Operating mode after reset
The following table shows the possible settings for this parameter:
ETS-Text
Dynamic range
[Default value]
Comment
Operating mode after reset
▪
Comfort with
parameterised setpoint
▪
Standby with
parameterised setpoint
▪
Maintain previous state
and setpoint
Setting which operating mode or
behaviour should be activated after a
bus voltage recovery
Table 45: Settings - Operating mode after reset
This parameter defines the operating mode, which shall be adjusted after a bus power return:
•
Comfort with parameterized setpoint
After a bus power return, comfort is activated with the setpoint, which was set by the ETS.
•
Standby with parameterized setpoint
After a bus power return, standby is activated with the setpoint, which was set by the ETS
(Comfort-Setpoint - Standby reduction).
•
Hold old state and setpoint
The temperature controller calls the setpoint and mode, which was set before bus power
down.
Attention:
After reprogramming the device, the memory is erased and there are no previous
settings. In this special case, the controller is therefore in
Standby
with the corresponding
parameterized setpoint!