor and its accessories originating during the guarantee period shall be cl...

Страница 19: ...MEg 30 AMOS PQ AMOS M...

Страница 20: ...M ic Energetick Apar ty s r o Letovick 1412 4 621 00 Brno tel fax 541 225 015 mega e mega cz www e mega cz MEg 33 for fixed mounting in LV networks MEg 33 s nasazen m plombovac m krytem a bez n j...

Отзывы: