background image

Page 6 of 24 / IM 407

Figure 5.

Figure 6.

Balancing
Valve With
Close-off

Flexible Hose
With Brass
Pipe Fitting

Supply

Return

Condensate

Isolator Pad

Electrical &
Compressor
Access

Blower
Motor
Access

Note: Condensate drain connection must be minimum of 1" (25mm)
below connection to heat pump.

1

4

'' Per Foot

(21mm Per Meter)

Optional Cleanout

1

1

2

"

(38mm)

1

1

2

"

(38mm)

1. Open all valves to full open position and turn on power

to the conditioners.

2. Set thermostat for “Fan Only” operation by selecting

“Off” at the system switch and “On” at the fan switch. If
“Auto” fan operation were selected, the fan would cycle
with the compressor. Check for proper air delivery.

3. All units have two-speed motors. Reconnect for low

speed operation if necessary.

4. Set thermostat to “Cool.” If the thermostat is an auto-

matic changeover type, simply set the cooling tempera-
ture to the coolest position. On manual changeover
types additionally select “Cool” at the system switch.

Start-up

1. Prior to first operation of any conditioner, the water cir-

culating system must be cleaned and flushed of all con-
struction dirt and debris.

If the conditioners are equipped with water shutoff

valves, either electric or pressure operated, the supply
and return runouts must be connected together at each
conditioner location. This will prevent the introduction of
dirt into the unit. Additionally, pressure operated valves
only open when the compressor is operating.

Figure 7.

2. The system should be filled at the city water makeup con-

nection with all air vents open. After filling, vents should be
closed.

The contractor should start main circulator with pres-

sure reducing valve makeup open. Vents should be
checked in sequence to bleed off any trapped air to
assure circulation through all components of the system.

Power to the heat rejector unit should be off, and the

supplementary heat control set at 80

o

F (27

o

C).

While circulating water, the contractor should check

and repair any leaks in the piping. Drains at the lowest
point(s) in the system should be opened for initial flush
and blow-down, making sure city water fill valves are set
to make up water at the same rate. Check the pressure
gauge at pump suction and manually adjust the makeup
to hold the same positive steady pressure both before and
after opening the drain valves. Flush should continue for
at least two hours, or longer if required, to see clear, clean
drain water.

3. Supplemental heater and circulator pump should be shut

off. All drains and vents should be opened to completely
drain down the system. Short circuited supply and return
runouts should now be connected to the conditioner
supply and return connections. Teflon tape is recom-
mended over pipe dope for pipe thread connections. Use
no sealers at the swivel flare connections of hoses.

4. Trisodium phosphate was formerly recommended as a

cleaning agent during flushing. However, many states
and localities ban the introduction of phosphates into
their sewage systems. The current recommendation is to
simply flush longer with warm 80

o

F (27

o

C) water.

5. Refill the system with clean water. Test the litmus paper

for acidity, and treat as required to leave the water slightly
alkaline (pH 7.5 to 8.5). The specified percentage of
antifreeze may also be added at this time. Use commer-
cial grade antifreeze designed for HVAC systems only. Do
not use automotive grade antifreeze.

6. Set the system control and alarm panel heat add setpoint

to 70

o

F (21

o

C) and the heat rejection setpoint to 85

o

F

(29

o

C). Supply power to all motors and start the circulating

pumps. After full flow has been established through all
components including the heat rejector (regardless of
season) and air vented and loop temperatures stabilized,
each of the conditioners will be ready for check, test and
start-up and for air and water balancing.

Cleaning and Flushing System

Note: Do not overtorque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb,
finger-tight plus one quarter turn. Use two wrenches to tighten the union, one to hold the line and one for simultaneous tightening of the nut.

Supply Runout

Return Runout

Mains

Runouts Initially
Connected Together

Rubber Hose

Electrical Access Panel

Содержание FDD Series

Страница 1: ...iagrams 8 14 Unit operation 15 LED Status and Fault Output Status 16 Thermostat Connections Mark IV AC units 17 Options for Mark IV AC units 19 22 Troubleshooting 23 Maintenance 24 2006 McQuay Interna...

Страница 2: ...e of rough handling the cartons should be opened at once to check for concealed damage If any damage is found notify the carrier within 48 hours to establish your claim and request their inspection an...

Страница 3: ...ance Opt Controls Main Access Panel Condensate Water Supply Water Return Heat Pump With Right Hand Return Air Arrangement Return Air Opt Controls Elec Entrance Main Access Panel Condensate Water Suppl...

Страница 4: ...duct material the return air duct should be internally lined with acoustic insulation for sound attenuation Glass fiber duct board material is more absorb ing and may permit omission of the flexible c...

Страница 5: ...system may also be made to work ac ceptably but proper water flow balancing is more diffi cult to achieve and maintain 2 The piping can be steel copper or PVC 3 Supply and return runouts are usually...

Страница 6: ...for initial flush and blow down making sure city water fill valves are set to make up water at the same rate Check the pressure gauge at pump suction and manually adjust the makeup to hold the same po...

Страница 7: ...chine should not Operating Limits Environment This equipment is designed for indoor installation only Sheltered locations such as attics garages etc generally will not provide sufficient protection ag...

Страница 8: ...upplied relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitiv...

Страница 9: ...relays in series with the inputs Figure 10 Unit sizes 019 through 048 208 230 265 volts single phase 060686606 Rev C Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Pr...

Страница 10: ...switches are normally closed 5 Field supplied relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Figure 12 Unit sizes 02...

Страница 11: ...d relays attached to the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micr...

Страница 12: ...24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Proper ground...

Страница 13: ...o the 24 volt terminals R W Y or G may introduce electrical noise Never install relays in series with the inputs Notes 1 Mark IV AC controller board contains a static sensitive micropro cessor Proper...

Страница 14: ...for 208V operation If 230V power supply is used transformer must be wired by disconnecting the power lead from the red transformer primary wire Place an insulation cap on the red transformer primary w...

Страница 15: ...itch or low pressure switch on unit sizes 048 and 060 The unit does not have to be reset on a condensate overflow detection The Mark IV AC control board has a fault output signal to an LED on a wall t...

Страница 16: ...rces may be used to operate Mark IV AC board inputs Note The fault output is energized when no faults exist The fault output is de energized during faults and when unit power is off Using Drive Using...

Страница 17: ...with other wires Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal o...

Страница 18: ...rk IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip Multiple Unit Control Panel TB3 TB2 TB1 TB4 R C W1 Y1 W2 Y2 G Thermostat Terminals This version of the board...

Страница 19: ...nal is not being used as a pump restart signal to other equipment If the P terminalmustbeusedasapumprestartsignaltootherequipment then wire the auxiliary relay s yellow wire to Y1 white wire to W1 and...

Страница 20: ...r tempera ture sensor on the water supply line and then connect the duct heater control contacts to the duct heater control circuit 9 66 245 mm 007 042 14 50 368 mm 048 060 6 5 165 mm 007 042 4 12 105...

Страница 21: ...C P terminal will change state causing a contact closure between terminal 58 and 64 signaling the loop water control LWC panel to restart the loop pump if Off The pump restart relay kit is typically m...

Страница 22: ...signals is required on a single WSHP the MicroTech 2000 Auxiliary Module Kit 107239001 must be used and these additional output control signals will be connected to the Auxiliary board 1 circuit unit...

Страница 23: ...eating Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor...

Страница 24: ...differences both heating and cooling is recommended A comparison of logged data with start up and other annual data is useful as an indica tor of general equipment condition 5 Periodic lockouts alway...

Отзывы: