HMI PLC all in one: TPAC1008 03 Mect srl
ME7068_05 11/19
24
Conf 10: 0 ÷ 1500
1 digit resolution
values: 0 ÷ 1500°C
PLC_AnIn_4
Analog input 4
value
RO Conf 1: 0 ÷ 20000
5 digit resolution
values: 0.0 ÷
20.000mA
Conf 2: 0 ÷ 10000
3 digit resolution
values: 0.0 ÷ 10.000V
Conf 3: 0 ÷ 600
1 digit resolution
values: 0 ÷ 600°C
Conf 4: 0 ÷ 1200
1 digit resolution
values: 0 ÷ 1200°C
Conf 5: 0 ÷ 400
1 digit resolution
values: 0 ÷ 400°C
Conf 6: -40 ÷ 800
1 digit resolution
values: -40 ÷ 800°C
Conf 7: -400 ÷
2000
1 digit resolution
values: -40.0 ÷
200.0°C
Conf 8: 0 ÷ 1710
1 digit resolution
values: 0 ÷ 1710°C
Conf 9: 100 ÷
1800
1 digit resolution
values: 100 ÷ 1800°C
Conf 10: 0 ÷ 1500
1 digit resolution
values: 0 ÷ 1500°C
PLC_FiltAnIn_1
Filter
RW Analog input 1 moving average
PLC_FiltAnIn_2
Filter
RW Analog input 2 moving average
PLC_FiltAnIn_3
Filter
RW Analog input 3 moving average
PLC_FiltAnIn_4
Filter
RW Analog input 4 moving average
PLC_AnOutConf_1
Analog output 1
configuration
RW
0 not configured
1 current
2 voltage
PLC_AnOutConf_2
Analog output 2
configuration
RW
0 not configured
1 current
2 voltage
PLC_AnOutConf_3
Analog output 3
configuration
RW Not used
PLC_AnOutConf_4
Analog output 4
configuration
RW Not used
PLC_AnOut_1
Analog output 1
RW Conf 1 (mA)
0 ÷ 2000
Conf 2 (V)
0 ÷ 1000
PLC_AnOut_2
Analog output 2
RW Conf 1(mA)
0 ÷ 2000
Conf 2 (V)
0 ÷ 1000
PLC_AnOut_3
Analog output 3
RW Conf 2 (V)
0 ÷ 1000
PLC_AnOut_4
Analog output 4
RW Conf 2 (V)
0 ÷ 1000
PLC_Tamb
Cold junction
compensation
RO 0 ÷ 1000 1 digit
Resolution
Values: 0.0 ÷ 100.0
PLC_EnableEnc
Enable encoder 5
RW 1: sets bidirectional encoder
2: sets counter
input A (M2-9) (In2) counter direction 0
= CUp, 1= CDown
input B (M2-8) (In3) clock
PLC_ResetCount
Reset Encoder 5
RW 1: encoder/counter reset