B) For MMC – C/CR series
Model
MMC 075C/CR
MMC 100C
MMC 150C
A (mm)
1,200
1,200
1,200
B (mm)
500
500
500
C (mm)
300
300
300
MMC 075C/CR / 100C
MMC 150C
Vacuuming And Charging
Vacuuming is necessary to eliminate all moisture and air from the system. The Series II Condensing Unit is
provided with flare valve fittings and charging nipples.
Vacuuming
After the system pipings are properly connected, connect the
flexible hoses to the correct charging nipples as shown in the
diagrams. Ensure that flexible hose from charging nipples are
connected to vacuum pump via standard servicing valves and
pressure gauges (gauge manifold). Vacuum the air conditioner
system to at least 500 microns Hg.
Charging
Before charging, the vacuum must be held at 500 microns Hg
for at least 15 minutes, then break vacuum by charging R-22
refrigerant. Operate the unit for 15 minutes and ensure that
refrigerant charges is of correct quantity by monitoring running
current and suction and liquid line pressures. Suction and
discharge pipe pressures should be in the region of 75 psig
and 275 psig generally.
After ensuring the system is correctly charged, remove flexible
hose from charging nipples and replace caps.
Содержание MDB075B
Страница 1: ...MDB 2004 Ducted Split Systems Models MDB 075 750B MDB 125 150C MDB 075 500BR MDB 125CR...
Страница 38: ...37 Blower Performance Curves MDB 075B BLOWER PERFORMANCE CURVE...
Страница 39: ...38 MDB 100B BLOWER PERFORMANCE CURVE...
Страница 40: ...39 MDB 125B BLOWER PERFORMANCE CURVE...
Страница 41: ...40 MDB 125C BLOWER PERFORMANCE CURVE...
Страница 42: ...41 MDB 150B BLOWER PERFORMANCE CURVE...
Страница 43: ...42 MDB 150C BLOWER PERFORMANCE CURVE...
Страница 44: ...43 MDB 200B BLOWER PERFORMANCE CURVE...
Страница 45: ...44 MDB 250B BLOWER PERFORMANCE CURVE...
Страница 46: ...45 MDB 300B BLOWER PERFORMANCE CURVE L s...
Страница 47: ...46 MDB 350B BLOWER PERFORMANCE CURVE...
Страница 48: ...47 MDB 400B BLOWER PERFORMANCE CURVE...
Страница 49: ...48 MDB 450B BLOWER PERFORMANCE CURVE...
Страница 50: ...49 MDB 500B BLOWER PERFORMANCE CURVE...
Страница 51: ...50 MDB 600B BLOWER PERFORMANCE CURVE...
Страница 52: ...51 MDB 750B BLOWER PERFORMANCE CURVE...
Страница 53: ...52 Outlines And Dimensions Indoor MODEL MDB 075 100 B BR MODEL MDB 125C HORIZONTAL AIR DISCHARGE ONLY...
Страница 60: ...59 MODEL MMC 075C CR MODEL MMC 100C...
Страница 61: ...60 MODEL MMC 125BR 150C STANDARD VERTICAL DISCHARGE NON CONVERTIBLE...
Страница 69: ...68 MODEL INDOOR MDB 400B4 MDB 500B4 WITH SEQUENTIAL CONTROLLER OUTDOOR MMC 100B x 4 MMC 125B x 4...
Страница 70: ...69 MODEL INDOOR MDB 600B4 WITH SEQUENTIAL CONTROLLER OUTDOOR MMC 150C x 4...
Страница 71: ...70 MODEL INDOOR MDB 750B5 WITH MAGNETIC CONTACTOR OUTDOOR MMC 150C x 5 INDOOR AUXILLARY C1 C1...
Страница 72: ...71 Wiring Diagrams Heatpump INDOOR EXPORT MODEL MDB 075 100BR C3 0B MODEL MDB 125CR EXPORT...
Страница 73: ...72 MODEL MDB 150 200 250 BR2 EXPORT MODEL MDB 300 350 BR3 EXPORT...
Страница 74: ...73 MODEL MDB 400 500 BR4 EXPORT...
Страница 84: ...83 Refrigerant Circuit Diagram MODEL MMC 075C 100C...
Страница 85: ...84 MODEL MMC 075B 100B 125B 150C...
Страница 86: ...85 MODEL MMC 075CR WITH CAPILLARY TUBE EXPANSION SPECIFICATION...
Страница 87: ...86 MODEL MMC 100BR 125BR WITH CAPILLARY TUBE EXPANSION SPECIFICATION...
Страница 88: ...87 MODEL MMC 075CR WITH THERMAL EXPANSION VALVE SPECIFICATION...
Страница 89: ...88 MODEL MMC 100BR 125BR WITH THERMAL EXPANSION VALVE SPECIFICATION...
Страница 101: ...100 SEQUENTIAL CONTROLLER BLOCK DIAGRAM...
Страница 163: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...