background image

2

Nomenclature

MCW  200  D- 8 R X  F-A A F1 - E 

Export

1-100mm Extended Drain Pan

2-200mm Extended Drain Pan

Omitted for Standard Drain Pan

Description of Products:

A-Standard Drain Pan

F-Extended Drain Pan

G-Extended Drain pan+2Way Valve

H-Extended Drain Pan+3Way Valve

I-Standard Drain Pan+2Way Valve

J-Standard Drain Pan+3Way Valve

K-Standard Drain Pan+Controller

L-Extended Drain Pan+Controller

M-Extended Drain Pan+2 Way Valve+Controller

N-Extended Drain Pan+3 Way Valve+Controller

O-Standard Drain Pan+2 Way Valve+Controller

P-Standard Drain Pan+3 Way Valve+Controller

Material of Drain Pan

A-Standard Material

S-Stainless Steel

Power Supply: A-220V/1PH/50Hz

With Filter

Back Rerurn Air Plenum With Bottom Removal Filter

Pipe Connection: R-Right Hand

L-Left Hand(Facing Air Flow)

75Pa External Static Pressure

Design Series: D-4 Rows and 2 Pipes

Nominal Air Flow(CFM)

McQuay Horizontal Ceiling concealed Fan Coil Unit

Содержание MCW1000D

Страница 1: ...ING CONCEALED Chilled Water Fan Coil Unit Models MCW200D MCW800D MCW300D MCW900D MCW400D MCW1000D MCW500D MCW1200D MCW600D MCW1400D Technical Manual Engineered for flexibility and performance TM MCWD...

Страница 2: ...in illustrations cover the general appearance of McQuay International products at the time of publication We reserve the right to change design and construction specifications at any time without noti...

Страница 3: ...ler L Extended Drain Pan Controller M Extended Drain Pan 2 Way Valve Controller N Extended Drain Pan 3 Way Valve Controller O Standard Drain Pan 2 Way Valve Controller P Standard Drain Pan 3 Way Valve...

Страница 4: ...customer requirements the new FCUs adopt the most reasonable and optimization water circuit design and utilize the national level thermal test room to guarantee both the perfect performance and a low...

Страница 5: ...75 75 75 75 75 75 in wg 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 RATED POWER INPUT W 74 98 107 123 167 268 275 304 501 555 SOUND PRESSURE LEVEL DB A 42 9 43 1 45 9 46 2 47 9 50 0 48 8 49 1 53 3 53 0 C...

Страница 6: ...n TESTING PRESSURE Pressure test 3 3MPa for 1 minute Leakage test 1 6MPa for 5 minutes TUBE MATERIAL COPPER DIAMETER mm 9 52 in 3 8 THICKNESS mm 0 3 in 0 012 FIN MATERIAL ALUMINIUM THICKNESS mm 0 11 i...

Страница 7: ...20 46 9 21 30 40 41 41 38 32 24 46 6 MEDIUM 21 31 40 42 41 38 28 19 46 5 21 31 40 41 40 38 31 23 46 2 LOW 18 29 38 40 39 35 25 16 44 4 20 30 38 40 38 36 28 19 44 6 600D HIGH 22 31 41 42 43 40 30 20 4...

Страница 8: ...5 14 5 3 4 2 4 0 344 15 8 MCW500D 75 24 0 17 9 5 5 14 5 3 8 2 7 0 389 7 2 MCW600D 75 24 0 17 9 5 5 14 5 5 0 3 7 0 482 11 4 MCW800D 75 24 0 17 9 5 5 14 5 6 2 4 6 0 618 10 0 MCW900D 75 24 0 17 9 5 5 14...

Страница 9: ...783 1651 1536 1420 1408 1347 1241 1120 L 1496 1413 1365 1281 1233 1143 1096 1088 1002 892 900D H 2197 2113 2027 1920 1795 1683 1622 1560 1455 1325 M 2078 1994 1902 1814 1685 1586 1538 1477 1370 1247 L...

Страница 10: ...ING LIMITS Maximum water side pressure 16 bar Minimum entering water temperature 3 C Maximum entering water temperature 95 C Minimum air inlet temperature 5 C Maximum air inlet temperature 43 C Power...

Страница 11: ...30 40 50 60 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 Water Flow m 3 h Water Pressure Drop kPa 400D 300D 200D 600D 500D 900D 800D 1400D 1200D 1000D Note The press...

Страница 12: ...51 94 143 218 2 902x244x25 2 600D 1214 1314 984 948 987 1047 534 150 251 94 143 218 2 1002x244x25 3 800D 1464 1564 1234 1198 1237 1297 534 150 251 94 143 218 3 1252x244x25 3 900D 1564 1664 1334 1298 1...

Страница 13: ...series H M L are connected to SHF HF MF respectively MODEL MCW 200 1400 POWER SOURCE ORANGE DRAWING NO M08024067082 N L MF LF SHF HF L M BROWN H YELLOW FAN BLACK FAN SPEED SWITCH NOTE MOTOR 1 BLACK F...

Страница 14: ...to the carrier with a formal claim LOCATION Before installation please check the following 1 There must be enough space for unit installation and maintenance Please refer to the unit s drawings and di...

Страница 15: ...IPE CONNECTION 1 Using suitable fittings as water pipe connections Refer to the specification 2 The water inlet is on the bottom while outlet on top 3 The connection must be concealed with rubberized...

Страница 16: ...15 Exploded view Part List 8 FAN 6 FILTER 7 MOTOR 2 FANDECK 4 PLENUM 1 TOP PLATE 3 DRAIN GUIDE PLATE 5 COIL 9 DRAIN PAN 10 HEDER OUTLET 11 HEADER NLET...

Страница 17: ...4061142 M02124061198 M02124061198 MODEL 800D 900D 1000D 1200D 1400D 1 TOP PLATE PART NO M01014060796 M01014060797 M01014060798 M01014060796 M01014060798 2 FAN DECK PART NO M01014060806 M01014060807 M0...

Страница 18: ...amless copper tubes slit type aluminum blue fins bonded to the tubes by mechanical expansion Each coil has a manual air vent and two Rc3 4 water pipe connections with a working pressure of 1 6MPa 3 Fa...

Страница 19: ...ect at the time of going to press we are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment without notice Details of specifications and eq...