IM 865
19
TROUBLE SHOOTING CHART
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
• Power off or loose electrical connection
•
Check for correct voltage at compressor contactor in control
box
• Thermostat out of calibration-set too high
•
Reset
• Defective contactor
•
Check for 24 volts at contactor coil - replace if contacts are
open
• Blown fuses
•
Replace fuses
• Transformer defective
•
Check wiring-replace transformer
• High pressure control open (if provided)
•
Reset-also see high head pressure remedy-The high pressure
control opens at 450 PSIG
• Interconnecting low voltage wiring damaged
•
Replace thermostat wiring
Condenser fan runs, compressor
• Run or start capacitor defective (single phase only)
•
Replace
doesn’t
• Start relay defective (single phase only)
•
Replace
• Loose connection
•
Check for correct voltage at compressor -
check & tighten all connections
• Compressor stuck, grounded or open motor winding
•
Wait at least 2 hours for overload to reset.
open internal overload.
If still open, replace the compressor.
• Low voltage condition
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
• Low voltage condition
•
Add start kit components
Insufficient cooling
• Improperly sized unit
•
Recalculate load
• Improper airflow
•
Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge
•
Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system
•
Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage
•
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Compressor short cycles
• Incorrect voltage
•
At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector
•
Replace - check for correct voltage
• Refrigerant undercharge
•
Add refrigerant
Registers sweat
• Low evaporator airflow
•
Increase speed of blower or reduce restriction - replace air
filter
High head-low vapor pressures
• Restriction in li
q
uid line, expansion device or filter drier
•
Remove or replace defective component
• Incorrect capillary tubes
•
Change coil assembly
High head-high or normal vapor
• Dirty condenser coil
•
Clean coil
pressure - Cooling mode
• Refrigerant overcharge
•
Correct system charge
• Condenser fan not running
•
Repair or replace
• Air or non-condensibles in system
•
Recover refrigerant, evacuate & recharge
Low head-high vapor pressures
• Defective Compressor valves
•
Replace compressor
• Incorrect capillary tubes
•
Replace coil assembly
Low vapor - cool compressor -
• Low evaporator airflow
•
Increase speed of blower or reduce restriction - replace air
iced evaporator coil
filter
• Operating below 65°F outdoors
•
Add Low Ambient Kit
• Moisture in system
•
Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure
• Excessive load
•
Recheck load calculation
• Defective compressor
•
Replace
Fluctuating head & vapor
• Air or non-condensibles in system
•
Recover refrigerant, evacuate & recharge
pressures
Gurgle or pulsing noise at
• Air or non-condensibles in system
•
Recover refrigerant, evacuate & recharge
expansion device or li
q
uid line
Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical
shock resulting in personal injury or death.
▲
▲
DANGER
!
Содержание Maverick I IM 865 MPS006AY
Страница 17: ...IM 865 17 6 TON AIR CONDITIONER SYSTEM CHARGE CHART REFRIGERANT 22 6 TON CIRCUIT 01 ...
Страница 18: ...18 IM 865 6 TON AIR CONDITIONER SYSTEM CHARGE CHART REFRIGERANT 22 6 TON CIRCUIT 02 ...
Страница 20: ...20 IM 865 ELECTRICAL WIRING DIAGRAM 208 230 460 575 3 PHASE 60 HZ BELT DRIVE DUAL CIRCUIT ...
Страница 21: ...IM 865 21 ...
Страница 22: ...22 IM 865 ...
Страница 23: ...IM 865 23 ...
Страница 24: ...24 IM 865 2007 McQuay International www mcquay com 800 432 1342 ...