10
IM 865
Miscellaneous
ELECTRICAL DATA
Minimum Circuit Ampacity
34/34
Unit Information
Unit Operating
Voltage Range
187-253
Minimum Overcurrent
Protection Device Size
40/40
Maximum Overcurrent
Protection Device Size
40/40
Compressor Motor
No.
2
Volts
208/230
Phase
3
HP
3
RPM
3450
Amps (RLA)
11.4/11.4
Amps (LRA)
77/77
Condenser Motor
No.
1
Volts
208/230
Phase
1
HP
1/3
Amps (FLA)
2.6
Amps (LRA)
4.7
Evaporator Fan
No.
1
Volts
208/230
Phase
3
HP
1 1/2
Amps (FLA)
5.8
Amps (LRA)
0
0
5.8
1 1/2
3
208/230
1
4.7
2.6
1/3
1
208/230
1
77/77
11.4/11.4
3450
3
3
208/230
2
40/40
40/40
34/34
187-253
0
2.8
1 1/2
3
460
1
2.4
1
1/3
1
460
1
39
5.9
3450
3
460
2
20
20
18
414-506
0
2.8
1 1/2
3
460
1
2.4
1
1/3
1
460
1
39
5.9
3450
3
460
2
20
20
18
414-506
0
2.3
1 1/2
3
575
1
1.5
0.9
1/3
1
575
1
31
4.7
3450
3
575
2
15
15
14
518-632
0
2.3
1 1/2
3
575
1
1.5
0.9
1/3
1
575
1
31
4.7
3450
3
575
2
15
15
14
518-632
006AYCL
006AYCM
006AYDL
006AYDM
006AYYL
006AYYM
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
Table A
Содержание Maverick I IM 865 MPS006AY
Страница 17: ...IM 865 17 6 TON AIR CONDITIONER SYSTEM CHARGE CHART REFRIGERANT 22 6 TON CIRCUIT 01 ...
Страница 18: ...18 IM 865 6 TON AIR CONDITIONER SYSTEM CHARGE CHART REFRIGERANT 22 6 TON CIRCUIT 02 ...
Страница 20: ...20 IM 865 ELECTRICAL WIRING DIAGRAM 208 230 460 575 3 PHASE 60 HZ BELT DRIVE DUAL CIRCUIT ...
Страница 21: ...IM 865 21 ...
Страница 22: ...22 IM 865 ...
Страница 23: ...IM 865 23 ...
Страница 24: ...24 IM 865 2007 McQuay International www mcquay com 800 432 1342 ...