McQuay LDD Скачать руководство пользователя страница 6

Page 6 of 24 / IM 439

Duct Collar Side

Duct
Collar

Filter
Rack

Ductwork and Attenuation

Discharge ductwork is normally used with these conditioners.
Return air ductwork may also be required but will require field
installation of a return air duct collar.

All ductwork should  conform to industry standards of good

practice as described in ASHRAE Systems Guide.

The discharge duct system will normally consist of a flex-

ible connector at the unit, a transition piece to the final duct
size, a short run of duct, an elbow without vanes and a trunk
duct tee’d  into branch ducts with discharge diffusers as shown
in Figure 10. Transition piece must not have angles totalling
more than 30 degrees or severe loss of air performance can
result.

All units have multiple fan outlets. A single duct can en-

close all the  openings as shown in Figure 10; however, the
preferred method for minimum static pressure loss would be
individual ducts at each outlet connected to a larger duct down-
stream.

For minimum noise transmission, the metal duct material

should be internally lined with acoustic fibrous insulation.

The ductwork should be laid out so that there is no line of

sight between the conditioner discharge and the distribution
diffusers.

Return air ducts can be brought in adjacent to the return

air of the conditioner. Typically, the equipment room becomes
the common return air plenum.

Do not insert sheetmetal screws directly into the unit cabi-

net for connection of supply or return air ductwork, especially
return air ductwork which can hit the drain pan or the air coil.

Ventilation Air

Outside air may be required for ventilation. The temperature
of the ventilation air must be controlled so that mixture of out-
side air and return air entering the conditioner does not ex-
ceed conditioner application limits. It is also general practice
to close off the ventilation air system during unoccupied peri-
ods (night setback).

The ventilation air system is generally a separate build-

ing subsystem with distribution ductwork. Simple introduction
of the outside air into each return air plenum chamber rea-
sonably close to the conditioner air inlet is not only adequate,
but recommended. Do not duct outside air directly to the con-
ditioner inlet. Provide sufficient distance for thorough mixing
of outside and return air 

(see Operating Limits on page 9).

Optional Duct Collar and 2" (51 mm)
Filter Rack

The optional duct collar kit is used to facilitate connection of
return air duct to the unit. The duct collar kit can be used in
conjunction with the standard 1" (25 mm) thick filter rack or
the optional 2" (51 mm) filter rack.

The 2" (51 mm) filter rack facilitates the installation of 2"

(51 mm) thick filters for side removal. The 2" (51 mm) filter
rack replaces the existing 1" (25 mm) filter rack and does not
require the use of the optional return air duct collar.

The kits are installed as follows:

1.

Remove all filters, filter racks and brackets. Save all
screws. Discard bracket end.

2.

Attach top duct collar in conjunction with top filter rack
with truss head screws.

3.

Attach bottom duct collar and filter rack.

4.

On single compressor units, attach two flanges using four
(4) #8 truss head screws provided.

5.

Attach center support in original location.

6.

Locate and attach center filter racks using screws pro-
vided.

7.

Attach duct collar sides using eight (8) #10 sheetmetal

8.

No point in the drain system may be above the drain
connection of any unit.

9.

Automatic flow controlled devices must not be installed
prior to system cleaning and flushing.

10. A high point of the piping system must be vented.

11.

Check local code for the need of dielectric fittings.

Figure 8. Assembly detail

Center Support

Chassis

Door End

Duct Collar Side

Center Filter Racks

Side Flanges

Top Duct Collar

Top Filter Rack

Filters

Figure 9.

Содержание LDD

Страница 1: ...tallation Maintenance Data IM 439 15 Group WSHP Part Number 106581103 Date June 2006 Large Vertical Water Source Heat Pumps 6 thru 25 Tons Models LDD LDE LDL LDS LME LMH LML LMS 2006 McQuay Internatio...

Страница 2: ...xt Range LMH High Static Large Vertical Mark IV Std Range LDL Std Large Vertical DDC Controls Ext Range Less Board LML High Static Large Vertical Mark IV Ext Range LDS Std Large Vertical DDC Controls...

Страница 3: ...on submittal drawings 7 The installing contractor will find it beneficial to confer with piping sheetmetal ceiling and electrical foremen together before installing any conditioners Note Check the un...

Страница 4: ...2 114 mm 51 2 140 mm 25 8 61 mm Figure 2 Side view from piping end Each unit is shipped with a filter bracket for side filter removal Two fan discharges and piping arrangements are available With the...

