OWNER’S MANUAL

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1 Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: 

Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: 

Space size  20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

______________ Btu/Hr

Gas water heater*

______________ Btu/Hr

Gas furnace

______________ Btu/Hr

Vented gas heater

______________ Btu/Hr

Gas fireplace logs

______________ Btu/Hr

Other gas appliances* +

______________ Btu/Hr

Total                            =

______________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________________ Btu/Hr (maximum the space can support)

_____________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200  Btu/Hr (maximum the space can support)

54,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Continued

Example:

Gas water heater

44,000

Btu/Hr

Vent-free heater   +

10,000

Btu/Hr

Total                     =

54,000

Btu/Hr

Содержание MBP10LA

Страница 1: ...adequate com bustion and ventilation air must be provided Refer to Air For Combustion and Ventila tion on page 4 of this manual 10 000 and 6 000 Btu Hr Manually Controlled Models WARNING Improper ins...

Страница 2: ...n oxygen depletion sensor ODS pilot light safety system The ODS shuts down the heater if not enough fresh air is available See Fresh Air for Combus tion and Ventilation pages 4 through 6 5 Keep all ai...

Страница 3: ...al Fire Protection Association Inc Batterymarch Park Quincy MA 02269 UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any ship...

Страница 4: ...ustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings ex...

Страница 5: ...uel burning appliances in the space Vent free heater ______________ Btu Hr Gas water heater ______________ Btu Hr Gas furnace ______________ Btu Hr Vented gas heater ______________ Btu Hr Gas fireplac...

Страница 6: ...PA 54 ANS Z223 1 Section5 3 AirforCombustionand Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermos...

Страница 7: ...sory page 18 LOCATING HEATER This heater is designed to be mounted on a wall WARNING Maintainthemini mumclearancesshowninFigure 4 Ifyoucan providegreaterclear ances from floor ceiling and joining wall...

Страница 8: ...s ANCHOR Figure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place...

Страница 9: ...from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly Installationmustincludeaequipmentshutoff valve ground joint union and plugged 1 8 NP...

Страница 10: ...opane LP supply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 15 Apply mixture of liquid soap and wa...

Страница 11: ...f control knob does not pop up when released contact a qualified service person or gas supplier for repairs 6 With control knob pressed in push down and release ignitor button This will light pilot Th...

Страница 12: ...LOT FLAME PATTERN Figure 18 shows a correct pilot flame pat tern Figure 19 shows an incorrect pilot flame pattern The incorrect pilot flame is not touching the thermocouple This will cause the thermoc...

Страница 13: ...maged OBSERVED PROBLEM When ignitor button is pressed there is no spark at ODS pilot When ignitor button is pressed there is spark at ODS pilot but no ignition ODS pilot lights but flame goes out when...

Страница 14: ...em will stop after a few hours of operation 1 Turn control knob to LOW position and let warm up for a minute 2 Operate burner until air is removed from line Have gas checked by local propane LP gas co...

Страница 15: ...burning vapors from paint hair spray glues etc See IMPORTANT statement above 2 Low fuel supply 3 Gas leak SeeWarning statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3...

Страница 16: ...16 105716 PROPANE LP GAS HEATER MBP10LA AND MBP6LA MBP10LA MBP6LA 12 2 12 1 ILLUSTRATED PARTS LIST 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 17 18 21 22 25 20 24 23 19 26 27 16...

Страница 17: ...01 098249 01 Nut M5 2 12 099059 03 099059 03 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 098594 01 098594 01 Ignitor Electrode 1 13 104263 02 104263 01 Burner 1 14 099387 05 099...

Страница 18: ...ctory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they cannot supply original replacement part s contact Cans Unlimited Incorporated s Parts Department at 1 800 922 7407 for...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...ns furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents...

Отзывы: