59
0x0097~
0x0099
0x00B0
0x00B1
0x00B2
0x00B3
0x00B4
0x00B5
0x00B6
0x00B7
0x00B8
0x00C0
0x00C3
0x00C4
0x03
0x03、0x06
0x03、0x06
0x03、0x06
0x03、0x06
0x03、0x06
0x03、0x06
0x03、0x06
0x03、0x06
0x03
0x03
0x03
0x03、0x06
1
2
2
2
2
2
2
2
2
2
2
2
2
MFR_SERIAL_
B6B11
CURVE_CC
CURVE_CV
CURVE_FV
CURVE_TC
CURVE_CONFIG
CURVE_CC_
TIMEOUT
CURVE_CV_
TIMEOUT
CURVE_FV_
TIMEOUT
CHG_STATUS
SCALING_FACTOR
SYSTEM_STATUS
SYSTEM_CONFIG
Command
Name
# of data
Bytes
Description
Manufacture serial number
Constant current setting of
charge curve
(format: value, F=0.01)
Constant voltage setting of
charge Curve
(format: value, F=0.01)
Floating voltage setting of
charge curve
(format: value, F=0.01)
Taper current setting
of charge curve
(format: value, F=0.01)
Configuration setting of
charge curve
CC charge timeout setting
of charging curve
CV charge timeout setting
of charging curve
FV charge timeout setting
of charging curve
Charging status reporting
Scaling ratio
System status
System configuration
Register
address
Function
code
0x008C~
0x008E
0x008F~
0x0090
0x0091~
0x0093
0x0094~
0x0096
0x03
0x03
0x03
0x03
6
3
3
3
MFR_REVISION_
B0B5
MFR_LOCATION_
B0B2
MFR_DATE_B0B5
MFR_SERIAL_
B0B5
Firmware version
Manufacture place
Manufacture date
Manufacture serial number
6
0x0089~
0x008B
0x03
6
MFR_MODEL_
B6B11
Manufacture model name
V
alid
w
C
URVE_C
O
NFIG:CUVE
=
1
hen
60
◎
FAULT_STATUS (0x0040)
:
Low byte:
Bit 1 OTP:
Over temperature protection
0=
Internal temperature normal
1=
Internal temperature abnormal
Bit 2 OVP:Output over voltage protection
-
0=
Output voltage normal
1=Output over voltage protected
Bit 3 OLP:
Output over current protection
0=
Output current normal
1=
Output over current protected
-
Bit 4 SHORT:Short circuit protection
0=Shorted circuit do not exist
1=Shorted circuit protected
Bit 5 AC_FAIL:AC abnormal flag
0=
AC range normal
1=
AC range abnormal
Bit 6 OP_OFF:
DC status
0=DC turned on
1=DC turned off
Bit 7 HI_TEMP:Internal high temperature protection
0=
Internal temperature normal
1=
Internal temperature abnormal
: Unsupported settings displays with "0"
Note
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Low byte
OVP
OTP
-
OP_OFF
AC_FAIL SHORT
OLP
HI_TEMP
Note: The conversion of setting and reading values is defined as
following: Actual value = Communication reading value Factor (F
value). Among them, Factor needs to refer to the definition of
SCALING_FACTOR in each model list.
EX: VDC_real (actual DC voltage) = READ_VOUT x Factor. If the Factor of
READ_VOUT of a certain model is 0.01, the communication reading
value is 0x0960 (hexadecimal) → 2400 (decimal), then VDC_real =
2400 x 0.01 = 24.00V.
6