4
29/11/2017
CM2M-K
Commonly asked questions
•
When installing with a three phase fan, interlock using just one phase of the fan.
•
Always install the current monitor before any speed controllers or invertors.
•
A flashing green power LED indicates that a jumper link is missing from one of the “course sensitivity
headers”, both A & B links must be fitted even if only using one side of the CM2M-K
•
When a fan is first switched on and the power drawn is detected, the corresponding “Running LED” will flash
red for the first 15 minutes running and then become solid. This can be used to help diagnose a fan which is
intermittently cutting out.
•
The current monitor will detect a current as low as 30mAmps, if when the fans are switched on you do not
have a red flashing check the sensitivity adjustment hasn't been raised too high.
•
Wire the connection for any supply air into the main panel terminals S1 and the extract air into E1, this will
allow correct reporting of the fans in the LCD screen.
•
If you only have extract air/one fan installed (and connected to E1) leave the shorting link fitted into S1 to avoid
the main panel waiting for another fan start.
Warranty
Medem UK Warranty
Terms & Conditions
1.
The warranty is a parts warranty and Medem UK Ltd will not cover or accept any labour or other expenses
that may be incurred in the process of changing faulty product.
2.
All panels and sender units are covered by a five year warranty.
3.
Gas detector units and other remote detectors carry a two year warranty. Installation of the detectors should
not be undertaken until all building and construction work is completed.
4.
Gas solenoid valves carry the original manufacturers warranty, though as the supplier Medem UK will
exchange faulty valves for return to the manufacturer.
5.
Where a Medem UK engineer (or another company appointed by Medem UK) commission and installed
system then that system will carry a ten year warranty. This applies to the main panel and the sender unit. At
the time of commissioning a security label with a serial number will be attached to the main panel box.
photographs and a comprehensive record of the installation will be held by Medem UK.
6.
Where a warranty claim is made then, where appropriate, a written order to attend site must be provided to
Medem UK A cost for labour and travel to site will be prepared as a quote. The cost must be included in the
order.
7.
Where it is found that the installation and/or the quality of workmanship has contributed to or wholly caused
the failure of the product then we reserve the right to charge the whole or a proportion of the cost of the faulty
item.