background image

IM 818

  Page 17

Evacuating and Charging

Evacuating the tubing and the indoor unit

The outdoor unit is pre-charged with refrigerant R-22. The
indoor unit and the refrigerant connection tubing must be
evacuated as follows:

1.

Remove the 3 caps from the valves on the outdoor unit.

2. Connect the center of the charging gauge to the vacuum

pump.

3. Connect the charging gauge to the service port of the

3-way valve (See Figure 13).

4. Start the pump and evacuate to -760 mm Hg (-29.9" Hg).
5. Close the valve of the changing gauge and stop the vac-

uum pump.

6. On the outdoor unit, open both valves using a 4 mm

Allen wrench. (See Figure 12.)

Figure 12. 3-way Suction Valve on Outdoor Unit

Figure 13 Evacuation Schematic

Additional charge

The refrigerant is pre-charged in the outdoor unit. If the tub-
ing length ("L") between the indoor and outdoor unit is no
more than 25 ft., additional charge after evacuation is not
necessary. If the tubing length ("L") is more than 25 ft., use
additional R-22 as indicated in Table 6. (See Installation Dia-
gram on page 5).

Table 6: Additional R-22 ounces per ft. (when tubing 
length "L" is more than 25 feet - see Installation 
Diagram on page 5)

Charge operation

This operation must be done by weighing the R-22 being
added thru the service port on the 3 way suction valve. (See
Table 6 and  Figure 14.)

1.

Remove the service port cap.

2. Connect the low pressure side of the charging gauge to

the suction service port center of the cylinder tank and
close the high pressure side of the gauge. Purge the air
from the service hose (See Figure 14).

3. Start the air conditioner unit.
4. Open the gas cylinder and low pressure charging valve.
5. When the required refrigerant quantity is pumped into

the unit, close the low pressure side and the gas cylinder
valve.

6. Disconnect the service hose from service port. Put back

the service port cap.

Figure 14. Charging Schematic

Hex Socket

for 4 mm

Allen wrench

Flare Nut

Refrigerant
Tubing

Service

Port

Outdoor Unit

3-way Valve

Indoor Unit

Liquid side

Outdoor Unit

Close

Discharge Valve

Suction Valve

Close

Gas side

Vacuum

 

Pump

High

Press

.

Low

Press.

Model

Oz. Per Ft.

Max. Length "L"-Ft.

20A

.16

49’

25A

.40

49’

30A

.53

115’

40A

.55

115’

50A

.55

115’

20AR

.16

49’

25AR

.50

49’

30AR

.53

115’

40AR

.55

115’

50AR

.55

115’

Indoor Unit

Outdoor Unit

Liquid side

Gas side

High

Press

.

Low

Press

.

Discharge Valve

Suction Valve

Содержание IM818

Страница 1: ...uctless Split Type Air Conditioner Installation and Maintenance Manual IM818 Group Unitary Part Number IM818 Date March 2005 2005 McQuay International Indoor Unit Wireless Remote Control Standard Outd...

Страница 2: ...e Controller Operation Guide 18 Wired Wall Control Optional 19 Special Features 20 Dry mode 20 Heat mode heat pump only 20 Overheating protection heat pump only 20 Frost prevention 20 Fan speed and ra...

Страница 3: ...ect power before servicing can cause severe personal injury or death CAUTION Use copper conductors only Unit terminals are not designed to accept other types of conductors Failure to do so can cause d...

Страница 4: ...More Detail 32 1 4 32 1 4 14 3 4 13 3 4 36 5 8 36 5 8 Front Panel Frame Frame and Front Panel Model MLC 20 25 B BR 30 40 50C CR A 16 19 1 4 B 33 40 1 2 C 25 1 2 33 1 2 D 2 1 4 3 1 2 E 13 1 4 15 3 4 F...

Страница 5: ...es The suspending structure must be stronge enough to avoid amplifying noise and vibration The height above the finished ceiling must be 13 3 4 mini mum See Figure 4 Avoid excessive heat Do not instal...

Страница 6: ...er the com pressor stops Max head is 27 H2O Water Level Switch This normally closed switch will open and turn off the com pressor if the condensate level gets to high If it closes within 5 minutes the...

Страница 7: ...Reattach the air intake grille and filter to the front panel The grille can swing in 4 directions Position the grille to maxi mize accessibility when open See Figure 7 From Front Panel LED Connectors...

Страница 8: ...gure 10 Remove burrs from cut ends by holding tubing down wards to prevent metal chips from entering the tubing Slide flare nut on tubing Flare the tubing as shown in Figure 10 Figure 11 and Table 2 T...