Страница 5: ...pitch diameter for desired speed by open ing moving parts by half or full turns from closed position Do not open more than five full turns 3 Replace external key E and securely tighten setscrews B ove...

Страница 6: ...ication limits It is also general practice to close off the ventilation air system during unoccupied peri ods night setback The ventilation air system is generally a separate build ing subsystem with...

Страница 7: ...he union one to hold the line and one for simultaneous tightening of the nut 4 Supply and return shutoff valves are required at each con ditioner The return valve is used for balancing and should have...

Страница 8: ...ermostat to Cool If the thermostat is an automatic changeover type simply set the cooling temperature to the coolest position On manual changeover types addi tionally select Cool at the system switch...

Страница 9: ...e with local codes or the National Electrical Code whichever is applicable 2 Apply correct line voltage to the unit Each unit is supplied with a 3 lug terminal block in the main control for three phas...

Страница 10: ...BK 21 15 Fan Motor GN GND YE RD BK Common Comp Fan Mark IV AC Board Compressor Contactor 36 35 21 L1 37 37 Breaker Optional OR 230V RD 208V BK RD 460V BK BK YE GND Xformer REV Valve Solenoid COF LT L...

Страница 11: ...itch BK WH BK WH BR BR BL BL BR53 Low Temp BR BR BL BL RD54 BR52 BK51 BL50 BL40 BK41 BR43 RD44 BR42 BK51 BL50 BL40 BK41 YE Condensate Overflow Sensor BK30 BK49 RD48 BK BK BK59 RD58 BK BK 1 2 5 3 4 BR8...

Страница 12: ...troller 68 67 66 65 64 63 62 1 2 3 4 5 6 7 11 10 9 8 7 6 5 4 3 2 1 J6 2 3 4 5 7 8 9 10 11 J5 J4 Low Temp SIG Lo Press SIG Condensate Lo Temp SRC RV Out Comp Com Comp Out Fan Com Fan Out 24VAC 24V Gnd...

Страница 13: ...3 4 1 2 3 4 1 J2 J1 2 1 46 Disch Air Water Out 44 42 43 Condensate Lo Temp SRC Lo Temp SIG Lo Press SIG Lo Press SRC Hi Press SIG RV Com RV Out Comp Com Comp Out Fan Com Fan Out 24VAC 24V Gnd Dischar...

Страница 14: ...he reversing valve is set up to be energized in the heating mode The circuit board has a fan interlock circuit to energize the fan whenever the compressor is on if the thermostat logic fails to do so...

Страница 15: ...s of the standard thermostat are then connected to the Mark IV AC board thermostat inputs and control inputs as needed Any re maining board input s may be operated by additional thermostat out puts or...

Страница 16: ...application guide LIA217 for thermostat 107095901 installation details WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit1 O W2 G W1 Y1 F E L U A P V R C R C W1 Y1 W2 Y2 G Thermostat Terminals W...

Страница 17: ...t Sizes 180 to 290 Non Programmable Electronic Thermostat 2 Circuits P N 107095901 7 Day Programmable Electronic Thermostat 2 Circuits P N 107095901 Includes Thermostat and Wall Plate Refer to the ins...

Страница 18: ...ressor operation is required the Mark IV AC P terminal will change state causing a contact closure between terminal 58 and 64 signaling the loop water control LWC panel to restart the loop pump if Off...

Страница 19: ...wn below can only be used when the P terminal is not being used as a pump restart signal to other equipment If the P terminal must be used as a pump restart signal to other equipment then wire the aux...

Страница 20: ...kit you attach the sheet metal enclosure to the unit as shown route the 4 wire harness through knockouts and connect to the Mark IV AC board mount and connect and insulate the water tempera ture senso...

Страница 21: ...rmally open contacts will close Operation In this example the auxiliary relay is used to interface other control devices to the Mark IV AC board Using the Orange and White wires and 24vac or 24vdc ano...

Страница 22: ...ot required 3 Fresh Air Damper These outputs provide a signal that can be used to control a remote fresh air damper The output will energize when the unit fan is energized and de energize when the uni...

Страница 23: ...eating Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor...

Страница 24: ...s will depend upon the project requirements Some applications such as motels produce a lot of lint from carpeting and linen changes and will require more frequent filter changes It is suggested that t...

Отзывы: