background image

                                                                                                                                                                                                                       

                                                                                                                                                                                                                     
                                                                                                                                                                    ©2005 McQuay International 

(machine dimension)820mm

(m

a

c

h

in

e

 d

im

e

n

s

io

n

)

8

2

0

m

m

790.0

(drill hole in ceiling) 890.0mm

6

2

0

.4

(d

ri

ll 

h

o

le

 i

n

 c

e

ili

n

g

)8

9

0

.0

m

m

indoor unit

ceiling

3

5

m

m

nut

washer

steeve

nut

washer

Right

flow

 

 

flow

 

 

Ceiling

Ceiling

Wrong

Cool air

 

 

Indoor unit

Cool air

 

 

Indoor

Pipe clamp

Right

Wrong

c)  The paper temperate shall be measure dimension before usage; 

d)  Ensure the paper temperate is the same dimension as hole dimension in the ceiling; 

e)  Before the completion of ceiling decoration, leave the paper temperate with the indoor unit; 

f)  Ensure the distance between the hang pole is 620.4mm

×

790.0mm

 

g)  To ensure use screw to fix the indoor units tightly; 

h)  To  adjust  distance  between  the  bottom  panel  and  ceiling  is  less  than 

35.0mm

 

i)  To check installation horizontally, and indoor units are fixed tightly without 

dropping off and vibration;             

j)  To cut the same shape of paper temperate in ceiling; 

k)    Drainage shall be smooth piping and slope installed; 

l)    To avoid drainage piping bent , shall be straight; 

m)   To install the drainage piping, do not exert too strong force; 

n)    It shall be installed diameter 20 flexible host to connect   

        outside part of drainage piping, as shown as Figure; 

o)    Drainage piping shall be covered with insulation material   

( thickness: 8.0mm polyphone plastic material ) , to avoid 

  the dropping off of the condensing water; 

p)    To connect the drainage host and flexible host; 

q)    To fill in some water to piping to test the leakage; 

r) 

  After  testing,  to  connect  the  other  end  of  flexible  host  to 

indoor units;

 

Note

  In this type of indoor units, a water pump is used to help to drain 

the   

condensing water, to install unit horizontally to avoid leakage of water and 

condensing water dropping off;   

Note

This series product need connect a MEX box out of the machine, 

please refer to page 7 of this manual; 

   

Installation of front Panel 

● 

To install the front panel , please check the piping connecting direction first; 

 

Follow the direction of the piping connection direction;

 

  To remove the paper temperate; 

  To remove the air filter and grill of front panel; 

  To use 4 screw bolt to fix the frame of front panel tightly; 

● 

To connect the indicator light with indoor unit and fan swing motor with indoor units respectively; 

Note

  Ensure the frame of the front panel is fixed tightly to avoid the leakage of cool and dropping of condensing water; 

 

 

 

 

 

 

 

There are also the hole for fresh air and exhaust air for connection with outside in indoor unit, but as for air piping,    and only be the other 

side of refrigerant piping connector; 

 

 

 

drain pipe

drain & leakage test

fill water

flexible pipe

Содержание MDS080B

Страница 1: ...Digital Variable Multi Air Conditioner MDS080B R MDS320B R Installation Manual...

Страница 2: ...ial Thickness 29 McQuay is a registered trademark of McQuay International All rights reserved throughout the world 1994 McQuay International McQuay reserve the right to make changes in design and cons...

Страница 3: ...leakage of refrigerant please open the window and door for good ventilation to avoid any fire because of the poisonous gas may occurred If the indoor unit is installed in a confined limited space it s...

Страница 4: ...er and slave unit of MDS320B R other combined units we recommend use the series connection You can refer 8 3 electrical connection which show how to connect the cable MCC Series Indoor Units Mode MCC0...

Страница 5: ...pport the units and prevent vibration To avoid to install units at dirty and salty place To avoid to install units at easy burning gas leakage place Do not install units which is subject to impact by...

Страница 6: ...one big place refer to the followings Space for single unit 1 Basic space required 2 When inlet air enters from right and left sides of unit 3 When there is an obstruction above the unit 4 When unit i...

Страница 7: ...shall be strong enough 5 Installation of the combined outdoor units Suitable for Model of MDS260 320 Two outdoor units can be grouped as one outdoor unit to couple with multi indoor units Grouped out...

Страница 8: ...tall around the Hi frequency equipment place 6 2 Installation of Indoor Unit 6 2 1 Installation of MCC T series indoor units This type indoor units shall couple with duct working of air supply and air...

Страница 9: ...ce for installation b Ensure no barrier and good ventilation is a must Please refer to the below figure 0 5m 1 0m H 0 5m 0 5m 0 3m obstacle floor indoor unit girder indoor unit To refer to the above i...

Страница 10: ...e o Drainage piping shall be covered with insulation material thickness 8 0mm polyphone plastic material to avoid the dropping off of the condensing water p To connect the drainage host and flexible h...

Страница 11: ...terial is the same length of the air outlet To extend the insulation material to cover the gas more than 10mm but not touch the air grill there is no need to extend insulation material more than 10 mm...

Страница 12: ...fter installation to run the leakage test is necessary d Only in cooling mode there is a need to detect the status of drainage 6 2 4 Installation of MCM T series indoor unit To check the accessories a...

Страница 13: ...n in the figure Do not place the indoor unit where there could be direct sunlight shining on it Also the location must be suitable for piping and drainage and be away from doors or windows Mounting in...

Страница 14: ...s following When the detected level is higher then 18mm the pump start run When the detected level is higher then 21mm the pump send an alarm signal to the controller of the indoor unit and the pump c...

Страница 15: ...not use the 2nd refrigerant piping 4 Do not use any detergent to clean the refrigerant piping 5 To seal the outlet of the copper tube to avoid any dust or dirt or water to enter inside 6 When install...

Страница 16: ...3 Between the gas distributors 16kW 9 52 16kW C 22 5kW 12 7 22 5kW C 50kW 12 7 15 88 Liquid Capacity 50kW C 85kW 19 05 9kW 15 88 9kW C 16kW 19 05 16kW C 22 5kW 22 23 22 5kW C 36kW 28 6 46kW C 50kW 34...

Страница 17: ...installation Horizontal and vertical type Distributor installation only available for horizontal 80 550 211 510 C D E I A B 75 F H G 148 19 3 B 250 E D C A 12 9 16 1 80 9 7 80 6 5 80 19 3 19 05 16 1...

Страница 18: ...alent length for trap For bifurcation the equivalent length is 0 5m branch piping 1 0m elbow and oil trap s equivalent as following table Equivalent length Equivalent length DIA Elbow m Oil trap m DIA...

Страница 19: ...rt entry To change the hallow seal pad To fix the flange connector and hallow sealed pad and fixed ball valve of gas side with screw bolt 2 Liquid side ball valve connecting to expand the copper tube...

Страница 20: ...es should be connected with master unit until it is earthed Each circuit shall has its own independent fuse or air switch Outdoor units use 3 phase power supply cable indoor units use 1 phase power su...

Страница 21: ...port A B Control box PCB A B JP 1 of last unit on main bus should be on Indoor unit i B Communication cable Control box A PCB JP1 A B A B A B com2 Connection port Connection port com1 com2 com2 com1...

Страница 22: ...td o o r u n it C o n tro l b o x M a in P C B C o n n e c tio n p o rt S c re e n la y e r B A A B P C B C o n tro l b o x In d o o r u n it 1 In d o o r u n it 2 C o m m u n ic a tio n c a b le C o...

Страница 23: ...1 0 1 3 0 0 0 0 1 0 15 0 0 1 1 1 0 27 0 1 1 0 1 0 39 1 0 0 1 1 0 4 0 0 0 0 1 1 16 0 0 1 1 1 1 28 0 1 1 0 1 1 40 1 0 0 1 1 1 5 0 0 0 1 0 0 17 0 1 0 0 0 0 29 0 1 1 1 0 0 41 1 0 1 0 0 0 6 0 0 0 1 0 1 18...

Страница 24: ...ntroller address code setting mode press the key or when the displayed value is then user can press the key ON OFF to cancel the address code set by the wired controller After cancel the wired control...

Страница 25: ...o be charged R22 weight is 16 2kg 10 Testing Operation Before trial running to ensure and check the safety and record the concerned data after units is in stable operation 10 1 Checking list before tr...

Страница 26: ...MDS300B R MDS320B R Master unit Slave unit MDS120B R M MDS150B R S MDS150B R M MDS130B R S MDS150B R M MDS150B R S MDS160B R M MDS160B R S D 990 10 1290 1290 10 1290 1290 10 1290 1290 10 1290 MCC008...

Страница 27: ...025 030 040 050 060T Unit mm MODEL A B C D E F G H I J K L M MCK010 015 018 020T 820 875 548 820 278 250 28 930 930 642 622 555 555 MCK025 030 040 050 060T 820 875 548 820 363 335 28 930 930 642 622 5...

Страница 28: ...J K L M N MCM020T 1174 75 1082 68 58 156 1214 57 670 216 319 879 517 MCM030T 1174 75 1082 68 93 156 1214 57 670 216 319 879 517 MCM050T 1674 75 1582 68 93 156 1714 57 670 216 319 1379 517 189 4 13 15...

Страница 29: ...0 128 132 MWM020 025T Unit mm MODEL A B C D E F G H I J K L M N O MWM020 025T 1060 310 220 912 294 99 51 8 48 43 354 403 160 138 160 Electrical heater Unit mm MODEL A B C D HDP1 2T08 15 HDP2 4T08 15 7...

Страница 30: ...8 HWT35 50 1372 1314 1342 1438 HWT60 1632 1574 1602 1688 Indoor units EXV BOX MODEL MEX 15 2SAP C D MEX 18 2SAP D MEX 18 3SAP C D MEX 24 3SAP C MEX 30 3SAP C OD I mm inch 6 35 1 4 9 52 3 8 Condensing...

Страница 31: ...is based on the PRC Standard Specification for Drawn Tube of Copper and Copper Alloys GB T1527 1997 TP2M and TP2Y2 are the marks of the material brand and state Using this table as reference choose th...

Отзывы: