OM 200MICRO

Menu 23, Lead Lag Setup

Item

Screen

Line

Display

Field

Range

Extended Name

Slave Address=01.00

1

00-09

Slave Unit Network Address

NoUnload

1

Start-Up=NotUnld

2

Unload

Unload Lead During Lag Start

Auto

Slave Lead

LL Mode=auto

1

Master Lead

Lead Lag Control Mode

2

Enable Lag=95%

2

0-100%

Lag Start Threshold

N/A
Sun

Mon

Tue

Wed

Thu

Fri

LL SwOver=N/A

1

Sat

Scheduled Lead Unit Switch

Over Day

1

3

Disable Lag=40%

2

1-100%

Lag Stop Threshold

1

Delay timer=5Min

1

1-60Min

Lag Unit time Delay

2

2

Lag-Standby=No

1

No-Yes

Lag Unit Standby Operation

Slave Address=

 This value 

(01.01)

 is the network address of the slave MicroTech.  This value is

determined by the Hex switches on the MicroTech.  The slave MicroTech will always be addressed as
01.  The master unit can be any hex switch setting greater that 00 but less that FF.

(00 & FF are

reserved numbers and cannot be used.)

  The wrong value will disconnect the communications

between the chillers and they would revert back to local control.  This could cause damage to a dual
chiller unit.

Start-Up=

 This value directs the lead chiller to unload or not to unload.  A dual chiller must unload the

lead chiller when starting the lag chiller.  This is optional in a two 

(2)

 single chiller configuration.

LL Mode=

 The value selected will direct the network to start the chillers in a fixed sequence.

Auto

—The chiller with the least run time will start as the lead unit.  The chiller with the most run

time will turn off first when only one chiller is required to meet load conditions.

Slave Lead

—The slave chiller will start first each time and the master chiller will shutdown when

only one chiller is needed to meet load requirements.

Master Lead

—The master chiller will start first each time and the slave chiller will shutdown when

only one chiller is needed to meet load requirements.

Enable Lag=

 This is the amp value 

(percentage)

 when the lag chiller will be started.  This value must

be maintained for a predetermine amount of time to indicate a true load.

LL Swover=

 Day of week for lead lag switch to occur.  This is optional.

Disable Lag=

 This is the amp value 

(percentage)

 when the lag chiller will be shutdown.  This value

must be maintained for a predetermine amount of time to indicate a true load.

Delay Timer=

 This value is used to delay the start of the lag chiller if the lag chiller is used in a stand

by mode only.  Stand by means the chiller is only started when the lead chiller fails.

Lag-Standby=

 This value sets the lag chiller as a standby chiller and will only start if the lead chiller

fails.

Cycle power to both MicroTech controllers.  This is necessary for the hex switch settings and com
port settings initialization.

Go to menu 11.  Set 

Auto:Network

 in this menu for both the slave and master MicroTech.  Set the

toggle switch on the face of the MicroTech panel (master and slave units) to the auto position.  The
chillers will now start when load conditions require cooling.

Содержание MicroTech 200 Series

Страница 1: ...Operating Manual OM 200MICRO Group Chiller Part Number 585515Y Effective April 2000 Supersedes OM125 1999 McQuay International 200 Series MicroTech Control Panel For Centrifugal Chillers...

Страница 2: ...ech Status Menus 18 Control Menu Description 24 Alarm Menus Description 38 Master Slave Setup 41 Alarms 43 McQuay and MicroTech are registered trademarks of McQuay International 1998 McQuay Internatio...

Страница 3: ...rge any static electrical charge by touching the bare metal inside the control panel before performing any service work Never unplug any cables circuit board terminal blocks or power plugs while power...

Страница 4: ...ons If a fault condition develops the controller will shut the system down and activate an alarm output Important operating conditions at the time an alarm condition occurs are retained in the control...

Страница 5: ...ondition occurred In addition the operating conditions that existed just prior to shutdown can be recalled to aid in isolating the cause of the problem Eight previous faults and related operating cond...

Страница 6: ...tus LED s located on the model 280 controller which will indicate the microprocessor s operating condition When power is first applied to the control panel the red reset LED will illuminate for approx...

