24
OM
AGSD-1
Description Default
Range PW
Evap pressure offset
0
-10.0 to 10.0 psi
M
Cond pressure offset
0
-10.0 to 10.0 psi
M
Oil pressure offset
0
-10.0 to 10.0 psi
M
Suction temp offset
0
-5.0 to 5.0 deg
M
Discharge temp offset
0
-5.0 to 5.0 deg
M
Fans
Fan VFD enable
On
Off, On
M
Number of fans
6
6 to 9
M
Saturated Condenser Temp
Target Min
90.0 80.0-110.0
o
F M
Saturated Condenser Temp
Target Max
110.0 90.0-120.0
o
F M
Stage 1 On Deadband
5
1.0-20.0
o
F M
Stage 2 On Deadband
5
1-20
o
F M
Stage 3 On Deadband
8
1-20
o
F M
Stage 4 On Deadband
10
1-20
o
F M
Stage 5 On Deadband
8
1-20
o
F M
Stage 6-8 On Deadband
8
1-20
o
F M
Stage 2 Off Deadband
8
1-20
o
F M
Stage 3 Off Deadband
7
1-20
o
F M
Stage 4 Off Deadband
6
1-20
o
F M
Stage 5 Off Deadband
5
1-20
o
F M
Stage 6-8 Off Deadband
5
1-20
o
F M
VFD Max Speed
100%
90 to 110%
M
VFD Min Speed
25%
20 to 60%
M
Forced Fantrol 1
2
1 to number of fans
M
Forced Fantrol 2
3
1 to number of fans
M
Forced Fantrol 3
4
1 to number of fans
M
Auto Adjusted Ranges
Some settings have different ranges of adjustment based on other settings. For example, for
the chilled water leaving setpoint range (Cool LWT), if the “Cool” mode is selected, the
range is 40F to 60F. If “Cool w/Glycol” mode is selected, the range is automatically
adjusted to 25F to 60F.
Cool LWT
Mode Range
Unit Mode = Cool
40 to 60
o
F
Unit Mode = Cool w/Glycol
25 to 60
o
F
Evaporator Water Freeze
Mode Range
Unit Mode = Cool
36 to 42
o
F
Unit Mode = Cool w/Glycol, Ice w/ Glycol
15 to 42
o
F
Low Evaporator Pressure Inhibit
Mode Range
Unit Mode = Cool
28 to 45 Psig
Unit Mode = Cool w/Glycol, Ice w/ Glycol
0 to 45 Psig
Low Evaporator Pressure Unload
Mode Range
Unit Mode = Cool
26 to 45 Psig
Unit Mode = Cool w/Glycol, Ice w/ Glycol
0 to 45 Psig