1-8
Model
07F / 10F/ 15F
20F
25F
07FR / 10FR / 15FR
20FR
25FR
10m/32.8ft
12m/39.4ft 15m/49.2ft
35
65
–
35
65
110
90
165
280
50
90
–
60
110
185
120
220
370
Additional charge in gram (For R22/R407C models)
Open
Open
Suction
Valve
Discharge
Valvet
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Check
Valve
Close
Hi
Low
Charge operation
This operation must be done by using a gas cylinder and a
precise weighing machine. The additional charge is topped-
up into the outdoor unit using the suction valve via the ser-
vice port.
•
Remove the service port cap.
•
Connect the low pressure side of the charging gauge to
the suction service port center of the cylinder tank and
close the high pressure side of the gauge. Purge the air
from the service hose.
•
Start the air conditioner unit.
•
Open the gas cylinder and low pressure charging valve.
•
When the required refrigerant quantity is pumped into
the unit, close the low pressure side and the gas cylinder
valve.
•
Disconnect the service hose from service port. Put back
the service port cap.
Model
07F / 10F/ 15F
20F
25F
07FR / 10FR / 15FR
20FR
25FR
10m/32.8ft
12m/39.4ft 15m/49.2ft
35
60
–
35
60
100
80
150
255
45
80
–
55
100
165
110
200
335
Additional charge in gram (For R410A models)
Additional charge
The refrigerant is pre-charged in the outdoor unit. If the
piping length is less than 7.62m (25ft), then additional charge
after vacuuming is not necessary. If the piping length is more
than 7.62m (25ft), then use the additional charge valve as
indicated in the table.
IR signal receiver
When an infrared remote control operating signal has
been transmitted, the signal receiver on the indoor unit
will make a <beep> sound to confirm acceptance of the
signal transmission.
Cooling unit
The table shows the LED indicator lights for the air condi-
tioner unit under normal operation and fault conditions.
The LED indicator lights are located at the bottom right
side of the air conditioner unit.
INDICATOR LIGHTS
LED indicator lights
IR Receiver
LED Indicator Lights for Cooling Unit
Timer
Sleep mode
Power ON
Dry mode
LED Indicator Lights : Normal Operation And Fault Conditions For Cooling Unit
Operation / Fault Indication
Action
Timer on.
–
Sleep mode on.
–
Dry mode.
–
Frost prevention.
Clean the filter and switch to high fan.
Room air sensor contact loose/short.
Call your dealer.
Indoor coil sensor contact loose/short.
Call your dealer.
Sensor contact problem, compressor
overload protection trip or gas leak
Call your dealer.
Continuously
once every 2 sec.
twice every 2 sec.
3 times every 2 sec.
ON
ON or OFF
Blinking
Содержание IM-WMF-0501
Страница 2: ......
Страница 66: ...6 2 i ii 2 3 3 4 5 6 R410A 7 Octopo R407C 7 7 8 10 10 10 11 a3 xpa 11 12 12...
Страница 67: ...6 3 Hapy SLC SLB A B C D 300 1000 300 500 45 C 11 8 39 4 11 8 19 7 2 A A B C D...
Страница 73: ...6 9...
Страница 75: ...6 11 1 6 2 3 4 T S R S T 1 PP01 2 R 71 LED PW P_R P_S P_T...
Страница 76: ...6 12 1 40 104 F 2 3 1 40 104 F 2 2 2 2 30 C 86 F 3 4 1 3 2 3 4 5 6 7...
Страница 77: ......
Страница 80: ......
Страница 95: ......
Страница 96: ...bzU w W eOKJ W M uJ X U WG W Q UN H WL d w VO J c dO H w UF b o UF s X w UM u u UH u W rOLB q bF o lMB kH...