Installation & Maintenance Data

IM 620-1

Group: 

Controls

Part Number: 

585524Y

Date: 

February 1998

© 1998 McQuay International

MicroTech®
Absorption Gateway for Absorption Chillers

MicroTech 
Absorption
Gateway

MicroTech

a0170

Содержание MicroTech MAG

Страница 1: ...tion Maintenance Data IM 620 1 Group Controls Part Number 585524Y Date February 1998 1998 McQuay International MicroTech Absorption Gateway for Absorption Chillers MicroTech Absorption Gateway MicroTe...

Страница 2: ...unications Trunk 23 Service Information 28 Wiring Diagrams 28 Test Procedures 30 Status LED Diagnostics 30 Troubleshooting Power Problems 31 Troubleshooting Analog Outputs 32 Troubleshooting Output Bo...

Страница 3: ...LED Indication 9 Table 4 Amber Status LED Indication 9 Table 5 Program Codes 11 Table 6 Accessory Installation Manuals 11 Table 7 PC Specification 13 Table 8 MAG Panel Environmental Specifications 14...

Страница 4: ...stop signals Cooling water inlet outlet temperature Heating cooling simultaneous and abnormality indicators Condensation temperature SVRP and SVRU valves Remote reset setting Cooling main heating mai...

Страница 5: ...al device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment Operat...

Страница 6: ...his type of configuration is called the Network Connect MAG The base panel is equipped with eight AC power rated relays plus the necessary hardware to support the addition of accessories listed in Tab...

Страница 7: ...rocessor Control Board The Microprocessor Control Board MCB is shown in Figure 2 It contains a microprocessor that is preprogrammed with the software required to monitor the data from the absorption c...

Страница 8: ...ormation on the Analog Output Expansion Module Power In Connector The MCB receives 18 Vac center tapped power through transformer T2 and the Power In connector This power drives all logic and communic...

Страница 9: ...On 1 second Off 1 second Communications exists between the MAG and the absorption chiller On 2 10 second Off 2 10 second Communications does not exist between the MAG and the absorption chiller Hex S...

Страница 10: ...using the RS 485 interface standard A twisted shielded pair cable should be connected to port B via terminals B B and GND on terminal block T11 The communications rate is 9600 bps For more informatio...

Страница 11: ...VENDOR MDL 280 50 DATE CODE 10 94 MCB part number Program code Ident Table 5 Program Codes MAG Type Program Code Direct Connect 950468 010 Network Connect 950469 010 Accessories The accessories of th...

Страница 12: ...C AC DC G Power LEDs 26 pin Expansion Bus Connector 26 pin Expansion Bus Connector Power Connector a0166 MicroTech Monitoring and Networking Options PC Monitoring A PC personal computer equipped with...

Страница 13: ...quired because the MAG can connect directly to the BAS interface If two or more MAG Panels are included the MicroTech Open Protocol Master OPM Panel is required For further information contact your Mc...

Страница 14: ...screw By adjusting this screw you can prevent the panel door from swinging open or closed unexpectedly Table 8 MAG Panel Environmental Specifications Panel State Temperature Relative Humidity Operatin...

Страница 15: ...r to Figures 7 and 8 Power wiring must be sized to carry at least 5 amps To gain access to the high voltage section remove the deadfront barrier It is attached to the panel with five 5 16 inch hex scr...

Страница 16: ...nd MAG 2 It is highly recommended that the installing contractor keep track of the physical order of the controllers on the daisy chained trunk This facilitates troubleshooting any network communicati...

Страница 17: ...ble Communications Interface Cable Hot Neutral Hot Neutral Legend Field Wiring Terminal Cable Shielded Twisted and Jacketed Pair with Drain Wire Factory Wiring Field Wiring Line Input Line Input WHT B...

Страница 18: ...ions Interface Cable Hot Neutral Legend Field Wiring Terminal Cable Shielded Twisted and Jacketed Pair with Drain Wire Factory Wiring Field Wiring Line Input a0168 PC Connection The PC is connected to...

