R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
75
3. Additional Refrigerant Charge
Caution
● Refrigerant cannot be charged until field wiring has been completed.
● Refrigerant may only be charged after performing the leak test and the vacuum pumping.
● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view
of the danger of liquid hammer.
● Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the
appropriate refrigerant is charged.
● Refrigerant containers shall be opened slowly.
● Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter
and the length of the liquid side pipe of the outdoor unit/indoor unit
R(g) D(mm)
L(m)
φ6.35
Φ9.52
Φ12.7
Less than 5m (One-way)
—
—
—
Added Refrigerant When
20g/m×(L-5)
40g/m×(L-5)
60g/m×(L-5)
Содержание MCI16036CCU216A
Страница 12: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 12 Operation temp C 16 32 16 32...
Страница 14: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 14 3 Service Space...
Страница 15: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 15 4 Wiring Diagrams...
Страница 16: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 16...
Страница 23: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 23 1 E4 E5 E6 T4 T5 T3 temperature sensors error...
Страница 25: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 25 4 E12 IPM modular sensor error...
Страница 26: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 26 5 E13 HLP Pressure sensor error...
Страница 27: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 27 6 E14 H8 H12 T3 or T5 sensor disconnect error...
Страница 28: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 28 7 E15 High pressure switch error...
Страница 41: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 41 1 3 Dimension MQC164036CCK216B MQC164060CCK216B...
Страница 60: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 60 2 7 Exploded View 2 7 1 MQC164036CFC216B...
Страница 63: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 63 2 7 2 MQC164060CFC216B...
Страница 81: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 81 16 seer Outdoor with Duct...
Страница 82: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 82 16 seer Outdoor with Floor Ceiling...
Страница 83: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 83 16 seer Outdoor with 10 seer AHU...