Page 6 of 32
OM 750
The UVC archives each change to the LUI Fan and Mode buttons.
When the On/Stop button is used to bring the unit out of Off mode,
the UVC will implement the last active fan and unit modes.
Each time the UVC power is cycled, the UVC will be in auto fan and
auto unit modes when power is returned.
FAN BUTTON
The Fan button is used to toggle through each of the Fan speeds (Fan
Speed Command Input): Auto, Low, Medium, and High.
MODE BUTTON
The Mode button is used to toggle through the LUI accessible unit
modes (Heat/Cool Mode Input): Auto, Heat, Cool, and Fan Only.
ARROW BUTTONS
The arrow buttons are used to scroll between and adjust parameters.
FUNC BUTTON
The Func button is used to view the actual space temperature. The Func
button is also used as an ENTER key to confirm selection and changes
to user adjustable or viewable parameters.
VIEWING ACTUAL TEMPERATURE (IAT)
The LUI displays the setpoint temperature. The LUI can be used to
view the actual room temperature. See Figure 2.
Two Digit
What is Restricted?
Password
Display
Level 0
Default level (access all)
10
Level 1
Do not allow user to adjust setpoint
21
Level 2
Do not allow user to adjust setpoint nor
make Mode button changes
32
Level 3
Do not allow user to adjust setpoint nor
make Mode and Fan button changes
43
Table 5. LUI Security Levels
Figure 4. Changing LUI Security Levels
WHY CAN’T I USE THE MODE OR FAN BUTTON,
OR ADJUST SETPOINT OFFSET?
Most likely this is due to the security feature being used. If the security
feature is set higher than level 0, then some LUI functionality is locked
out. To ensure this is not the problem, enter the level 0 password then
try again to use the LUI.
When using the +/- 3
°
F (+/- 1.7
°
C) remote wall sensor, any setpoint
offset adjustment made at the LUI will cause the UVC to override
and ignore the remote wall sensor setpoint adjustment knob. To
again use the remote wall sensor setpoint adjustment knob, you
must clear the LUI setpoint offset adjustment by cycling UVC
power.
Figure 3. Adjusting the Setpoint Offset
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
LOCAL USER INTERFACE (LUI) SECURITY LEVELS
The LUI provides a 4-level password security feature which can be
used by owners to restrict LUI access.
The setpoint offset is cleared after every power cycle. When
changing the setpoint offset after a power cycle, or for the first time,
this cleared value will be shown as the highest allowed value (5
°
F
/ 3
°
C) but will not be
an actual offset value.
Figure 2. Viewing Actual Temperature (IAT)
When the actual space temperature (Effective Space Temp Output)
equals the effective setpoint (Effective Setpoint Output) you will
see no change to the LUI display when you view space temperature.
NOTICE
When using the 55
O
F to 85
O
F remote wall sensor, the UVC will
ignore any LUI setpoint offset adjustments.
USING THE LUI TO ADJUST SETPOINT OFFSET
The LUI can be used by room occupants to easily make +/- 5
O
F (+/-
3
O
C) adjustments to the effective temperature setpoint. See the Space
Temperature Setpoints section to learn more about temperature setpoints.