Страница 9: ...ned back on This will require two disconnects one by the outdoor unit and one by the indoor unit Table 4 Wire Fuse Breaker Requirements Cooling Only Table 5 Wire Fuse Breaker Requirements Heat Pump On...

Страница 10: ...C I C MC FAN MOTOR GREEN YELLOW GREEN YELLOW COMP N L2 NOTE DISCONNECT CN6 IF CN4 IS USED KEY FIELD SUPPLY WIRING AS AIRSWING MOTOR DP DRAIN PUMP CONDENSATE COMP WHITE FAN MOTOR BROWN C CM BLUE DP MO...

Страница 11: ...SED KEY FIELD SUPPLY WIRING AS AIRSWING MOTOR DP DRAIN PUMP CONDENSATE 208 230V 1 PH L2 L1 10A REDRED BLUE REDRED RED R L1S L2 T L3 U T1V T2 W T3 A2 A1 BLACK RED BLUE WHITE COMP L N GREEN YELLOW RED B...

Страница 12: ...Y FIELD SUPPLY WIRING AS AIRSWING MOTOR DP DRAIN PUMP CONDENSATE 208 230V 1 PH 60Hz L2 L1 10A RED RED REDRED RED RED RED RED RED RED RED 1L1 3L2 5L3 2T1 4T2 6T3 1 2 A2 A1 BLUE BLACK BLUE BLUE RED BLAC...

Страница 13: ...CN6 IF CN4 IS USED KEY FIELD SUPPLY WIRING AS AIRSWING MOTOR DP DRAIN PUMP CONDENSATE WHITE FAN MOTOR CM DP MODEL MCK 020 025AR INDOOR UNIT HEAT PUMP MODEL MLC M4L020 025BR OUTDOOR UNIT HEAT PUMP L L1...

Страница 14: ...60Hz L2 L1 10A REDRED RED RED 21 L2 L3 22 T2 T3 A2 A1 BLUE WHITE COMP L N RED BLUE C R S COMPRESSOR NOTE FIELD INSTALL 10A FUSE IN BLUE WIRE AS SHOWN DP MODEL MCK 030AR INDOOR UNIT HEAT PUMP MODEL MLC...

Страница 15: ...08 230V 1 PH 60Hz L2 10A RED 1L1 5L3 1 2T1 6T3 2 A2 A1 BLUE COMP L N RED BLUE C R S COMPRESSOR NOTE FIELD INSTALL 10A FUSE IN BLUE WIRE AS SHOWN DP MODEL MCK 040AR 50AR INDOOR UNIT HEAT PUMP MODEL MLC...

Страница 16: ...OUTDOOR UNIT COOLING ONLY OPTIONAL LOW AMBIENT KIT OL MODEL MLC20BR 25BR OUTDOOR UNIT HEAT PUMP OPTIONAL LOW AMBIENT KIT FM CM 4 3 2 1 FSCM COMP N OF 4V TO INDOOR UNIT RED BLACK TH2 BLACK 4V BLACK BLA...

Страница 17: ...er ft when tubing length L is more than 25 feet see Installation Diagram on page 5 Charge operation This operation must be done by weighing the R 22 being added thru the service port on the 3 way suct...

Страница 18: ...ture Setting Set the desired room temperature by pressing the buttons to increase or decrease the set temperature The temperature setting range is from 60 F to 86 F Press both buttons simultaneously t...

Страница 19: ...air baffle for better air dis tribution 9 Display normally shows room temperature Momen tarily shows set point when a change is made 10 Heat symbol blinks while outdoor coil defrosts heat pump only 1...

Страница 20: ...ing Conditions Cooling 32 F on size 20 and 25 23 F on size 30 40 and 50 with optional Low Ambient Kit Heating heat pump only Ts Dry Bulb Temperature Th Wet Bulb Temperature Overall Checking Ensure tha...

Страница 21: ...or Lights IR Receiver LED Indicator Lights and On Off Switch SLEEP TIMER POWER HEAT TIMER POWER POWER TIMER SLEEP HEAT Mode or Fault Action or Possible Cause ON ON Timer on ON ON Sleep mode on ON ON H...

Страница 22: ...rting Wait for 3 to 4 minutes for the compressor to start operating Fans and compressor do not operate Power failure Check fuse or circuit breaker Power supply is disconnected Delay timer may be set i...

Страница 23: ...nel by wiping it using soft cloth soaked in lukewarm water below 40 C 104 F with neutral detergent solution Note Do not use gasoline volatile substances or chemicals to clean the unit Every year Conde...

Страница 24: ...818 2004 McQuay International www mcquay com 800 432 1342 This document contains the most current product information as of this printing For the most up to date product information please go to www...

Отзывы: