R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
50
E5: Outdoor unit failure
Check the detail of failure at the outdoor unit.
E7: EEPROM failure
Change the indoor mainboard
E8: The protection for the stall of indoor fan motor
Solution:
(1)Check the connection between motor and main board is loosen or not, inset it firmly
(2)Check that is something blocked the motor or fan blade, if it is, remove it; if not, change the indoor main board or
DC motor
E9: Indoor unit and wire controller communication failure
Solution:
(1)Check the connection between wired controller and main board is loosen or not, inset it firmly
(2)Connect with a new wired controller, if not solve, change with a new communication cable
(3)If all above steps done, it still not solves, change the indoor main board or transformer.
F6: Outdoor condenser pipe temperature sensor (T3) failure
Solution:
(1)Check the T3 sensor connection loosen or not, inset it firmly, if not solve, go to next step;
(2)Take out the sensor, measure the resistance of the sensor, it is about 5KΩ at 25
℃
, if not, replace it; if resistance
normally, change the main board.
EE: Water fulfilled protection (Alarm of condensing water overflow)
Содержание MCI16036CCU216A
Страница 12: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 12 Operation temp C 16 32 16 32...
Страница 14: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 14 3 Service Space...
Страница 15: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 15 4 Wiring Diagrams...
Страница 16: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 16...
Страница 23: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 23 1 E4 E5 E6 T4 T5 T3 temperature sensors error...
Страница 25: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 25 4 E12 IPM modular sensor error...
Страница 26: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 26 5 E13 HLP Pressure sensor error...
Страница 27: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 27 6 E14 H8 H12 T3 or T5 sensor disconnect error...
Страница 28: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 28 7 E15 High pressure switch error...
Страница 41: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 41 1 3 Dimension MQC164036CCK216B MQC164060CCK216B...
Страница 60: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 60 2 7 Exploded View 2 7 1 MQC164036CFC216B...
Страница 63: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 63 2 7 2 MQC164060CFC216B...
Страница 81: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 81 16 seer Outdoor with Duct...
Страница 82: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 82 16 seer Outdoor with Floor Ceiling...
Страница 83: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 83 16 seer Outdoor with 10 seer AHU...