Unit Operation

Last Setting Memory Backup

The digital control will start with the last settings used prior to
power down.  These settings are saved in a not-volatile memory
and the default mode is 

OFF

.

On/Off Triggering

The Control can be turned On or Off via the touch pad.  The
Control will show the temperature set point when turned on.
In the Fan Mode, the display is blank.

1.

On/Off triggering with the touch pad:

Control will turn ON or OFF when the On/Off button is
pressed on the touch pad control. Once turned on, the
control will start on the last mode used before it was turned
OFF.

2.

On/Off triggering with the SLEEP Feature:

The SLEEP Feature works in combination with the Timer
Setting. Sleep Timer setting is adjustable from 1 to 15
hours via the touch pad. The Timer counts down to  “0”
and turns the Control OFF if it was previously ON or vice
versa.

NOTE: 

Sleep Operation is overridden by the room freeze

protection.

OFF Mode

When the control is in the OFF MODE, relay outputs will be
disabled with the exception of the indoor fan (blower).  It will
stay on to meet the 

Hot Keep 

specification. Indicator LED’s

are all off. The normally open hydronic valve will be powered
closed in the OFF MODE.

Temperature Range

The maximum operating temperature range is selectable via
the Touch Pad and is 60°F to 85°F.

Indoor and Outdoor Fan Operation

The indoor fan can be set to operate on High or Low speed
with the Fan Speed Button on the touch pad. It can also be set
for Continuous or Cycled operation on the touch pad. When
set for Continuous, the “CONT” LED will be on and the fan
will run continuously. When set for Cycle, the “CYCLE” LED
will be on and the fan will turn on at a call for heat or cooling.

Fan Cycle Operation:

On a call for Heating or Cooling, the indoor fan and the
heating source or the compressor will be activated. When
the call is satisfied and the heating source or the
compressor is deactivated, the indoor fan will repeatedly
run for 2 minutes on and 30 minutes off,  until the next cut-
in cycle.

With a single (1) motor PTAC:

The outdoor motor speed is determined by the indoor fan
speed.

With a (2) two motor PTAC:

The compressor and the outdoor fan are controlled
simultaneously.

Damper Control

Damper control is user selectable via a jumper on the board for
one of two modes:

1)

Automatic

 when the jumper is 

present.  The control is

shipped with the jumper on.

In the 

Automatic Mode, 

 the damper will open when the indoor

fan is operating and close when it is not.

2)

In the 

Manual Mode 

the damper is opened and closed

manually.

Wireless Remote Control (Optional)

To add to existing Digital Control units, codes 55, 56
or 57, Front Panel Part No. 668104501 and Infrared
Control Kit Part No. 107029001 must be ordered.

The Remote Consists of 10 Push-buttons

Power:

Functions same as ON/OFF button on the touch pad.

Sleep:

Functions same as SLEEP button on the touch pad.

Mode Buttons

Heat, Cool, Cool/Dry, Fan:

Performs same function as the MODE button on the touch
pad, and allows user to select specific mode of operation
using only one button.

Temp Buttons 

 

+,  

 – :

Functions same as buttons on touch pad, allowing user
to change the setpoint.

Fan Speed Buttons (High & Low):

Performs same function as the FAN SPEED button on the
touch pad, allows user to select specific speed using only
one button.

Remote must be aimed in a line of sight of the window in upper
right corner on the front panel, at less than a 45

o

 angle from

center of the window.

The control board will beep when any button is pressed on
the remote control to confirm signal.

Содержание OM 813

Страница 1: ...OM 813 Group PTAC Part No 106878501 Date August 2005 Digital Control For Incremental Top mounted Hydronic Heat Comfort Conditioners Operation Maintenance Data...

Страница 2: ...ir Sensor Reading 7 Indoor Coil Sensor Reading 7 OutdoorAir Sensor Reading 8 Thermistor failure Code Condition 8 Compressor random restart 8 Unit Protective Logic 8 Compressor minimum run time 8 Compr...

Страница 3: ...itioner and a source of heat The Digital Control is operated with a Touch Pad Inputs and Outputs The Digital Control offers the following inputs Indoor Coil Sensor ICS IndoorAir Sensor IAS OutdoorAir...

Страница 4: ...SLEEP COOL COOL DRY FAN HEAT HIGH LOW CYCLE CONT LED 2 Digit Displays User Interface Touchpad and Display Low Voltage Communication Figure 2 Digital Controls on PDNS Unit Figure 3 Digital Control Touc...

Страница 5: ...LED will be on and the fan will turn on at a call for heat or cooling FanCycleOperation On a call for Heating or Cooling the indoor fan and the heating source or the compressor will be activated When...

Страница 6: ...rs for five 5 seconds Before the sleep time expires the setting can be adjusted above the number of hours passed by pressing the Sleep Button Pressing the On Off Button can terminate the Sleep Mode A...

Страница 7: ...met the set point will be reset to the user s setting and the unit will run in regular heat mode Hot start is not available with the Sleep feature The fan will operate per the Fan Mode and Speed setti...

Страница 8: ...ring room freeze conditions the temperature setting can be adjusted with the touch pad Fan modes and Sleep Operation are overridden during Room Freeze Protection Room Freeze Protection is active in al...

Отзывы: