Master/Slave Setup
Chiller setup for dual unit
(WDC)
or two single
(WSC)
units with master/slave and or lead/lag control.
There are several menus that require modification to accomplish this setup. The first menu that has to
be modified is menu 26. One MicroTech controller has to be designated as the Master unit. The other
unit will be the Slave unit.
Set the toggle switch on the face of the MicroTech panel
(master and slave units)
to the stop
position. Go to menu 26 on the Master unit. Only the values that require changes will be discussed.
Menu 26, Unit Setup
Item
Screen
Line
Display
Field
Range
Extended Name
IDENT=CFG3E02AC
1
Software Version
WSC048
WSC050
WSC063
WSC079
WSC087
WSC100
1
Unit Type=WSC063
2
WSC126
Chiller Model Number
L1-TTY-Master
L1-TTY-TTY
L2-Master-Slave
L2-TTY-Slave
Config=L2 TTY-Slave
1
L3-TTY-Slave
Unit Controller Configuration
Chiller
2
Chiller Only
2
Templifier
Chiller Control Options
1200
2400
4800
Port A Baud =9600
1
9600
Port A Comm Rate
1
3
Low Temperature=No
2
No-Yes
Ice Operation
Master
Master/Slave=Slave
1
Slave
Network Configuration
1
Evap Gpm Sensor=No
2
Yes-No
Evaporator Flow Transmitter
None
Local
OAT Sensor=None
1
Remote
Location of OAT
2
Evap Full Gpm=6500
2
0-65535
Maximum Flow Rate
Ambient Lockout=No
1
Yes-No
Lockout on OAT
2
3
Cond Gpm Sensor=No
2
Yes-No
Condenser Flow Transmitter
Cond Full Gpm=6500
1
0-65535
Maximum Flow Rate
Valve
1
Oil Cooler=Solenoid
2
Solenoid
Oil Cooler Control Method
Refrig Leak Sen=No
1
Yes-No
Refrigerant Leak Sensor Signal
2
Full Load Amp=300
2
0-65535
Chiller RLA
3
3
Ht Recovery Sen=No
1
Yes-No
Heat Recovery Temp Sensor
Config=
This defines the communication link, com port type and MicroTech controller level. The
master unit must be set to L2-Master-Slave. This setting makes menu 23 available only on the master
unit.
(The slave unit must be set to L3TTY-Slave).
Master/Slave=
Set this to 'Master' on the Master unit.
(Set this value to 'Slave' on the slave unit).
This completes the setup of menu 26 on both the master and slave units.
Go to menu 23 on the master unit. This menu is only available on the master unit. The network
communications depends on the values selected in this menu.