Unit Protective Logic

Compressor Minimum Run Time

For thermostat-controlled running cycles, the compressor will
have a minimum run time of 90 seconds. The compressor can
be stopped at any time if the system is switched to any Mode,
except the Cool Dry Mode.

Compressor Minimum Off Time (delay on break)

When compressor is under the thermostat control, it has a 2-
minute delay before restarting when it has cycled off.

Anti-freeze Protection

In Anti-Freeze Mode, the compressor and outdoor fan will be
stopped and the display will show “AF”. The compressor and
outdoor fan can be started only if the following conditions are
met:
1.

after the 2 minute delay on break, AND

2.

the indoor coil reaches 54°F or above and remains there for
at least 1 minute, OR

3.

another Mode is selected.

The system is in Anti-Freeze Mode when the following
conditions are met:
1.

The control is in either Cool or Cool/Dry Mode.

2.

The indoor coil reaches 30°F and stays there for at least
five (5) minutes.

3.

The compressor has run for at least 90 seconds.

Fan Modes, Constant or Cycle, and the Delay On/Off Timer are
overridden during this operation.  Anti-freeze Protection is active
in all modes of operation and when the control is Off.

Room Freeze Protection

When room temperature falls below 41°F, the hydronic valve is
opened and the indoor fan operates on High Speed. The
compressor and outdoor fan are off and the display will show
“rF”.  The hydronic valve will close when the room temperature
rises back to 50°F. During room freeze conditions, the temperature
setting can be adjusted with the touch pad. Fan modes and
Sleep Operation are overridden during Room Freeze Protection.
Room Freeze Protection is active in all modes of operation and
when control is off.

Temperature Limiting

When the room temperature drops 5°F below set point, the
display will indicate “Lo”.  When the room temperature rises
5°F above set point, the display will indicate “hI”. Alarm
indications of 5°F above or below set point will be consistent
with the set up mode settings for minimum and maximum
temperatures.

Outdoor Air Low Ambient Lockout

If the outdoor air temperature is lower than 40°F, the compressor
and outdoor fan will stop and the display will indicate “LA”.
When outdoor air temperature is 50°F or more, the unit will
resume normal operation.

Table 1. – Failure Code and Condition

Thermistor Sensor

Condition

Error Code

< - 58°F or

Room

> 140°F or

E1

Open or Close

 < - 22°F for > 2s or

Indoor  Coil

> 176°F for > 2s or

E2

Open or Close

< - 22°F for > 2s or

 Outdoor Air

> 176°F for > 2s or

 E4

Open or Close

Outdoor Air Sensor Reading

To advance from Indoor Coil Sensor reading to Outdoor Air
Sensor reading, press the Mode button once. The control read-
out will show the outdoor air sensor temperature.

Thermistor Failure Code and Condition

The system treats a sensor open or short as extremely cold or
hot and reacts accordingly. The exception is the room air sensor,
in which case the system will turn off. When the fault is corrected
by replacement or repair, the respective error code will clear
from the display (see Table 1, page 8).

Compressor Random Restart

When power is interrupted, a random compressor restart delay
of 0 to 2 minutes is initiated. In the Cool Mode only, the
compressor will start operating only after the random delay
plus 2 minutes (minimum off time for thermostat, ie. 2 to 4
minutes).  Random delay is used only during system startup or
reset.

Содержание OM 813

Страница 1: ...OM 813 Group PTAC Part No 106878501 Date August 2005 Digital Control For Incremental Top mounted Hydronic Heat Comfort Conditioners Operation Maintenance Data...

Страница 2: ...ir Sensor Reading 7 Indoor Coil Sensor Reading 7 OutdoorAir Sensor Reading 8 Thermistor failure Code Condition 8 Compressor random restart 8 Unit Protective Logic 8 Compressor minimum run time 8 Compr...

Страница 3: ...itioner and a source of heat The Digital Control is operated with a Touch Pad Inputs and Outputs The Digital Control offers the following inputs Indoor Coil Sensor ICS IndoorAir Sensor IAS OutdoorAir...

Страница 4: ...SLEEP COOL COOL DRY FAN HEAT HIGH LOW CYCLE CONT LED 2 Digit Displays User Interface Touchpad and Display Low Voltage Communication Figure 2 Digital Controls on PDNS Unit Figure 3 Digital Control Touc...

Страница 5: ...LED will be on and the fan will turn on at a call for heat or cooling FanCycleOperation On a call for Heating or Cooling the indoor fan and the heating source or the compressor will be activated When...

Страница 6: ...rs for five 5 seconds Before the sleep time expires the setting can be adjusted above the number of hours passed by pressing the Sleep Button Pressing the On Off Button can terminate the Sleep Mode A...

Страница 7: ...met the set point will be reset to the user s setting and the unit will run in regular heat mode Hot start is not available with the Sleep feature The fan will operate per the Fan Mode and Speed setti...

Страница 8: ...ring room freeze conditions the temperature setting can be adjusted with the touch pad Fan modes and Sleep Operation are overridden during Room Freeze Protection Room Freeze Protection is active in al...

Отзывы: