OMM TGZ-1
TGZ 040A through TGZ 190A
9
Table 3, Wire Sizing Amps, Optional Single Point Power Supply
MINIMUM CIRCUIT AMPACITY (MCA)
POWER SUPPLY
WITHOUT EXTERNAL OL'S
WITH EXTERNAL OL’S
TGZ
UNIT
SIZE
VOLTS
FREQ.
(HERTZ)
SINGLE POINT
POWER SUPPLY )
WITHOUT EXT OL'S
SINGLE POINT
POWER SUPPLY
WITH EXT OL'S
FIELD WIRE
QUANTITY
WIRE GAUGE
75
°
°
°
°
C
FIELD WIRE
QUANTITY
WIRE GAUGE
75
°
°
°
°
C
208
150
131
3
1/0
3
1/0
230
150
119
3
1/0
3
#1
460
76
60
3
#4
3
#6
040
575
60
49
48
3
#8
3
#8
208
204
179
3
4/0
3
3/0
230
204
163
3
4/0
3
2/0
460
93
82
3
#3
3
#4
050
575
60
85
65
3
#4
3
#6
208
230
230
3
4/0
3
4/0
230
224
207
3
4/0
3
4/0
460
109
104
3
#2
3
#2
060
575
60
90
83
3
#3
3
#4
208
311
247
3
400
3
250
230
311
224
3
400
3
4/0
460
128
112
3
#1
3
#2
080
575
60
104
90
3
#2
3
#3
208
311
294
3
400
3
350
230
311
265
3
400
3
300
460
150
133
3
1/0
3
1/0
100
575
60
120
107
3
#1
3
#2
208
357
338
6 (2)
3/0
6 (2)
2/0
230
357
305
6 (2)
3/0
3
350
460
173
152
3
2/0
3
2/0
110
575
60
139
122
3
1/0
3
#1
208
398
377
6 (2)
3/0
6 (2)
3/0
230
398
340
6 (2)
3/0
6 (2)
2/0
460
193
170
3
3/0
3
2/0
120
575
60
155
136
3
2/0
3
1/0
208
457
433
6 (2)
4/0
6 (2)
4/0
230
457
390
6 (2)
4/0
6 (2)
3/0
460
221
195
3
4/0
3
3/0
150
575
60
176
158
3
3/0
3
2/0
208
524
496
6 (2)
300
6 (2)
250
230
524
447
6 (2)
300
6 (2)
4/0
460
254
224
3
250
3
4/0
170
575
60
203
180
3
4/0
3
3/0
208
585
555
6 (2)
350
6 (2)
300
230
585
500
6 (2)
350
6 (2)
250
460
284
250
3
300
3
250
190
575
60
228
200
3
4/0
3
3/0
NOTES:
.
1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of the other compressor RLA's.
2. Single point power supply requires a single fused disconnect to supply electrical power to the unit.
3. External compressor overload option is only available for units with 140
°
F maximum leaving condenser water temperature.
4. Wire Sizes shown above are for standard ambient temperature and short runs of wire.