Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
26
26
4.3.2 Status value 1-3
The following settings are available:
Figure 9: Settings
–
Info display: Status values 1-3
The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
State values 1 - 3
▪
not active
▪
On/Off (DPT 1.001)
▪
Percent 0…100% (DPT 5.001)
▪
Value 0…255 (DPT 5.005)
▪
Current (mA) (DPT 7.012)
▪
Brightness (Lux) (DPT 7.013)
▪
Temperature (°C) (DPT 9.001)
▪
Brightness (Lux) (DPT 9.004)
▪
Wind speed (m/s) (DPT 9.005)
▪
Humidity (%) (DPT 9.007)
▪
Air quality (ppm) (DPT 9.008)
▪
Current (mA) (DPT 9.021)
Setting the DPT to be
displayed as status value.
Labelling
“Unit”
any text
[up to 5 bytes allowed]
Enter the text describing the
unit.
Labelling
“Value”
any text
[up to 15 bytes allowed]
Enter the text describing the
measurement.
Table 15: Settings
–
Info display: Status values 1-3
The following table shows the available communication objects:
Number Name/Function
Length
Usage
82
Status text 1
14 Byte Receiving a status text
83
Status text 2
14 Byte Receiving a status text
84
Status value 1
Receiving a status value.
DPT according to parameter setting
85
Status value 2
Receiving a status value.
DPT according to parameter setting
86
Status value 3
Receiving a status value.
DPT according to parameter setting
Table 16: Communication objects
–
Info display: Status values 1-3