Страница 19: ...connection between the PC and a controller is 50 feet Cable Specification for Direct PC Connection A properly terminated twisted shielded pair cable is required to directly connect a PC to a MicroTech...

Страница 20: ...damage The analog output signals voltage mode must be isolated from any ground other than the MicroTech controller chassis ground If it is not ground loop currents could occur which could damage the M...

Страница 21: ...24V GND Ribbon Cable Expansion Bus 13 VDC GND DC GND MCB 24V AC 13V DC 13V DC AOX 4 Board Analog Output Device Current Mode 24 VAC Power Analog Output Device Voltage Mode 24 VAC Power To MicroTech Co...

Страница 22: ...For more on hex switch settings see Microprocessor Control Board in the Component Data section of this manual The Network Connect MAG Network The Network Connect MAG Network includes a Network Master...

Страница 23: ...ock or directly on the port B connector of the level 1 controller With one lead on the control panel chassis ground check for voltage at the and ground terminals There should be no AC or DC voltage se...

Страница 24: ...PORT B FUSE BUSSMAN MCR 1 4 FUSE 1 3 2 4 5 3 1 2 4 6 a0114 Network MAG Controller Connection In order for the NMP OPM or other level 1 controller in a network to connect and communicate with level 2...

Страница 25: ...on trunk voltages at the field wiring terminals if any or directly on the connector The trunk must not be connected to the controller when you do this If no voltage or improper voltages are found chec...

Страница 26: ...to the MAG Panel or connection to port A if an AMP connector was used Check to see if the MAG Panel and the absorption chiller unit controller are energized Direct Connect MAG Controller Connection T...

Страница 27: ...ber LED on the MAG controller stays on for 1 second and goes off for 1 second if communications exists see Table 4 Amber Status LED Indication in the Component Data section of this manual If communica...

Страница 28: ...shown in Figure 14 Figure 14 Network Connect MAG Schematic Legend Component Designation Description CB1 Circuit Breaker MCB Microprocessor Control Board OB Output Board AOX BRD Auxiliary Output Expan...

Страница 29: ...s reproduced here for your convenience The legend is shown in Figure 16 Figure 16 Direct Connect MAG Schematic Legend Component Designation Description CB1 Circuit Breaker MCB Microprocessor Control B...

Страница 30: ...described in the Component Data section of this manual see Tables 3 and 4 there is a problem with the MCB Following are troubleshooting procedures for the various symptoms Red LED Remains On If the r...

Страница 31: ...ce them Go to step 4 b If the fuses are intact the MCB is defective 4 Reconnect the Power In plug and disconnect all other connectors on the MCB Cycle power to the controller close and then open CB1 a...

Страница 32: ...o step 13 b If the resistance does not rise above 5000 ohms the MCB is defective 12 One at a time reconnect the modem and each AOX 4 board as applicable Each time a component is reconnected measure th...

Страница 33: ...tput Boards Each output on the output board consists of a solid state relay an LED 5 amp fuse and an MOV metal oxide varistor Normally when the MCB commands an output to energize the solid state relay...

Страница 34: ...Restore power by pressing CB1 to the ON position The LED should light regardless of the controller s command a If the output LED illuminates it is likely that the MCB is defective b If the output LED...

Страница 35: ...components Output Energized LED not Lit If the LED of a suspect output is not lit but the load connected to it is energized either the solid state relay or the MOV is bad The solid state relay contac...

Страница 36: ...re 20 In this circuit a solid state relay behaves like an electromechanical relay If the relay is energized the relay output is hot If the relay is de energized voltage cannot be measured at the relay...

Страница 37: ...s program Therefore it is possible to download the proper controller software to a replacement MCB at the building site if a PC equipped with that job s Monitor software is available In addition if t...

Страница 38: ...ibbon Cable Assembly 3 AOX 4 to AOX 4 654997B 06 CIC Communications Interface Cable 50 733173B 01 AOX 4 Analog Output Expansion Module 005532370 1 SSR Solid State Relay Kit 005532390 1 Solid State Rel...

Страница 39: ...IM620 1 39...

Страница 40: ...40 IM620 1...

Страница 41: ...13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330...