System description

 

AGDS-V 

Emergency Stop. To isolate the gas 
valve in the event of an emergency 

A

 Mute button, to mute the internal tone 

Reset button, for resetting and opening the valve after an alert/alarm condition.  

The AGDS-V is a gas detection system designed to monitor the atmosphere for target gases.  The system comprises of a mains 
powered panel capable of operating up to four Medem sensors 
The sensors are pre-calibrated by Medem (UK) Ltd such that they only require to be connected to the panel and functionally 
tested.  
In the event of a high alarm from one of the sensors the system will isolate the gas supply by closing a connected electric control 
valve. Emergency stop buttons and Thermal Links can be fitted and a fire alarm can close the gas valve when connected to the 
panel.  

    Control Panel 

The front of the panel has the following controls and indications: 

 

Emergency stop button. 

 

Mute button for the internal toner. 

 

Reset button for clearing an alert 

 
 

OLED display: 

 

For displaying system status during both installation and normal use, also for displaying diagnostics 

 

Содержание AGDS-V

Страница 1: ...to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commis...

Страница 2: ...Medem UK Ltd such that they only require to be connected to the panel and functionally tested In the event of a high alarm from one of the sensors the system will isolate the gas supply by closing a...

Страница 3: ...r detectors Methane LPG CO CO2 Oxygen Temperature 10 Panel Mode switches factory set do not alter 11 Internal tone on off 12 Spare 13 Learn field device button press once only when all detectors are c...

Страница 4: ...e commissioned a er installa on by Medem UK This will extend the warranty period from 5 years to 10 years and ensure the system is working as designed Please see warranty condi ons that came with the...

Страница 5: ...ctions for more guidance AGDS V Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to one another daisy chain Address...

Страница 6: ...d between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional informati...

Страница 7: ...d be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicato...

Страница 8: ...er Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry...

Страница 9: ...lay that all the detectors have been recognised by the panel 10 At this point press the reset button the panel will open the gas valve Checklist AGDS V Please do not hesitate to call for advice on the...