DER2 digital regulator instruction manual - rev. 02 - pag. 22
The parameter P[9] sets the excitation current limit: the value P[9]=0 is setting to zero the excitation
current, while the maximum value P[9]=32767 is removing the current limitation. The default value is P[9]
=32767. When the interval of action of the soft start has been exceeded, the output voltage moves to the
value set. The rapidity of the change is set by parameter P[18] (see paragraph on "Slow voltage
variations”)
1.2 Soft Start
In the event of fast start up of the prime mover or sudden regulator excitation with the generator running at
nominal speed an uncontrolled regulator could result in a temporary generator overvoltage or in a
transitory prime mover overload due to the high peak of excitation current..
These effects can be minimised by setting parameter “Delay” and “Excitation Limit” in the area “Soft-Start”
of the
Settings/Advanced
menu, corresponding to parameters P[8] and P[9] : during starting, they
determine a limit of the excitation current.
Parameter P[8] sets the duration of the excitation current limitation, namely the value of the parameter
corresponds to the number of periods in which the limitation is active. The default value is P[8]=0 which
corresponds to deactivation of the soft start. Considering that in most cases the alternator is already at
nominal speed, an estimate in temporal terms (corresponding to the setting “Delay” in Soft-Start area) for 4
pole machines, may be obtained with the formula:
SETTING OF VOLT, STAB, AMP and Hz PARAMETERS.
1. Voltage
1.1 Setting voltage.
Setting can take place through the trimmer or software: on sensing inputs 6/7 – 10/11/12 (with bridge 8-9),
15-16 and 20-21, the voltage can be set between 75÷150 Vac (scale H); on sensing inputs 4/5 -
9/10/11/12, 14-17 and 19-22 between 150÷300 Vac (scale F).
There are two ways to set from minimum to maximum value:
1. With the VOLT trimmer, which must be enabled by the
Settings/potentiometers
menu of DxR Termi-
nal software
2. With parameter P[19] (The Volt trimmer must be enabled from the
Settings/Potentiometers
menu:
the value 0 corresponds to minimum voltage, 16384 corresponds to the intermediate value
(respectively 112.5 V and 225 V), while 32767 corresponds to maximum voltage.
The setting is facilitated using the software DxR Terminal, through
Settings/Potentiometers menu.
It is possible to vary voltage with respect to the value set, with the Pext input (terminals 29-30) if enabled
from the area Pext/Vext in the
Settings/Advanced
menu, with a 25Kohm or 100Kohm potentiometer, with
a range of variation that can be programmed up to ±100% (parameter P[16]. The default setting is ± 14%,
even if it is opportune not to exceed ±10%). Alternatively, variation can be made with continuous voltage
applied on Pext (terminal 30) or ±10V (terminal 32), based on the value of that voltage. If the Pext voltage
is disabled, it is possible to vary the voltage with parameter P[15] or location L[49]. For additional details
see the paragraph "Remote control of voltage".
Where f
n
= nominal frequency in Hz or
n
= nominal speed in R.P.M
n
n
P
f
P
t
30
]
8
[
1
]
8
[
lim
By way of example, for high power alternators of the ECO46 series, the following settings may be
experimented: Delay=1280ms (P[8]=64) and Excitation limit=50% (P[9]=16384); for low power alternators of
the ECP3 series, the effects of a reduction of both the duration and limitation of the current may be
experimented, such as Delay=320ms (P[8]=16) and Excitation limit=3,72% (P[9]=4096).
The optimal values of “Delay” and “Excitation limit” (parameters P[8] and P[9]) depend a great
deal on the type of alternator and final application and it must be found through experimentation.
An inappropriate setting of parameters P[8] and P[9] could cause failure of the alternator to
excite itself.
Содержание DER2
Страница 2: ...DER2 digital regulator instruction manual rev 02 pag 2...
Страница 11: ...DER2 digital regulator instruction manual rev 02 pag 11 SCC0301 01 Three phase sensing 75V 150V...
Страница 12: ...DER2 digital regulator instruction manual rev 02 pag 12 SCC0302 01 Three phase sensing 150V 300V...
Страница 13: ...DER2 digital regulator instruction manual rev 02 pag 13 SCC0303 01 Single phase sensing 75V 150V...
Страница 14: ...DER2 digital regulator instruction manual rev 02 pag 14 SCC0304 01 Single phase sensing 150V 300V...
Страница 15: ...DER2 digital regulator instruction manual rev 02 pag 15 SCC0305 01 Single phase sensing 300V 600V...
Страница 35: ...DER2 digital regulator instruction manual rev 02 pag 35...