McQuay Skyline IM 777-2 Скачать руководство пользователя страница 22

22

McQuay IM 777-2

Service and Maintenance

Service and Maintenance

Periodic Service and Maintenance

1

Check all moving parts for wear every six months.

2

Check bearing collar, sheave, and wheel hub setscrews, 
sheave capscrews, and bearing hold-down bolts for 
tightness every six months.

3

Annually check and snug all electrical connections. Inspect 
for signs of water damage such as corrosion and repair if 
necessary. Check ground conductor and connection 
integrity. Service if needed.

Ball Bearing Lubrication

1

Motor bearings—All ball bearings are prelubricated and do 
not require additional grease at time of installation. 
However, periodic cleaning out and renewal of grease is 
necessary. Exercise extreme care to prevent foreign matter 
from entering the bearing. It also is important to avoid over 
greasing. Use a high grade, clean mineral grease with the 
following characteristics:

• 

Melting point over 302°F (150°C)

• 

Free from oil and soap separation under operating and 

storage conditions

• 

Free of abrasive matter, acid, alkali and moisture

Specific greasing instructions are located on a label 
attached to the fan section door.

2

Fan shaft bearings—All ball bearings are prelubricated and 
do not require addition of grease at time of installation. 
However, periodic renewal of grease is necessary. Bearings 
are accessible through access door in fan section. Grease 
fittings are located in front of door opening on drive end of 
blower section. Apply grease slowly until a very slight 
bleeding of grease from the seals is noted. Tie hinged 
door(s) open. 

Do not over lubricate.

 Wipe off any excess 

grease to prevent overheating.

The lubrication interval varies with the period of operation 
and temperature of the ambient air. Use the guidelines in 
the table below.

Note

: Temperature ranges over 225°F are shown for lubricants only. High 

temperature applications are not suitable for standard air handler 

components.

Fan Drive Adjustments

Upon completion of the air balance, replace the variable 
pitched motor sheave with a properly sized, fixed sheave. A 
matching fixed sheave provides longer belt and bearing life 
and minimizes vibration. Initially, it is best to have a variable 
pitched motor sheave for the purpose of air balancing. Once 
the balance is achieved, fixed sheaves maintain balancing and 
alignment more effectively. Replace the adjustable sheaves 
with fixed sheaves.

With the electrical power disconnected, locked and tagged out, 
measure the diameter of the V-belt outer surface where it 
passes around the sheave (pitch diameter). Calculate fan speed 
from the motor nameplate rpm.

Table 12: Lubrication Guidelines

Bearing operating temp range

Temperature

to 130°F 

(54°C)

to 150°F 

(66°C)

over 150°F 

(66°C)

Continuous operation

6 months

4 months

2 months

12-hr. day operation

12 months

12 months

6 months

Table 13: Lubricants Recommended for Fan Shaft Ball 
Bearings

Manufacturer

Product name

Temp. range

°F

°C

Texaco Lubricants Company

 Premium RB

–30 to 300 –34 to 149

 Keystone Ind. Lubricants

 81EP-2

 0 to 250

18 to 121

 Mobil Oil Corporation

 Mobilith SCH100

40 to 350

40 to 177

 Chevron U.S.A. Inc.

 SRI-2

20 to 325

29 to 163

 Exxon Company, U.S.A.

 Ronex MP

40 to 300

40 to 149

 Shell Oil Company

 Alvania No. 2

20 to 240

29 to 116

WARNING

Before servicing fans, lock out and tag out all power to the 
unit.

 Fans or belts can cause severe personal injury or death.

AVERTISSEMENT

Avant de faire le service sur les ventilateurs,couper et 
indiquer que le courant est coupé.

 Les ventilateurs ou les 

courroies peuvent causer des blessures personnelles graves 
ou entraîner la mort.

WARNING

Do not open the hinged access door and screw-fastened 
access panels while the unit is operating. 

Moving parts and 

strong suction forces can cause severe personal injury or death.

AVERTISSEMENT

Ne pas ouvrir les portes d’accès à charnières et les 
panneaux à vis lorsque l’unité fonctionne.

 Les pièces 

mobiles et le niveau de succion peuvent causer des blessures 
personnelles graves ou même entraîner la mort.

Fan rpm = motor rpm ×

Measured diameter at motor sheave
Measured diameter at fan sheave 

Содержание Skyline IM 777-2

Страница 1: ...Installation and Maintenance Manual IM 777 2 Skyline Air Handler Group Applied Air Sizes 003 090 Part Number IM 777 Date July 2007 2007 McQuay International...

Страница 2: ...ounting 10 Piping Vestibules 10 Piping and Coils 10 Drain Pan Traps 13 Internal Isolation Assembly Adjustment 14 Electrical Installation 14 Operation Guidelines 16 Startup Checks 16 Fan Wheel Alignmen...

Страница 3: ...and shaft before unit installation to verify this has not happened Screws bolts etc for assembling sections are supplied in a bag attached to each section All necessary gasketing is applied in the fa...

Страница 4: ...12 deep See Figure 2 Figure 1 Servicing Space Requirements Figure 2 Service Clearance for Electrical Power Devices Rigging Skyline air handlers ship as separate sections completely assembled or in mo...

Страница 5: ...1 Caulk all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the mating faces of the cabinet Use the splice joint as a guide for applying th...

Страница 6: ...flanges Bend the ends of the splice cap down to secure in place 6 Assemble the small splice plate at the top rail to secure the sections together at the top Use 5 16 bolts See Figure 9 Figure 9 Splic...

Страница 7: ...quire the use of tools to access compartments containing moving parts or electrical wiring See Figure 11 1 Remove padlock if one is present 2 Insert 1 2 socket into cup and rotate 1 4 turn clockwise a...

Страница 8: ...ccur If larger heavier components require mounting on unit panels use through bolts with flat washers through both outer and inner panels To maintain panel integrity seal both ends with an industrial...

Страница 9: ...er Between Hoods Mounting Actuators The installing contractor is responsible for the mounting of all field installed actuators No provisions are made for the location of these actuators due to the num...

Страница 10: ...cal codes and industry standards Do not apply undue stress at the connection to coil headers always use a backup pipe wrench Support pipework independently of the coils Water Cooling Coils Note Use gl...

Страница 11: ...thermostatic or bucket traps for low pressure steam On high pressure steam use bucket traps Use thermostatic traps only for air venting Use bucket traps for on off control only Locate traps at least 1...

Страница 12: ...Return main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two position Float and thermostatic tr...

Страница 13: ...drain pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the static...

Страница 14: ...when adjustments are completed For models 040 through 090 the isolators should be at equal height during fan operation 6 Center the fan outlet in the outlet panel opening If adjustment is required lo...

Страница 15: ...vicing Perform lockout tagout procedures to ensure that power can not be energized For variable frequency drives or other energy storing components that have been furnished and mounted by either McQua...

Страница 16: ...Can cause property damage personal injury or death Wire fan power supply and ground motor frame in accordance with local electric codes AVERTISSEMENT Risques d incendie et d lectrocution pouvant cause...

Страница 17: ...by loosening wheel hub setscrews shifting wheel s axially as needed and retightening setscrews Figure 26 Wheel to Inlet Funnel Relationship Plenum Fans Table 2 Wheel to Inlet Funnel Relationship Airf...

Страница 18: ...line Fans Wheel funnel overlap Size Overlap 150 375 165 438 182 562 200 625 222 688 245 750 270 812 300 875 330 1 000 365 1 125 402 1 250 445 1 375 Overlap Table 6 Bearing Collar and Wheel Hub Set Scr...

Страница 19: ...56 24 00 Maximum rpm Class I 3000 3000 2300 2000 1700 1500 Maximum rpm Class Il 4335 3918 3457 2858 2427 2255 300 250 200 150 100 90 80 Torque in lb 350 400 450 500 600 650 700 750 800 850 1000 1500...

Страница 20: ...ameter 13 5 15 16 5 18 25 20 22 25 24 5 27 30 33 36 5 40 25 44 50 49 54 25 60 Maximum rpm Class I 2895 2589 2376 2256 2077 1875 1691 1479 1328 1209 1073 972 882 799 725 651 Maximum rpm Class II 3786 3...

Страница 21: ...t or debris on wheel blades b Loose set screws in wheel hub or bearing to shaft c Wheel distorted from overspeed 2 Bent shaft 3 Drive faulty a Variable pitch sheaves Axial and radial runout of flanges...

Страница 22: ...nts Upon completion of the air balance replace the variable pitched motor sheave with a properly sized fixed sheave A matching fixed sheave provides longer belt and bearing life and minimizes vibratio...

Страница 23: ...3 Replace external key E and securely tighten setscrews B over key and setscrews C into keyway in fixed half of the sheave 4 Put on belts and adjust belt tension Do not force belts over grooves See F...

Страница 24: ...ews E 9 Put on belts and adjust belt tension Do not force belts over grooves See Fan Drive Belt Adjustment on page 26 10 Before starting the drive ensure that all keys are in place and all setscrews a...

Страница 25: ...s or 6 turns for the B belts Do not open C sheaves more than 9 1 2 turns Do not open 5V sheaves more than 6 turns Do not open 8V sheaves more than 8 turns 6 Tighten BOTH locking screws A in the outer...

Страница 26: ...o N o t R e m o v e I n n e r L o c k i n g R i n g O u t e r L o c k i n g R i n g S p l i t T a p e r B u s h i n g 3 H o l e s f o r S p a n n e r W r e n c h o r D r i f t Belt span Deflection Bel...

Страница 27: ...Filter Gauge Table 15 Belt Deflection Force per Browning specifications Cross section Sheave diameter in Deflection force lbs Smallest sheave diameter range rpm range Cross section A B 5V Cross secti...

Страница 28: ...ls Removing and Replacing Components See Access Doors and Panels on page 7 for instructions on removing panels and opening fan access doors to remove or replace components Removing the Fan Section The...

Страница 29: ...in place with a clamp See Figure 41 1 Disconnect all piping and remove the brass plugs for the vents and drains located in the connections 2 Remove all screws and remove the access panel 3 Remove the...

Страница 30: ...ce bolt the coil to the section 4 Caulk the mounting surface of the steel plate and install the plate on the coils 5 Caulk the mounting surface of the drain trough and install the drain trough on the...

Страница 31: ...arges must be prepaid The return of the part does not constitute an order for replacement Therefore a purchase order must be entered through the nearest McQuay representative The order should include...

Страница 32: ...training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consul...

Отзывы: