Dynamic Default Values
The fan staging dead bands have different default values based on the VFD enable setpoint.
When the VFD enable setpoint is changed, a set of default values for the fan staging dead
bands is loaded as follows:
VFD is Enabled
VFD is Disabled
Setpoint
Default
loaded (
o
F)
Setpoint
Default
loaded (
o
F)
Stage 1 On Deadband
8
Stage 2 On Deadband
5
Stage 2 On Deadband
10
Stage 3 On Deadband
8
Stage 3 On Deadband
11
Stage 4 On Deadband
10
Stage 4 On Deadband
12
Stage 5 On Deadband
8
Stage 5 On Deadband
13
Stage 6 On Deadband
8
Stage 6 On Deadband
13
Stage 7 On Deadband
8
Stage 7 On Deadband
13
Stage 8 On Deadband
8
Stage 8 On Deadband
13
Stage 2 Off Deadband
8
Stage 2 Off Deadband
20
Stage 3 Off Deadband
7
Stage 3 Off Deadband
16
Stage 4 Off Deadband
6
Stage 4 Off Deadband
11
Stage 5 Off Deadband
5
Stage 5 Off Deadband
8
Stage 6 Off Deadband
5
Stage 6 Off Deadband
8
Stage 7 Off Deadband
5
Stage 7 Off Deadband
8
Stage 8 Off Deadband
5
Stage 8 Off Deadband
8