background image

13/12/2017 

Detector Information 

Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for.  
The descriptions below describe the position for each detector after considering these characteristics.  
 
For proper function care must be taken not to site a detector in a “dead space” or in the flow of any ventilation. 
 

Natural Gas/Methane 

Natural gas detectors should be mounted at high level on a wall approximately 150mm from the ceiling height and avoiding 
corners and potential dead air areas. 
 
Natural gas detectors should not be mounted below the height of the top of a doorway for example. This is because as the gas 
is slightly lighter than air it will rise filling the room from the ceiling down and will spill through the top of a door opening into the 
next room. If the detectors are mounted below this height then it will take longer the gas to reach the detector. 
 

LPG /Propane 

LPG gas is heavier than air so detectors need to be mounted at low level 100mm from the floor, consideration should be given 
to any potential mopping or wet floor height. 
 

Carbon Monoxide  

Carbon Monoxide is similarly weighted to air so detectors should be mounted between 1 to 2 meters from the floor. 
 

Carbon Dioxide  

Carbon Dioxide detectors should be installed so they monitor the general level of CO2 within the area. They should be mounted 
above standing head height and between 1m and 3m from the potential source. Care should be taken so they are not located 
close to the edge of a canopy or in direct flow of the supply or extract ventilation. 
 

For additional information or guidance on site specific requirements please don’t hesitate to contact us. 

Each detector has  its own Bi-Colour LED which is used to indicate the status of that detector. 
 
Not Lit:  

 

No power/comm’s. These a four wire units and all connections are required, check the polarity of both the 

 

 

 

power and the comm’s (MA/MB) terminals are correct. Check the detector is address to the correct channel 

 

 

 

and the channel has been enabled using switch (

12

 

Flashing Green: 

Detector is warming up, the detectors will flash green on power up for 90 seconds while the sensor  

 

 

 

elements stabilize. The system will ignore any detectors while flashing.  

 
Solid Green:   

Detector is powered and active.  

 

Flashing Red:  

Low level alarm. All detectors have both a low and high level alarm, low level alarms serve as a warning 

 

 

 

that an unsafe condition maybe building and gives chance to intervene before loss of gas service. 

 
Solid Red 

 

High level alarm. An unsafe level of the target gas have been reached and the system will isolate the  

 

 

 

gas supply. The cause of the alarm will require identifying and resolving before  the gas supply can be re-

 

 

 

established. 

 
After installation a simple bump test can be performed by using an appropriate level test gas in order to check operation. Full 
testing and calibration checking takes place during a Medem commissioning. 

AGDS-2 

    Detector Location information 

    Detector Indications 

Содержание AGDS-2

Страница 1: ...alled and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer...

Страница 2: ...gh alarm Carbon Monoxide detectors are pre calibrated at 80ppm pre alarm and 100ppm for high alarm Connect a detector to either the detector 1 terminals 6 7 or detector 2 terminals 8 9 each detector h...

Страница 3: ...connection Reset 12 Enable Detectors Channels enable a channel when it has a detector connected 13 High alarm time delay function Controls the length of time between a High alarm and the closing of th...

Страница 4: ...be followed with reference to running low and mains voltage cables together The maximum cable length between a detector and the control panel should not exceed 100 metres if the distance between the...

Страница 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Страница 6: ...s that is being monitored for See the gas detectors own instructions for more guidance AGDS 2 Detector Information VE supply Comm s From either the main panel Address Selector The selector must be set...

Страница 7: ...ng head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For add...

Страница 8: ...lier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carr...

Страница 9: ...ector 1 or detector 2 on the panel 5 Enable the detector channels 1 or 2 as being used by with switch 12 Connect the 3 amp fused spur 240 volt supply to marked terminals 6 Once power is connected to t...

Отзывы: