3
00252
Main features
AGDS-V
Connections to panel: marked on board
1.
Live & Neutral 230 volt supply from 3amp switched fuse spur
2.
230 volts out to gas solenoid valve (required)
3.
Earth connection terminals
4.
AUX 1 BMS Relay
5.
AUX 2 BMS Relay
6.
Remote emergency stop and thermal links, SELV, connect in series multiple buttons (requires a N/C circuit)
7.
Fire Alarm Panel connection, (requires N/C, volt free contact in the Fire Panel)
8.
Power connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature
9.
Comms connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature
10.
Panel Mode switches (factory set, do not alter)
11.
Internal tone on/off
12.
Spare
13.
Learn field device button, press once only when all detectors are connected and powered.
14.
Display detector information 1 & 2 on screen
15.
Display detector information 3 & 4 on screen
16.
BMS Relay setting (see page 4 for details)
Power at 230
volts from a
3amp fused spur
16
1
2
3
4
6
5
7
8
9
10
11
12
13
14
15
17
18
19
EM Stop
Buttons,
Thermal links
(Normally closed)
Medem
Gas detectors
4 Core wiring
Multiple, connect in
parallel
Fire Alarm
Requires a volt
free NC contact
Earth Connections not
shown
230v Supply
3Amp Fused Spur
Gas Solenoid
230v
BMS Relays
See table on page 4 for
settings.