8
TGZ 040A through TGZ 190A
OMM TGZ-1
Table 2, Wire Sizing Amps, Standard Multi-Point Power Supply
MINIMUM CIRCUIT AMPACITY (MCA)
POWER SUPPLY
WITHOUT EXTTERNAL
OVERLOADS
WITH EXTERNAL
OVERLOADS
WITHOUT EXTERNAL
OVERLOADS
WITH EXTERNAL
OVERLOADS
MULTIPLE POINT POWER SUPPLY
WIRE GAUGE
75
°
°
°
°
C
WIRE GAUGE
75
°
°
°
°
C
TGZ
UNIT
SIZE
VOLTS
FREQ.
(HERTZ)
CIRCUIT
NO.1
CIRCUIT
NO.2
CIRCUIT
NO.1
CIRCUIT
NO.2
FIELD
WIRE
QTY.
CIRCUIT
NO.1
CIRCUIT
NO.2
FIELD
WIRE
QTY.
CIRCUIT
NO.1
CIRCUIT
NO.2
208
79
79
69
69
3
#4
#4
3
#4
#4
230
79
79
63
63
3
#4
#4
3
#6
#6
460
40
40
32
32
3
#8
#8
3
#10
#10
040
575
60
26
26
25
25
3
#10
#10
3
#10
#10
208
108
108
95
95
3
#2
#2
3
#3
#3
230
108
108
86
86
3
#2
#2
3
#3
#3
460
49
49
43
43
3
#8
#8
3
#8
#8
050
575
60
45
45
34
34
3
#8
#8
3
#10
#10
208
122
122
122
122
3
#1
#1
3
#1
#1
230
118
118
110
110
3
#1
#1
3
#2
#2
460
58
58
55
55
3
#6
#6
3
#6
#6
060
575
60
48
48
44
44
3
#8
#8
3
#8
#8
208
165
165
131
131
3
2/0
2/0
3
1/0
1/0
230
165
165
119
119
3
2/0
2/0
3
#1
#1
460
68
68
59
59
3
#4
#4
3
#6
#6
080
575
60
55
55
48
48
3
#6
#6
3
#8
#8
208
165
165
156
156
3
2/0
2/0
3
2/0
2/0
230
165
165
140
140
3
2/0
2/0
3
1/0
1/0
460
79
79
70
70
3
#4
#4
3
#4
#4
100
575
60
64
64
57
57
3
#6
#6
3
#6
#6
208
165
211
156
200
3
2/0
4/0
3
2/0
3/0
230
165
211
140
180
3
2/0
4/0
3
1/0
3/0
460
79
102
70
90
3
#4
#2
3
#4
#3
110
575
60
64
82
57
72
3
#6
#4
3
#6
#4
208
211
211
200
200
3
4/0
4/0
3
3/0
3/0
230
211
211
180
180
3
4/0
4/0
3
3/0
3/0
460
102
102
90
90
3
#2
#2
3
#3
#3
120
575
60
82
82
72
72
3
#4
#4
3
#4
#4
208
238
238
225
225
3
250
250
3
4/0
4/0
230
238
238
203
203
3
250
250
3
4/0
4/0
460
115
115
101
101
3
#2
#2
3
#2
#2
150
575
60
92
92
82
82
3
#3
#3
3
#4
#4
208
238
304
225
289
3
250
350
3
4/0
350
230
238
304
203
260
3
250
350
3
4/0
300
460
115
148
101
130
3
#2
1/0
3
#2
#1
170
575
60
92
119
82
104
3
#3
#1
3
#4
#2
208
304
304
289
289
3
350
350
3
350
350
230
304
304
260
260
3
350
350
3
300
300
460
148
148
130
130
3
1/0
1/0
3
#1
#1
190
575
60
119
119
104
104
3
#1
#1
3
#2
#2
NOTES:
1.
Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of the other compressor RLA's.
2.
Multiple point power supply requires a separate fused disconnect for each circuit to supply electrical power to the unit.
3.
External compressor overload option is only available for units with 140
°
F maximum leaving condenser water temperature.
4.
Wire sizes shown above are for standard ambient temperature and short runs of wire.