1-5
English
Piping Length & Elevation
If the pipe is too long, both the capacity and reliability of
the unit will drop. As the number of bends increases,
resistance to the flow of refrigerant system increases, thus
lowering cooling capacity. As a result, the compressor may
become defective. Always choose the shortest path and
follow the recommendations as tabulated below:
REFRIGERANT PIPING
Outdoor Unit
Indoor Unit
H
L
Remove Burr
Cutting Copper Tube
Piping Works
•
Do not use contaminated or damaged copper tubing. Do
not remove plastic, rubber plugs and brass nuts from the
valves, fittings, tubings and coils until you are ready to
connect suction or liquid line into valves or fittings.
•
If any brazing work is required, ensure that the nitrogen
gas is passed through coil and joints while the brazing
work is being done. This will eliminate soot formation on
the inside walls of the copper tubings.
•
Cut the connection pipe with a pipe cutter.
•
Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips
from entering the pipe.
•
Insert the flare nuts, mounted on the connection parts of
both the indoor unit and outdoor unit onto the copper pipes.
•
Flare the pipe with extra length above the flaring tool as
shown in the table.
•
The flared edge must be even and not cracked or scratched.
1/4t
Copper Tube
Swaging Block
Ø Tube, D
A (mm)
Inch
mm
Imperial
Rigid
1/4"
6.35
1.3
0.7
3/8"
9.52
1.6
1.0
1/2"
12.70
1.9
1.3
5/8"
15.88
2.2
1.7
3/4"
19.05
2.5
2.0
Piping Connection To The Units
•
Align the center of the piping and tighten the flare nut
sufficiently with fingers.
•
Finally, tighten the flare nut with the torque wrench until
the wrench clicks.
Pipe Size mm / (in)
Torque Nm / (ft - lb)
6.35 (1/4)
18(13.3)
9.53 (3/8)
42(31.0)
12.7 (1/2)
55(40.6)
15.88 (5/8)
65(48.0)
19.05 (3/4)
78(57.6)
Indoor Piping
Flare Nut
Flared Tube
Flare Joint
Spanar
Torque Wrench
Remark:
The refrigerant pre-charged in the outdoor unit
is for piping length up to 7.62 m/25 ft.
Model
Maximum length, m (ft), L
Max. elevation, m (ft), H
Max. number of bends
Liquid pipe size
Gas pipe size
07
10
15
20
25
12 (39) 12 (39) 12 (39) 15 (49) 15 (49)
5 (16.4) 5 (16.4) 5 (16.4) 8 (26.2) 8 (26.2)
10
10
10
10
10
1/4"
1/4"
1/4"
1/4"
3/8"
3/8"
3/8"
1/2"
5/8"
5/8"
Содержание IM-WMF-0501
Страница 2: ......
Страница 66: ...6 2 i ii 2 3 3 4 5 6 R410A 7 Octopo R407C 7 7 8 10 10 10 11 a3 xpa 11 12 12...
Страница 67: ...6 3 Hapy SLC SLB A B C D 300 1000 300 500 45 C 11 8 39 4 11 8 19 7 2 A A B C D...
Страница 73: ...6 9...
Страница 75: ...6 11 1 6 2 3 4 T S R S T 1 PP01 2 R 71 LED PW P_R P_S P_T...
Страница 76: ...6 12 1 40 104 F 2 3 1 40 104 F 2 2 2 2 30 C 86 F 3 4 1 3 2 3 4 5 6 7...
Страница 77: ......
Страница 80: ......
Страница 95: ......
Страница 96: ...bzU w W eOKJ W M uJ X U WG W Q UN H WL d w VO J c dO H w UF b o UF s X w UM u u UH u W rOLB q bF o lMB kH...