Страница 7: ...will be appropriate for most common installations Step through all of the unit s setpoints by using the keypad display and adjust them as required to meet the specific job requirements Any faults app...

Страница 8: ...er Water Pump 1 Off On 18 Condenser Water Pump 2 Off On 19 Spare 20 Spare 21 Spare 22 Spare 23 Spare Analog Digital Input Board ADI The ADI Board provides low voltage power for the temperature and pre...

Страница 9: ...OM 200MICRO 9 of 4 20 mA Temperature and pressure readings have a resolution of 0 1 F and 0 1 psi respectively Flow readings and remote reset signals are resolved to 1...

Страница 10: ...Vent Pressure 0 165 psig 0 1137 6 kPa 16 S16 Evaporator Refrigerant Pressure 0 165 psig 0 1137 6 kPa 17 S17 Condenser Refrigerant Pressure 0 165 psig 0 1137 6 kPa 18 S18 Oil Feed Gauge Pressure 0 165...

Страница 11: ...analog signal that is proportional to compressor motor current Figure 7 AOX Board Analog Outputs Optional The analog outputs available at the AOX board provide a variable voltage used to control field...

Страница 12: ...ardistor board monitors the motor winding temperature through the embedded Guardistor sensors If the motor temperature rises to an unsafe level the board will signal the M280 controller and the chille...

Страница 13: ...can be accessed through the keypad by following the tree like structure of menus and menu items The keypad keys are divided into four groups with four or more keys in each to ease navigation through t...

Страница 14: ...11 Control Mode which is the first menu of the CONTROL category Alarm Key Menus and menu items in this category provide information regarding current and previous fault conditions along with the oper...

Страница 15: ...he display pressing NEXT causes and end of items message to appear in the display Previous Item Pressing PREV shifts the display to the previous group of items within a menu Note When the first item i...

Страница 16: ...ries After entering the correct password the controller will allow a 5 minute time period during which the operator may make any necessary setpoint adjustments Any keypad activity will reset the timer...

Страница 17: ...change the numeric value or select the next option When the correct value or option is flashing press the ENTER key to store it into memory The flashing will stop and the time and date is returned to...

Страница 18: ...Field Range Extended Name AllSystemsOff Off Alarm Off Ambient Lockout Off Front Panel Sw Off Remote Contacts Off Remote Comm Off Time Schedule Off Manual Setpoint Off System Comm Start Requested Waiti...

Страница 19: ...Lvg Ht Rcvy xx x F 1 Heat Recv Lvg Water Temp 2 Cond Flow xxxxgpm 2 Averaged Cond Water Flow 2 3 Delta T xx x F 1 Heat Rcvy Delta Temp Press the NEXT MENU key and Menu 3 Refrig Temps Press will be dis...

Страница 20: ...g value if limiting is being enforced by the control software Pressing the switch key will toggle between this menu and Menu 13 MotorAmp Set Points This allows the operator to compare actual operating...

Страница 21: ...ower valve is controlled by the chiller Screen 2 line 1 field 1 indicates the outdoor air temperature This is optional and will be valid if an out door thermistor is installed Pressing the switch key...

Страница 22: ...perator to compare actual operating conditions versus set points Menu 23 is only available on the master chiller when a network exists between two 200 Series MicroTech chillers A network can be establ...

Страница 23: ...Temp 2 Evap Flow xx x F 2 Recorded Evap Water Flow Feed Press xx xpsi 1 Recorded Oil Feed Pressure 4 3 Cond Flow xxxxpgm 1 Recorded Cond Water Flow 1 Wk Ending 1 Date of Previous Log Peak xxx 1 Record...

Страница 24: ...al Off Selected Unit Operation Manual Off This mode causes the chiller to stop If the unit is operating it will go through a controlled shutdown and remain off If the unit is off it will remain off Au...

Страница 25: ...ater temperature set point Local Spt This is the actual chilled water leaving temperature for the chiller to maintain if there is not a network Local spt is active depending upon which set point sourc...

Страница 26: ...elected as a reset option If this set point is set to high it can cause the compressor to surge and damage the chiller Return Spt This value will control the MicroTech if the chw reset option was set...

Страница 27: ...This value can be used to limit the operational amperage should abnormal conditions exist Soft Load This value activates the soft load ramp up option if set to on Upon chiller start soft load takes ov...

Страница 28: ...for each day of the week should be entered The default value 00 00 23 59 allows the chiller to operate continuously Hol The time entered at this menu will control the chiller nun time for the holiday...

Страница 29: ...t to Start Delay Timer 2 Evap Recirc 15Sec 1 15 Sec 5 Min Chilled Water Recirculation Timer 1 3 Stop Start 3Min 1 3 20 Min Stop to Start Delay Timer Start Start This value determines the minimum time...

Страница 30: ...econd pump number 2 will not be started if number 1 fails Pmp 2 Only The pump designated as number 2 will be started and the second pump number 1 will not be started if number 2 fails Auto Lead The Mi...

Страница 31: ...Stageup Time This value will delay the MicroTech from starting the staging control This can be used to provide specific system control requirements Stagedn Time This value will delay the MicroTech fr...

Страница 32: ...egration Time Max Change 4 1 1 20 Max Allowable Valve Pos Change 2 3 PA Time 15Min 2 1 0 60 Min Proj Ahead Calculation Window Min Start Pos 0 1 0 100 Min Valve Position at Startup 1 Max Start Position...

Страница 33: ...an Changing these values could cause compressor damage The menu can be monitored and set points compared to actual operating conditions Menu 22 Alarm Set Points Item Screen Line Display Field Range Ex...

Страница 34: ...ad unit The chiller with the most run time will turn off first when only one chiller is required to meet load conditions Slave Lead The slave chiller will start first each time and the master chiller...

Страница 35: ...d protected and requires the service password Menu 25 Service Testing Item Screen Line Display Field Range Extended Name Output 0 Off 1 Off On Manual Output Control 1 Output 3 Off 2 Off On Manual Outp...

Страница 36: ...pe WSC063 2 WSC126 Chiller Model Number L1 TTY Master L1 TTY TTY L2 Master Slave L2 TTY Slave Config L2 TTY Slave 1 L3 TTY Slave Unit Controller Configuration Chiller 2 Chiller Only 2 Templifier Chill...

Страница 37: ...orator flow sensor The MicroTech scales the value linearly between 4 and 20 milliamp input or 0 to 10VDC input Ambient Lockout This value determines according to the outside air temperature the point...

Страница 38: ...ooling at Alarm Dsch Suprht xxx x F 1 Discharge Superheat at Alarm 2 Sump Temp xxx x F 2 Oil Sump Temp at Alarm Suct Suprhtxxx x F 1 Suction Superheat at Alarm 3 3 Feed Tempxxx x F 2 Oil Feed Temp at...

Страница 39: ...depending on this setting Problems This value will define how problems will report open close or how fast slow the reporting will occur Only one can be selected If fast slow is selected the alarm cont...

Страница 40: ...40 OM 200MICRO Menu 37 Message Board Item Screen Line Display Field Range Extended Name 1 1 No Message A Message can be Posted via a Connected Computer...

Страница 41: ...Low Temperature No 2 No Yes Ice Operation Master Master Slave Slave 1 Slave Network Configuration 1 Evap Gpm Sensor No 2 Yes No Evaporator Flow Transmitter None Local OAT Sensor None 1 Remote Locatio...

Страница 42: ...the least run time will start as the lead unit The chiller with the most run time will turn off first when only one chiller is required to meet load conditions Slave Lead The slave chiller will start...

Страница 43: ...ride normal chiller operation in order to keep the unit on line PROBLEM CONDITION DISPLAY ACTION CLEAR Entering Evaporator Water Temperature Sensor Fail Problem Sensor is shorted or open and Leaving W...

Страница 44: ...pPumpsOff and Evaporator Water Flow switch digital input in No Flow position for more then 3 seconds adjustable and Evaporator pump 1 is present and Evaporator pump 1 has not yet failed Evap Pump 2 Fa...

Страница 45: ...ch Hi Pres Switch High Motor Temperature Motor High Temperature digital input in Alarm position High Motor Temp High Suction Superheat Suction Superheat temperature Set Point 50 F Hi Suction Superht N...

Страница 46: ...Post Office Box 2510 Staunton Virginia 24402 2510 800 432 1342 www mcquay com...

Отзывы: